Recovering R-32 from a Failed Split

IE F-Gas Category IV · Put your knowledge to work in context.

All case studies

Recovering R-32 from a Failed Split

An installer is replacing a 10-year-old 7 kW wall-mounted split in an apartment. The nameplate gives R-32, factory charge 1.15 kg, and the unit carries the A2L flammable refrigerant symbol. The van holds one recovery cylinder: a 12.3 litre cylinder marked 'R-410A' that was last used on an R-410A job and sits at 0 bar on the gauge. He has an A1-rated recovery machine, a manifold gauge set and standard hand tools. The pipework runs through a service void and the indoor unit is a metre from a gas hob. The building caretaker wants the old unit taken away with the general bulky waste 'because the gas is gone - it hasn't worked since March'. The cylinder's last test date is legible and in date.

1. Is recovery required given the charge is only 1.15 kg? Explain your reasoning and calculate the CO2e.

Read the worked answer

Calculation

  • 1.15 kg x GWP 675 (R-32) = 776 kg CO2e = 0.78 tonnes CO2e

What that means

  • At 0.78 t it is below the 5 t CO2e threshold, so no leak-checking duty and no F-gas log obligations attach to this equipment.
  • That does not mean the gas can be released. The deliberate release of fluorinated greenhouse gas into the atmosphere is prohibited regardless of charge size. There is no small-system exemption from the venting ban.

'It hasn't worked since March' That is exactly the trap. A unit that has stopped working may have lost most of its charge, or it may still hold liquid in the evaporator, the accumulator or the compressor sump. A sealed circuit does not care that the compressor has failed.

Consequences of cutting corners: brazing, cutting the pipework with a saw, or unbolting the flare connections on a system that still holds R-32 will vent it, and brazing a charged line can produce a blowtorch effect and toxic decomposition products. Recover before disconnecting, whatever the charge. Record the recovery and the quantity on the job sheet.

2. Can the R-410A recovery cylinder be used? What must be done first, and what are the risks of not doing it?

Read the worked answer

Not as it stands.

Why 0 bar is not empty A gauge reading 0 bar is reading gauge pressure; the cylinder still contains R-410A vapour at about 1 bar absolute. It is not evacuated, and it is marked for a different refrigerant.

What must be done first

  1. Recover the residual R-410A vapour into the R-410A reclaim stock, so the cylinder is genuinely empty and under vacuum.
  2. Re-label the cylinder for R-32 - contents, date, technician - before any R-32 goes into it.
  3. Check the cylinder's test date (in date here) and its general condition.
  4. Observe the fill limit: never exceed 80% of the cylinder's water capacity with liquid, and weigh the cylinder rather than relying on feel.

Risks of skipping it

  • Contamination: the mixture becomes an unidentified gas. It cannot be reclaimed to a specification and has to be destroyed, which is a cost to somebody.
  • Safety: R-32 is A2L (mildly flammable). Diluting it with an A1 gas does not make the resulting mixture predictably safe, and the cylinder can no longer be treated as either class.
  • Traceability: a cylinder whose label does not match its contents is the single most common way bad gas enters a system on the next job.

3. What are the safety issues specific to R-32 on this job, and what must happen to the refrigerant and the old unit?

Read the worked answer

Safety on this job

  • Flammability: R-32 is A2L. No smoking, no hot work, no grinder, no ignition sources within the work zone; ventilate the apartment, and remember the indoor unit is a metre from a gas hob.
  • Equipment rating: an A1-rated recovery machine is not automatically suitable for A2L. Confirm the machine is rated for A2L before connecting it, or use one that is.
  • Bonding and earthing: static is a real ignition route during recovery; bond the unit and the cylinder.
  • Cold burns: liquid R-32 boils at about -52 degrees Celsius at atmospheric pressure. Gloves and sealed goggles, and never trap liquid against skin.
  • Leak detection before and after: check the joint areas before brazing on the replacement, and pressure-test with OFN rather than refrigerant.

Refrigerant and equipment

  • Recovered R-32 is a single-component refrigerant and can be sent for reclamation; if not reclaimable, it goes for destruction. Either way, only through a permitted operator, with a record of the quantity and the destination.
  • The old unit is waste electrical and electronic equipment. It may only leave site once the refrigerant has been recovered, and it should travel with a handover note. It does not go into the general bulky waste, and the caretaker should be told so in writing.