Oil Storage

What the questions test

Storage questions focus on integrity, containment, siting and protection. You need to know the features of a compliant tank installation and the reasons behind each feature.

Key concepts

  • Tank types: single-skin, integrally bunded, and separately bunded. Bunding capacity is normally 110% of the tank's capacity so a full loss is contained.
  • Materials: steel tanks need internal and external protection against corrosion; plastic tanks need UV stability and support on a level, load-bearing base.
  • Siting: distance from buildings, boundaries, drains, and sources of ignition; protection from vehicle impact; access for filling and inspection.
  • Fill point and vent: fill pipe sized and labelled, with a secure, lockable fill point; vent terminating safely, sized to the fill rate, with flame arrestor where required and screened against insects.
  • Pipework: oil supply lines protected, fire valves fitted where required, and bottom-outlet arrangements understood.
  • Overfill prevention, contents gauges, and leak detection.
  • Pollution prevention: sight gauges must not be of the unprotected glass-tube type; drip trays under fill points.

Traps in questions

  • Confusing tank capacity with bund capacity (bund is 110% of tank, not 110% of the fill volume).
  • Forgetting that a vent must not terminate where vapour can enter a building or reach an ignition source.
  • Missing the requirement for a fire valve on the supply line.
  • Assuming a plastic tank needs no base preparation.

Worked example

A 1,000 litre tank needs a bund. Rule of thumb: bund capacity = 1.1 × 1,000 = 1,100 litres, and the bund must not contain a drain valve that could release spilled oil. If a question offers 1,000 litres as the answer, it is the classic distractor.