F-Gas Regulation (EU) 2024/573
EU regulation controlling fluorinated greenhouse gases such as HFCs, PFCs and SF6; it sets leak-check, certification, labelling, recovery and phase-down obligations and replaced Regulation (EU) No 517/2014.
ODS Regulation (EC) 1005/2009
EU regulation controlling ozone-depleting substances including CFCs, HCFCs and halons; it restricts production, use, recovery and destruction of ODS such as R-22.
Irish F-Gas competent authority
The Environmental Protection Agency (EPA) is the competent authority in Ireland for enforcing F-Gas and ODS rules and for certification and reporting requirements.
F-Gas certification
A personal qualification required for activities such as leak checking, servicing, recovery and charging of equipment containing fluorinated greenhouse gases; it must be obtained through an accredited certification body.
HFC phase-down
An EU quota system that limits the total CO2e of HFCs placed on the market, reducing available quota over time to encourage lower-GWP alternatives.
F-Gas record retention
Operators must keep leak-check, refrigerant and repair records for at least five years and make them available to the competent authority on request.
Global Warming Potential (GWP)
The 100-year warming effect of one kilogram of a gas compared with one kilogram of CO2, whose GWP is 1; higher GWP means greater climate impact.
CO2e formula
Tonnes CO2e = refrigerant mass in kilograms multiplied by the refrigerant's GWP, divided by 1000; for example 1 kg R-410A with GWP 2088 equals 2.088 tCO2e.
R-410A GWP
R-410A has a 100-year GWP of 2088, so each kilogram released is equivalent to 2.088 tonnes of CO2.
R-404A GWP
R-404A has a 100-year GWP of 3922, so each kilogram released is equivalent to 3.922 tonnes of CO2.
Ozone Depletion Potential (ODP)
A relative measure of a substance's ability to destroy stratospheric ozone, with CFC-11 set at ODP 1.0; HFCs have ODP zero.
R-22 environmental properties
R-22 is an HCFC with ODP about 0.055 and GWP 1810; it depletes ozone and contributes to climate change, and its use is restricted.
TEWI
Total Equivalent Warming Impact: the sum of direct refrigerant emissions in CO2e and indirect CO2 emissions from the electrical energy used by the equipment over its life.
Leak check 5–50 tCO2e
Equipment containing 5 to 50 tonnes CO2e must be leak-checked at least every 12 months, or every 24 months if fitted with a leak detection system.
Leak check 50–500 tCO2e
Equipment containing more than 50 and less than 500 tonnes CO2e must be leak-checked at least every 6 months, or every 12 months with a leak detection system.
Leak check above 500 tCO2e
Equipment containing 500 tonnes CO2e or more must be leak-checked at least every 3 months, or every 6 months if fitted with a leak detection system.
Leak detection system threshold
A leak detection system is mandatory for equipment containing 500 tonnes CO2e or more; the system must be checked at least once every 12 months.
Post-repair leak check
After a leak is repaired, the operator must ensure the equipment is leak-checked again within 24 hours to confirm the repair is effective.
F-Gas record contents
Records must include refrigerant type and charge, quantities added, leak-check dates and results, repairs carried out, and details of the technician or company.
Hermetically sealed exemption
Hermetically sealed equipment containing less than 10 tonnes CO2e is exempt from periodic leak checks under EU F-Gas rules, but recovery and record rules still apply.
Refrigerant recovery
The collection of refrigerant from equipment into a suitable container so it can be reused, recycled, reclaimed or destroyed instead of being released.
Refrigerant recycling
Basic cleaning of recovered refrigerant, such as oil separation and filtration, for reuse; it does not restore the refrigerant to virgin product specification.
Refrigerant reclamation
Reprocessing recovered refrigerant to virgin specification, usually by an approved facility with laboratory analysis to verify purity before it is returned to the market.
No venting rule
It is prohibited to release fluorinated greenhouse gases or ODS to the atmosphere; refrigerant must be recovered before servicing, decommissioning or disposal.
Recovery cylinder filling
Recovery cylinders must be dedicated, labelled and filled by weight; the maximum filling ratio must never be exceeded to prevent hydraulic rupture.
Refrigerant mixing ban
Different refrigerants must never be mixed in a recovery cylinder; a mixture cannot be reclaimed as a single product and must be treated as waste.
Refrigerant PPE
Personal protective equipment for refrigerant work includes cold-insulating gloves, goggles or face shield and protective clothing to prevent frostbite and liquid splash injury.
Blend charging method
Zeotropic refrigerant blends must be charged as liquid from the cylinder to maintain the correct composition; charging as vapour can cause fractionation and poor performance.
Pressure test gas
Dry nitrogen (oxygen-free nitrogen) is used for pressure testing refrigeration systems; oxygen, air or other gases can cause fire or explosion and must never be used.
Evacuation target
A typical evacuation target is 500 microns, about 67 Pa; the system should hold the vacuum, as a rising pressure indicates moisture or a leak.
Flammable refrigerant precautions
For A2L or A3 refrigerants, remove ignition sources, use intrinsically safe tools and leak detectors, and ensure adequate ventilation to prevent flammable accumulation.
Decommissioning recovery
Before dismantling equipment, recover all refrigerant, isolate and purge the system with nitrogen, then label and remove the equipment for disposal.