OFTEC Oil Firing (OFT101/105E) flashcards
OFTEC Oil Firing (OFT101/105E) · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Kerosene flash point
- Kerosene has a flash point above 38 °C, classifying it as Class C2. It is not highly flammable but its vapour can ignite at the burner under the right conditions.
- Stoichiometric air requirement
- Complete combustion of kerosene requires approximately 14.4 kg of air per kg of fuel, equivalent to about 12 cubic metres of air per litre of kerosene.
- Target CO2 pressure jet
- A correctly set domestic pressure jet burner typically produces 11.5-12.5% CO2 in the flue gas, with a smoke number of 0-1 on the Bacharach scale.
- Nozzle flow rating
- Nozzle flow is rated in US gallons per hour at 7 bar (100 psi). Actual flow varies approximately with the square root of the pump pressure ratio.
- Electrode gap setting
- Pressure jet electrodes are typically set with a 3-4 mm gap and tips positioned 2-3 mm forward of the nozzle face, per the manufacturer's gauge.
- Photocell function
- The photocell (cad cell) detects flame presence. Its resistance is high in darkness and falls when flame is detected, proving combustion to the control box.
- Control box lockout time
- On flame failure the control box locks out after a safety time, typically 5-15 seconds, shutting the oil solenoid and requiring manual reset.
- Fire valve operation
- A fire valve closes the oil supply on temperature rise, using either a fusible head (about 90 °C) or a capillary sensor located above the burner.
- Bund capacity requirement
- Where oil storage regulations apply, a bund or secondary containment must hold 110% of the largest tank's capacity, or 110% of the total where tanks share a bund.
- Tank outlet height
- The tank draw-off outlet should be at least 100 mm above the tank base so that water and sludge settle below the outlet and are not drawn into the line.
- Flue terminal clearance
- A flue terminal must be at least 600 mm from an opening window and clear of combustible materials, with exact clearances taken from the manufacturer's instructions.
- Chimney termination height
- Under Part J a chimney should terminate at least 2.3 m above a flat roof or 0.6 m above the ridge of a pitched roof, per the applicable diagram.
- Draught stabiliser purpose
- A barometric draught stabiliser maintains constant flue draught where natural draught varies or exceeds the manufacturer's limit, preventing excess air and efficiency loss.
- Condensate trap requirement
- Oil condensing boilers need a condensate drain of at least 22 mm with a trap giving a water seal, typically 75 mm, plus frost protection for the discharge.
- Sealed system components
- A sealed heating system requires an expansion vessel, a pressure relief valve typically set at 3 bar, a pressure gauge, and a filling loop.
- Annual service scope
- An annual oil service includes cleaning the heat exchanger, baffles, burner head, electrodes and photocell, plus replacing the nozzle and recording combustion readings.
- Nozzle replacement rule
- The nozzle must be replaced at every service and never cleaned and refitted, because the precision spray pattern cannot be restored once worn or blocked.
- Lockout fault causes
- Common lockout causes include air in the oil line, incorrect electrode gap, a dirty photocell, a faulty control box, or loss of oil supply.
- Water in oil symptom
- Water contamination in the tank causes flame pulsation and repeated lockout. Drain water from the tank bottom and check the oil filter for water.
- Combustion efficiency factors
- Combustion efficiency is derived from flue gas temperature and CO2 or O2. A 20 °C reduction in flue temperature improves efficiency by roughly 1%.
- Air-free CO measurement
- Air-free CO corrects the measured CO for excess air and is the true indicator of incomplete combustion; a well-set pressure jet should be below 100 ppm.
- Two-pipe oil supply
- A two-pipe system returns surplus oil to the tank and is used where the tank outlet is below the burner or suction lift is marginal.
- Single-pipe bypass plug
- A single-pipe supply requires a bypass plug fitted in the pump so surplus oil recirculates internally; it is used where lift is within the pump's limits.
- Pressure jet atomisation
- A pressure jet burner atomises fuel at 7-14 bar through a nozzle; domestic pumps are commonly set at 8-10 bar depending on the nozzle specification.
- Vaporising burner fuel
- Vaporising (pot) burners rely on heat to vaporise fuel at atmospheric pressure and must use kerosene; gas oil will not vaporise reliably and causes coking.
- Combustion air ventilation
- Open-flue oil appliances require permanent high and low level ventilation sized to the appliance input per BS 5410 and the manufacturer's instructions.
- Overheat thermostat
- The overheat (limit) thermostat is manual reset and set above the control thermostat; it interrupts the burner on overheat and must not be bypassed.
- Electrical supply requirement
- Oil appliances are typically supplied via a fused spur with a 3 A fuse and a double-pole isolator, wired to BS 7671 with RCD protection where required.
- COSHH fuel requirement
- COSHH requires a risk assessment and safety data sheets for fuel and chemicals used on site, with suitable controls and PPE specified for handling.
- Manual handling drum weight
- A 205-litre drum of kerosene weighs roughly 170-180 kg, so mechanical assistance or a two-person lift is required for handling.
- Commissioning sequence
- Commissioning order: pre-check installation, fill and vent the oil line, set pump pressure, adjust air for CO2 and smoke, then measure CO and flue temperature.
- Handover documentation
- Handover must include the commissioning certificate, benchmark or checklist, user instructions, fuel type, servicing schedule, and building control notification.