OFTEC Oil Firing (OFT101/105E) study materials
OFTEC Oil Firing (OFT101/105E) study resources

OFTEC Oil Firing (OFT101/105E): Supply and Fuel Properties

OFTEC Oil Firing (OFT101/105E) · Work through your exam, one topic at a time.

All guide sections

Supply and Fuel Properties

Fuel properties you must know

  • Kerosene (28-second oil) - the standard domestic heating oil. Low sulphur, clean burning, suitable for pressure-jet burners.
  • Gas oil (35-second oil) - heavier, used in some larger or older appliances and commercial plant.
  • Flash point, viscosity, calorific value, sulphur content, cloud point and pour point, and waxing behaviour at low temperature.
  • Specific gravity and why it matters for gauging and for detecting contamination.

The supply system

  • Gravity feed from a tank above the burner, versus two-pipe (sub-gravity) supply with a lift and a return.
  • Top outlet with a dip pipe versus bottom outlet, and the role of the fire valve and filter.
  • Pipe sizing depends on flow rate, length, lift and fittings; undersized pipe causes pump cavitation and erratic running.
  • De-aeration: two-pipe systems return air and excess oil to the tank; single-pipe systems rely on bleeds.
  • Filters and water traps protect the nozzle and pump; water in oil causes flame failure and corrosion.

Traps in questions

  • Mixing up the two oil grades by their second (viscosity) number.
  • Forgetting that a lift reduces available pump suction and may require a two-pipe arrangement.
  • Assuming any pipe diameter will do - length and fittings count.
  • Overlooking that air leaks on the suction side cause the same symptoms as a blocked filter.

Worked example

A burner runs and then locks out after a few minutes, with a clear filter and good tank level. Rule of thumb: suspect air on the suction line before condemning the pump. Check joints, the fire valve and the dip pipe connection; air ingress shows as a frothy sight-glass or repeated bleeds.