OFTEC Oil Firing (OFT101/105E) study materials
OFTEC Oil Firing (OFT101/105E) study resources

OFTEC Oil Firing (OFT101/105E) cheat sheet

OFTEC Oil Firing (OFT101/105E) · Keep the key ideas within reach.

Quick reference

Health and Safety

  • COSHH applies to oil, kerosene fume, and combustion products; safety data sheets must be available before handling fuel.

  • Kerosene (Class C2) flash point is above 38 °C; it is not classified as highly flammable but vapour can still ignite at the burner.

  • Confined-space entry for tanks or flues requires a permit, atmospheric testing (O2, CO, flammable gas) and a rescue plan.

  • Manual handling: a 205-litre drum of kerosene weighs roughly 170-180 kg; two-person or mechanical handling is required.

  • Fuel oil can cause dermatitis; nitrile gloves and eye protection are minimum PPE for burner and nozzle work.

  • Isolate and lock off electrical supply before opening burner or control panel; prove dead with a tester.

  • Carbon monoxide is odourless; never commission or service a combustion appliance in a poorly ventilated space without a working CO alarm and personal monitor.

  • Reportable incidents under RIDDOR include specified injuries, over-7-day absences, and dangerous occurrences such as fires or explosions.

Quick reference

Legislation and Industry Standards

  • Building Regulations Part J (England and Wales) covers combustion appliances, oil storage, flues and ventilation; equivalent requirements apply in Scotland and Northern Ireland.

  • OFTEC registration covers three scopes: OFT101 (domestic pressure jet), OFT105E (domestic vaporising), plus tank installation and commissioning/ servicing where held.

  • BS 5410-1 covers domestic oil firing installation and maintenance; BS 5410-2 covers commercial/industrial.

  • Work on oil storage must comply with the Control of Pollution (Oil Storage) Regulations where applicable (England, Scotland, Wales, NI thresholds differ).

  • Gas Safety style notification does not apply to oil, but building control notification is required for controlled work such as replacing a boiler or installing a new flue.

  • Competent person self-certification schemes (e.g. OFTEC) allow registered businesses to notify controlled work without separate building control application.

  • Manufacturer's instructions must be followed; deviation requires documented justification and must not reduce safety.

  • The Pressure Systems Safety Regulations apply to pressure jet burners only where the fuel pump/pressure system falls in scope; domestic burner pumps are typically exempt but must be maintained.

Quick reference

Oil Storage

  • Single-skin domestic tanks require a bund or secondary containment of 110% of tank capacity where oil storage regulations apply.

  • Tank base must be non-combustible, level, and capable of supporting the full tank weight (kerosene ~0.82 kg/litre).

  • Minimum separation from a non-fire-rated boundary is 1.8 m for tanks up to 3500 litres; fire-rated walls allow reduced separation.

  • Tank outlet should be at least 100 mm above the base to allow sludge and water to settle below the draw-off point.

  • Fill point must be within sight of the delivery hose and fitted with a lockable cap, overfill prevention and a label stating fuel type and capacity.

  • Vent pipe sizing: typically 50 mm minimum for domestic tanks, terminating with a flame arrestor and turned down, above flood level.

  • Tanks should be sited to allow inspection of all sides and access for filling; sight gauge or contents indicator must be visible.

  • Plastic tanks must be protected from UV degradation and supported across their full base; steel tanks require internal and external corrosion protection.

Quick reference

Supply, Fuel Properties and Pipework

  • Kerosene (C2, 28-second oil) calorific value approx 46.2 MJ/kg; gas oil (C1, 35-second oil) approx 45.5 MJ/kg.

  • Kerosene density approx 0.82 kg/litre at 15 °C; gas oil approx 0.85 kg/litre.

  • Viscosity determines atomisation: kerosene ~1.5-2.5 cSt at 40 °C, gas oil ~3-6 cSt; preheaters are used for heavier grades.

  • Two-pipe (return) supply is used where the tank outlet is below the burner or where lift is marginal; single-pipe uses a bypass plug in the pump.

  • Oil line should be continuously rising from tank to burner where possible to allow air to vent back to tank.

  • Maximum suction lift for a single-stage pump is typically around 3.5 m with a two-pipe system; consult pump data for exact limits.

  • Pipework should be in annealed copper or approved plastic-coated steel, protected from mechanical damage, with accessible isolation valve at the tank.

  • Fire valve: a fusible-head or capillary fire valve must be fitted, with the sensor located above the burner and the valve closing on temperature rise (typically 90-95 °C).

Quick reference

Oil Fired Appliances: Types and Construction

  • Pressure jet burners atomise fuel at 7-14 bar through a nozzle; vaporising (pot) burners rely on heat to vaporise kerosene at atmospheric pressure.

  • Vaporising burners are kerosene-only; gas oil will not vaporise reliably and causes coking.

  • Pressure jet boilers are typically rated 15-70 kW domestic; output is set by nozzle size, pump pressure and combustion air.

  • Heat exchanger materials: cast iron for conventional boilers, stainless steel or aluminium for condensing; condensing boilers recover latent heat below dew point (~55 °C return).

  • Vaporising appliances include range cookers, room heaters and some small boilers; they require a natural draught flue and constant level oil control.

  • Combustion chamber and baffles must be correctly positioned; missing or misplaced baffles reduce efficiency and raise flue gas temperature.

  • Balanced-flue and room-sealed oil appliances take combustion air directly from outside, reducing ventilation requirements.

  • Oil-fired condensing boilers require a condensate drain with a trap and frost protection; the plume must be sited away from windows and boundaries.

Quick reference

Combustion

  • Stoichiometric combustion of kerosene: approx 14.4 kg air per kg fuel (about 12 m³ air per litre of kerosene).

  • CO2 in flue gas indicates excess air: typical pressure jet target 11.5-12.5% CO2, vaporising 9-11%.

  • Smoke number target for pressure jet is 0-1 (Bacharach scale); anything above 2 indicates poor atomisation or air imbalance.

  • Flue gas temperature for non-condensing oil boilers typically 180-250 °C; high temperature with low CO2 suggests excess air or fouled heat exchanger.

  • CO should be below 100 ppm (air-free) for a well-set pressure jet appliance; rising CO with falling CO2 suggests air starvation or blocked flue.

  • Excess air (lambda) of 1.15-1.25 gives clean combustion with acceptable efficiency for pressure jet burners.

  • Flame colour: correct pressure jet flame is orange-yellow with a bright incandescent core; a smoky or long lazy flame indicates under-aeration or worn nozzle.

  • Combustion efficiency is calculated from flue temperature and CO2/O2; a 20 °C reduction in flue temperature improves efficiency by roughly 1%.

Quick reference

Burner Components and Settings

  • Nozzle flow rate is rated in US gallons per hour at 7 bar (100 psi); flow varies approximately with square root of pressure.

  • Nozzle spray angles: 60° for narrow chambers, 80° for most domestic boilers, 45° for wide/low chambers; hollow cone for pressure jet boilers.

  • Electrode gap typically 3-4 mm with tips 2-3 mm forward of the nozzle face; incorrect gap causes ignition failure or delayed ignition.

  • Pump pressure adjustment via pressure regulator screw; typical domestic setting 8-10 bar (higher for some nozzles).

  • Photocell (cad cell) detects flame; it must be clean and correctly aligned, with resistance falling when flame is present.

  • Solenoid valve on the pump controls oil supply; it opens on demand and closes on shutdown to prevent after-drip.

  • Blast tube and turbulator/air swirl plate position must match the manufacturer's dimensions; incorrect insertion depth affects flame shape.

  • Combustion air damper setting is adjusted with a CO2/smoke test to achieve the specified CO2 and smoke number at the correct draught.

Quick reference

Installation of Appliances and Systems

  • Boiler must be mounted on a non-combustible base, level, with manufacturer's clearances to combustible materials maintained.

  • System design: sealed systems require expansion vessel, pressure relief valve (typically 3 bar), and filling loop; open vented systems require feed and expansion tank.

  • Pipe sizing for heating circuits based on flow rate and allowable pressure drop; typically 0.5-1.0 m/s velocity for domestic.

  • Oil line isolation valve must be accessible and labelled; fire valve must be fitted upstream of the burner and operate independently of the electrical supply.

  • Condensing boilers require a condensate drain of at least 22 mm ID with a trap providing a water seal (typically 75 mm) and frost protection.

  • System must be flushed and inhibited before commissioning; sludge and flux residues cause premature failure and block heat exchangers.

  • Boiler house/compartment ventilation: high and low level openings sized to manufacturer's requirements; typically free area based on appliance output.

  • Electrical supply to the appliance must be via a double-pole isolator with a 3 A fuse (or as specified) and RCD protection where required.

Quick reference

Flues, Ventilation and Combustion Air

  • Flue draught for natural draught oil appliances typically 0.05-0.15 mbar (5-15 Pa) measured at the test point.

  • Chimney/flue must terminate above roof level per Part J: typically 2.3 m above a flat roof or 0.6 m above the ridge of a pitched roof.

  • Flue terminal must be at least 600 mm from an opening window, and clear of combustible materials and boundaries per manufacturer.

  • Flue must be suitable for the fuel and appliance type: stainless steel or vitreous enamel for conventional, plastic or approved condensing flue for condensing.

  • Combustion air: open-flue appliances require permanent ventilation; typical domestic requirement is based on kW input plus a fixed allowance (consult BS 5410).

  • Draught stabiliser (barometric damper) maintains constant draught; must be fitted where flue draught varies or exceeds manufacturer's limit.

  • Flue must be swept and inspected; a blocked flue causes CO rise and flame failure. Flue integrity test with smoke pellet confirms draught and no leakage.

  • Room-sealed/balanced flue terminals must be sited to avoid recirculation of products and comply with manufacturer's terminal clearances.

Quick reference

Commissioning, Testing and Handover

  • Commissioning sequence: pre-check installation, fill and vent oil line, set pump pressure, adjust air for correct CO2 and smoke, then measure CO and flue temperature.

  • Oil line must be bled at the pump until clear bubble-free oil flows before attempting ignition.

  • Combustion analysis: record CO2, O2, CO, flue temperature, smoke number, and draught; compare to manufacturer's data.

  • Nozzle output verification: measure oil flow over a timed period (e.g. 1 minute) at set pressure to confirm rated output.

  • Handover pack: installation/commissioning certificate, benchmark/checklist, user instructions, fuel type, and servicing schedule.

  • Building control notification or competent person self-certification must be completed and copy provided to the customer.

  • Electrical checks: polarity, earth continuity, RCD trip test, and correct fuse rating at the isolator.

  • Record all settings (nozzle size, pump pressure, CO2, smoke number) on the appliance/service label and in documentation.

Quick reference

Servicing, Fault Diagnosis and Repair

  • Service interval for oil appliances is typically annual; includes cleaning heat exchanger, baffles, burner head, electrodes, photocell and nozzle replacement.

  • Nozzle should be replaced at every service; never clean and refit, as the spray pattern cannot be restored.

  • Common faults: no ignition (electrodes, transformer, photocell), lockout (photocell dirty, flame failure, air in line), pulsating flame (water in oil, incorrect nozzle, air).

  • Lockout on start-up: check oil supply, electrode gap, photocell cleanliness, and control box reset - do not repeatedly reset without finding cause.

  • Smoky flame: check nozzle size/type, pump pressure, air damper setting, and flue/combustion air blockage.

  • Water in tank causes flame pulsation and lockout; draw off from tank bottom and check for water in filter.

  • Combustion analysis before and after service demonstrates improvement and confirms safe operation; record results.

  • Fault finding sequence: verify electrical supply and controls, then oil supply and pressure, then ignition components, then combustion settings.

Quick reference

Electrical Controls, Safety Devices and Wiring

  • Control box sequence: pre-purge (fan and air), ignition, oil valve open, flame proven by photocell, then run; on flame failure, lockout after safety time (typically 5-15 s).

  • Photocell resistance: high (dark) = high resistance; low resistance when flame detected; check with meter and clean lens.

  • Fire valve types: fusible head (operates at ~90 °C) and capillary (remote sensor); must be wired to close oil supply independent of electrical power.

  • Overheat thermostat (limit stat) on boiler must be manual reset and set above the control thermostat; it interrupts the burner on overheat.

  • Wiring must comply with BS 7671; oil appliances typically supplied via a fused spur with 3 A fuse and double-pole isolation.

  • Safety devices must not be bypassed; any bypass found must be corrected and recorded as a defect.

  • Solenoid valve and photocell circuits are low voltage on many burners; check control box terminal diagram for correct connections.

  • Annual electrical checks include earth continuity, insulation resistance, and functional test of overheat stat, fire valve and lockout.

Quick reference

Health and Safety (additional reference)

  • COSHH assessment required for all chemicals used (fuel, cleaning agents, inhibitors); safety data sheets on site.

  • Personal protective equipment: nitrile gloves, eye protection, and suitable footwear for fuel handling and servicing.

  • Working at height for flue terminals and tank inspection: use ladders safely, three points of contact, or scaffold for extended work.

  • Electrical safety: isolate and prove dead before work; use RCD-protected tools where required.

  • Fire precautions: no smoking, no naked flames, extinguisher suitable for fuel fires (foam/dry powder) available.

  • Waste oil and contaminated materials must be disposed of via licensed waste carrier with waste transfer note.

  • Report accidents and dangerous occurrences per RIDDOR; keep accident book.

  • Lone working: risk assessment, communication plan, and first aid arrangements must be in place.

Quick reference

Legislation and Industry Standards (additional reference)

  • Building Regulations Part J requires notification for replacement appliances and new flues; competent person schemes allow self-certification.

  • BS 5410-1 is the primary installation standard for domestic oil firing; BS 5410-2 for commercial.

  • Oil Storage Regulations apply in England (above 200 litres at most premises), Scotland (above 200 litres), Wales and NI with different thresholds.

  • Manufacturer's instructions are the primary source for appliance-specific settings and clearances.

  • OFTEC registration requires periodic assessment and continuing professional development.

  • Waste transfer and disposal of oil-contaminated waste must comply with environmental legislation.

  • Electrical installation must comply with BS 7671 (IET Wiring Regulations).

  • Gas/oil interlock and notification requirements apply where multiple fuels are present.

Quick reference

Oil Storage (additional reference)

  • Bund capacity must be 110% of the largest tank's capacity where multiple tanks share a bund.

  • Tank must be sited on a base extending at least 300 mm beyond the tank footprint and impermeable to oil.

  • Fill point and vent must be sited so spillage does not enter drains or watercourses; drip tray under fill point recommended.

  • Tank labelling: fuel type, capacity, and 'No smoking' / 'Flammable' signage.

  • Inspection: check for corrosion, splits, bund integrity, and clear sight gauge at each service visit.

  • Pipework from tank to appliance should be protected and not buried without protection; use approved sleeving where passing through walls.

  • Tank replacement requires disposal of old tank via licensed waste contractor and notification where applicable.

  • Plastic tanks have a limited design life; check manufacturer's guidance and inspect for UV degradation.

Quick reference

Supply, Fuel Properties and Pipework (additional reference)

  • Kerosene is the standard domestic fuel; gas oil (35-second) is used in some larger or commercial appliances.

  • Fuel oil must be clean and water-free; filters should be fitted at tank outlet and at burner.

  • Pipework should be sized to maintain adequate flow at the burner; undersized pipe causes pressure loss and air ingress.

  • Two-pipe system returns surplus oil to tank; single-pipe requires bypass plug and is used where lift is within pump limits.

  • Fire valve must be fitted at the tank or where pipe enters the building, with sensor above the burner.

  • Oil line should be pressure-tested after installation; typically 10 bar for 10 minutes on pressure systems, or as specified.

  • Copper pipe must be protected from contact with mortar/cement which causes corrosion; use sleeving.

  • De-aeration: air in oil line causes lockout; bleed at pump and check for loose connections.

Quick reference

Appliances (additional reference)

  • Pressure jet burner components: pump, nozzle, electrodes, transformer, photocell, control box, blast tube, fan, air damper.

  • Vaporising burner components: constant level valve, wick or pot, carburettor, flame ring, and natural draught flue.

  • Condensing boilers require a condensate trap and drain; the plume is visible and must be sited per manufacturer.

  • Boiler output must match heat loss; oversizing causes short cycling and reduced efficiency.

  • Heat exchanger cleaning restores efficiency; soot deposits act as insulation and raise flue temperature.

  • Baffles must be refitted in correct order after cleaning; incorrect fitting causes hot spots and efficiency loss.

  • Combustion chamber insulation (if fitted) must be intact; damaged insulation affects flame and efficiency.

  • Appliance data plate gives model, output, fuel type, nozzle size, and pump pressure - always check before servicing.

Quick reference

Combustion (additional reference)

  • Air-free CO measurement corrects for excess air and is the true indicator of incomplete combustion.

  • CO2 reading falls with excess air; a rising CO2 with falling O2 indicates reducing excess air.

  • Smoke pump (Bacharach) test: draw flue gas through filter paper and compare stain to scale 0-9.

  • Flue draught measured with a manometer at the appliance test point; too much draught cools the flue and reduces efficiency.

  • Combustion efficiency tables use flue temperature and CO2 (or O2) to derive efficiency; typical domestic target 85-90% net for non-condensing.

  • Incomplete combustion produces CO; causes include air starvation, blocked flue, incorrect nozzle, and flame impingement.

  • Excess air increases stack losses; too little air produces CO and smoke - aim for the manufacturer's CO2 with smoke 0-1.

  • Ambient CO testing around the appliance confirms no products escaping into the room.

Quick reference

Burner Settings (additional reference)

  • Nozzle markings: flow rate (gph), spray angle (e.g. 80°), and spray pattern (hollow/solid).

  • Pump pressure gauge fitted at pump test point; adjust to manufacturer's specification (commonly 8-10 bar domestic).

  • Electrode position: tips set to manufacturer's gauge; typically 3-4 mm gap and 2-3 mm ahead of nozzle.

  • Photocell must be clean and aligned with flame; test by covering and confirming lockout.

  • Air damper adjustment affects CO2 and smoke; set after pump pressure and nozzle are correct.

  • Turbulator/air swirl position affects flame shape; set per manufacturer's dimension from blast tube.

  • Ignition transformer output typically 10-12 kV; check for spark at electrodes with tester.

  • Solenoid valve and pump coupling must be secure; loose coupling causes erratic oil supply.

Quick reference

Installation (additional reference)

  • Boiler clearances to combustibles per manufacturer; typically 50-100 mm sides, more at front for access.

  • Sealed system components: expansion vessel pre-charge, pressure relief valve, and pressure gauge.

  • Condensate drain must fall continuously to a suitable discharge point; trap must be primed.

  • System flush and inhibitor required before commissioning; record inhibitor concentration.

  • Oil line fire valve and isolation valve must be accessible and labelled.

  • Electrical supply: double-pole isolator, correct fuse, and RCD where required.

  • Ventilation openings must be permanent and not obstructed; size per manufacturer and BS 5410.

  • Commissioning certificate and handover documentation must be completed and given to the customer.

Quick reference

Flues and Ventilation (additional reference)

  • Flue terminal clearances: 600 mm from openings, 300 mm from combustible materials (check manufacturer).

  • Chimney height: minimum per Part J; typically 2.3 m above flat roof or 0.6 m above ridge.

  • Draught stabiliser fitted where flue draught exceeds manufacturer's limit; maintains constant draught.

  • Flue integrity test: smoke pellet confirms draught and no leakage; visual inspection of joints.

  • Combustion air openings sized for appliance input; high and low level where required.

  • Room-sealed appliances take air directly; terminal must avoid recirculation.

  • Flue must be swept and inspected at service; soot and debris cause CO and efficiency loss.

  • Condensing flue must be suitable for wet products; plastic or approved stainless.

Quick reference

Commissioning (additional reference)

  • Bleed oil line at pump until bubble-free before ignition.

  • Set pump pressure and nozzle per manufacturer; verify output by timed flow measurement.

  • Adjust air for correct CO2 and smoke number; record readings.

  • Measure CO, flue temperature, and draught; compare to manufacturer's data.

  • Electrical checks: polarity, earth continuity, RCD trip, fuse rating.

  • Complete commissioning certificate and service label; record all settings.

  • Handover: user instructions, fuel type, servicing schedule, and notification.

  • Demonstrate safe operation and explain controls to the customer.

Quick reference

Servicing and Fault Diagnosis (additional reference)

  • Annual service: clean heat exchanger, baffles, burner head, electrodes, photocell; replace nozzle.

  • Nozzle replacement every service; never clean and refit.

  • Lockout causes: oil supply, electrode gap, photocell, control box, air in line.

  • Smoky flame: nozzle, pump pressure, air damper, flue blockage.

  • Water in oil causes pulsation and lockout; drain tank and check filter.

  • Combustion analysis before and after service to confirm improvement.

  • Fault sequence: electrical, oil supply, ignition, combustion settings.

  • Record defects and advise customer; do not leave unsafe appliance in operation.

Quick reference

Electrical Controls (additional reference)

  • Control box sequence: pre-purge, ignition, oil valve, flame proven, run; lockout on failure.

  • Photocell resistance changes with flame; clean and test.

  • Fire valve: fusible head or capillary; closes oil supply on temperature rise.

  • Overheat thermostat: manual reset, interrupts burner on overheat.

  • Wiring per BS 7671; fused spur with 3 A fuse and double-pole isolation.

  • Never bypass safety devices; correct and record any bypass found.

  • Check control box terminal diagram for correct connections.

  • Annual electrical checks: earth continuity, insulation resistance, functional tests.

Quick reference

Health and Safety (further reference)

  • COSHH assessment for fuel and chemicals; safety data sheets on site.

  • PPE: nitrile gloves, eye protection, suitable footwear.

  • Working at height: safe ladder use or scaffold for extended work.

  • Electrical safety: isolate and prove dead; RCD-protected tools.

  • Fire precautions: extinguisher suitable for fuel fires; no smoking.

  • Waste oil disposal via licensed carrier with waste transfer note.

  • RIDDOR reporting for accidents and dangerous occurrences.

  • Lone working risk assessment and communication plan.

Quick reference

Legislation (further reference)

  • Part J requires notification for replacement appliances and new flues; competent person self-certification.

  • BS 5410-1 domestic; BS 5410-2 commercial.

  • Oil Storage Regulations thresholds differ by nation.

  • Manufacturer's instructions primary for settings and clearances.

  • OFTEC registration requires periodic assessment and CPD.

  • Waste transfer and disposal per environmental legislation.

  • Electrical installation per BS 7671.

  • Multi-fuel interlock and notification requirements.

Quick reference

Oil Storage (further reference)

  • Bund 110% of largest tank where multiple tanks share.

  • Base extends 300 mm beyond tank footprint, impermeable.

  • Fill point and vent sited to avoid drains/watercourses; drip tray.

  • Labelling: fuel type, capacity, flammable signage.

  • Inspection: corrosion, splits, bund integrity, sight gauge.

  • Pipework protected and sleeved through walls.

  • Tank replacement via licensed waste contractor and notification.

  • Plastic tank design life and UV inspection.

Quick reference

Fuel Properties (further reference)

  • Kerosene standard domestic; gas oil for larger/commercial.

  • Fuel must be clean and water-free; filters at tank and burner.

  • Pipe sizing to maintain flow; undersized causes pressure loss and air.

  • Two-pipe returns surplus; single-pipe with bypass plug within lift limits.

  • Fire valve at tank or entry point, sensor above burner.

  • Pressure test oil line after installation.

  • Copper protected from mortar/cement; use sleeving.

  • Bleed at pump; check for loose connections.

Quick reference

Appliances (further reference)

  • Pressure jet components: pump, nozzle, electrodes, transformer, photocell, control box, blast tube, fan, damper.

  • Vaporising components: constant level valve, wick/pot, carburettor, flame ring, natural draught flue.

  • Condensing requires condensate trap and drain; plume siting per manufacturer.

  • Output match to heat loss; oversizing causes short cycling.

  • Heat exchanger cleaning restores efficiency; soot insulates.

  • Baffles refitted in correct order.

  • Combustion chamber insulation intact.

  • Data plate gives model, output, fuel, nozzle, pressure.

Quick reference

Combustion (further reference)

  • Air-free CO corrects for excess air; true incomplete combustion indicator.

  • CO2 falls with excess air; rising CO2 with falling O2 indicates reducing excess air.

  • Smoke pump test: stain compared to 0-9 scale.

  • Flue draught measured with manometer; too much cools flue.

  • Efficiency from flue temperature and CO2/O2; target 85-90% net non-condensing.

  • Incomplete combustion causes: air starvation, blocked flue, wrong nozzle, impingement.

  • Excess air increases stack losses; too little causes CO and smoke.

  • Ambient CO test confirms no escape into room.

Quick reference

Burner Settings (further reference)

  • Nozzle markings: flow (gph), angle, pattern.

  • Pump pressure gauge at test point; 8-10 bar domestic typical.

  • Electrode gap 3-4 mm, tips 2-3 mm ahead of nozzle.

  • Photocell clean and aligned; test by covering for lockout.

  • Air damper set after pressure and nozzle correct.

  • Turbulator position per manufacturer's dimension.

  • Transformer output 10-12 kV; check spark.

  • Solenoid and coupling secure; loose causes erratic supply.

Quick reference

Installation (further reference)

  • Clearances to combustibles per manufacturer; access at front.

  • Sealed system: expansion vessel, PRV, pressure gauge.

  • Condensate drain falls continuously; trap primed.

  • Flush and inhibitor before commissioning; record concentration.

  • Fire valve and isolation valve accessible and labelled.

  • Electrical: double-pole isolator, correct fuse, RCD.

  • Ventilation permanent and unobstructed per BS 5410.

  • Commissioning certificate and handover documentation.

Quick reference

Flues and Ventilation (further reference)

  • Terminal clearances: 600 mm openings, 300 mm combustibles (check manufacturer).

  • Chimney height per Part J: 2.3 m flat roof, 0.6 m above ridge.

  • Draught stabiliser where draught exceeds limit.

  • Smoke pellet test for draught and leakage.

  • Combustion air openings per input; high and low level.

  • Room-sealed terminal avoids recirculation.

  • Sweep and inspect flue at service.

  • Condensing flue suitable for wet products.

Quick reference

Commissioning (further reference)

  • Bleed oil line bubble-free before ignition.

  • Set pressure and nozzle; verify output by timed flow.

  • Adjust air for CO2 and smoke; record.

  • Measure CO, flue temperature, draught.

  • Electrical checks: polarity, earth, RCD, fuse.

  • Complete certificate and service label.

  • Handover instructions, fuel, schedule, notification.

  • Demonstrate safe operation to customer.

Quick reference

Servicing (further reference)

  • Annual service: clean heat exchanger, baffles, burner, electrodes, photocell; replace nozzle.

  • Nozzle replaced every service.

  • Lockout causes: oil supply, electrode gap, photocell, control box, air.

  • Smoky flame: nozzle, pressure, damper, flue.

  • Water in oil: pulsation and lockout; drain and filter.

  • Combustion analysis before/after service.

  • Fault sequence: electrical, oil, ignition, combustion.

  • Record defects; do not leave unsafe appliance.

Quick reference

Electrical Controls (further reference)

  • Control sequence: pre-purge, ignition, oil valve, flame proven, run; lockout on failure.

  • Photocell resistance changes with flame; clean and test.

  • Fire valve: fusible or capillary; closes oil on temperature rise.

  • Overheat thermostat manual reset; interrupts burner.

  • BS 7671 wiring; fused spur 3 A, double-pole isolation.

  • Never bypass safety devices; correct and record.

  • Check control box terminal diagram.

  • Annual checks: earth, insulation, functional tests.