OFTEC Oil Firing (OFT101/105E): Burner Components and Settings

OFTEC Oil Firing (OFT101/105E) · Work through your exam, one topic at a time.

All guide sections

Burner Components and Settings

The pressure-jet burner, part by part

  • Pump - draws oil, raises pressure, and contains the pressure regulating valve and solenoid.
  • Nozzle - sets the flow rate and spray pattern; rated in US gallons per hour at a stated pressure (commonly 100 psi / 7 bar).
  • Electrodes - set to the manufacturer's gap and position relative to the nozzle.
  • Blast tube and turbulator/air guide - shape the air/oil mixing.
  • Fan and air damper - set the combustion air; damper position affects CO₂ and smoke.
  • Control box - runs the sequence and provides lockout; flame detection by photocell (or flame sensor on some types).
  • Solenoid valve - opens to admit oil at the right point in the sequence.

Settings that matter

  • Pump pressure - affects atomisation and flow; raising pressure increases flow through the same nozzle.
  • Electrode gap and position - too wide or wrongly placed causes poor ignition; too close can carbon up.
  • Nozzle selection - flow rate, spray angle and pattern must match the appliance.
  • Air damper - the main efficiency adjustment in service.
  • Photocell - must see the flame but not be fooled by stray light.

Traps in questions

  • Assuming a bigger nozzle always means more heat - it may over-fire the appliance and soot the flue.
  • Forgetting that nozzle flow is rated at a specific pressure.
  • Mixing up electrode gap with nozzle position.
  • Overlooking a dirty photocell as a lockout cause.

Worked example

A burner locks out with a good flame that dies after a few seconds. Rule of thumb: clean the photocell and check it sees flame before touching the pump. A sooted or misaligned photocell gives exactly this signature, and it costs nothing to rule out first.