OFTEC Oil Firing (OFT101/105E) study materials
OFTEC Oil Firing (OFT101/105E) study resources

OFTEC Oil Firing (OFT101/105E): Installation of Oil Fired Appliances and Systems

OFTEC Oil Firing (OFT101/105E) · Work through your exam, one topic at a time.

All guide sections

Installation of Oil Fired Appliances and Systems

Planning the installation

Installation questions test whether you consider the whole system: fuel supply, flue, ventilation, electrical supply, condensate, access and clearances.

Key requirements

  • Base and clearances: appliance on a suitable non-combustible base with service access and manufacturers' clearances to combustible materials.
  • Fuel line: correctly sized, protected, with a fire valve and isolator; bottom outlet tanks need a fire valve and often an anti-siphon arrangement.
  • Flue: correct route, rise, support, terminal position and clearance from openings and combustible materials.
  • Ventilation: permanent air for combustion and cooling, sized to the appliance and to the room.
  • Electrical: isolator adjacent to the appliance, correct fuse/breaker, and wiring to BS 7671.
  • Condensate: for condensing appliances, a suitable drain with trap and frost protection.
  • System: pipework, expansion, controls, and flushing/water treatment for boilers.

Traps in questions

  • Forgetting the fire valve or placing it where it cannot sense a fire at the burner.
  • Sizing ventilation for combustion only and ignoring cooling air.
  • Installing a condensing appliance without a condensate route or frost protection.
  • Ignoring clearance to combustibles when the flue passes through a wall or roof.

Worked example

A replacement boiler goes into a small utility room with a louvre door. Rule of thumb: treat the louvre as a ventilator only if it is permanent, correctly sized and unobstructed; otherwise fit dedicated permanent vents. Record the ventilation calculation on the commissioning paperwork.