Quick reference

Legislation, Regulations and Standards (Gas Safety Framework)

  • The Gas Safety (Installation and Use) Regulations 1998 apply to gas fittings and appliances used for domestic and commercial premises; they do not apply to premises used wholly as a factory or mine.

  • Regulation 3 places duties on installers: work must be carried out in a competent manner and gas fittings must be maintained in a safe condition so that gas is not allowed to escape.

  • Regulation 26 requires a landlord's gas safety check on every relevant appliance and flue in let domestic premises at intervals of no more than 12 months, with a record given to tenants within 28 days.

  • Regulation 36 prohibits the installation of any gas appliance in a room used or intended to be used as a bathroom or shower room unless it is a room-sealed appliance.

  • The Gas Safety (Management) Regulations 1996 govern gas network safety, while the Pipelines Safety Regulations 1996 cover larger transmission and distribution pipelines; neither is the domestic installation rulebook.

  • British Standard BS 6891 covers low-pressure installation pipework up to 35 mm nominal size; BS 5440 Parts 1 and 2 cover flues and ventilation; BS 6400 covers domestic meter installation.

  • Manufacturer's instructions are the primary benchmark for installation, commissioning and servicing under the Gas Safety (Installation and Use) Regulations; where instructions conflict with a standard, the more onerous requirement normally governs.

  • The Health and Safety at Work etc. Act 1974 imposes general duties on employers and the self-employed to ensure safety so far as is reasonably practicable, and gas work falls within it.

Quick reference

Gas Properties, Combustion and Ventilation

  • Natural gas is predominantly methane (typically around 90%) with a gross calorific value of about 39-41 MJ/m3; it is lighter than air, with a relative density of approximately 0.6 (air = 1).

  • Liquefied petroleum gas (propane) has a relative density of about 1.5-2.0, so it is heavier than air and accumulates at low level in basements, pits and drains.

  • Complete combustion of methane: CH4 + 2O2 -> CO2 + 2H2O. Each cubic metre of gas needs roughly 2 volumes of oxygen, which is about 10 volumes of air.

  • Incomplete combustion produces carbon monoxide; a CO/CO2 ratio above 0.004 (0.4%) on a flue gas analyser indicates a potentially unsafe appliance condition.

  • The upper and lower explosive limits for natural gas in air are approximately 5% and 15% by volume; for propane approximately 2% and 10%.

  • Ventilation for a room-sealed appliance is generally not required for combustion air, but ventilation openings must never be obstructed and air bricks must be checked for blockage.

  • For open-flued appliances, permanent ventilation is sized from the appliance input rating in kW; the manufacturer's instructions give the exact free area required, commonly 5 cm2 per kW above a threshold.

  • A spillage test confirms combustion products are clearing the appliance draught diverter; smoke or a flame is held at the draught hood and must be drawn into the flue, not escape into the room.

Quick reference

Pipework, Fittings, Jointing and Pressure Testing

  • BS 6891 applies to low-pressure natural gas installation pipework up to 35 mm; pipework must be supported at intervals not exceeding those given in the standard, generally 1.5 m for 15 mm and 2 m for 22 mm copper.

  • Sleeving is required where pipework passes through a wall, floor or cavity: the sleeve must be sealed to the wall and the annular space between pipe and sleeve left open to allow gas to disperse.

  • Only joints of a type permitted by the standard may be used; compression fittings must be accessible unless the manufacturer permits otherwise, and soldered capillary joints must be made with lead-free solder.

  • A let-by test is performed before a tightness test: the test medium pressure is applied to the installation with the meter or test nipple closed, and any rise in pressure indicates gas passing an internal valve.

  • For a low-pressure installation, the tightness test uses air at 20-30 mbar (or as specified) and the permissible pressure drop depends on installation volume and test duration, per BS 6891 tables.

  • Purging displaces air from new or disturbed pipework with gas before an appliance is lit; purge volume is calculated from pipe internal volume and the number of volume changes required by the standard.

  • Pipework must not be installed in a lift shaft, in an unventilated void, or buried in concrete without protection; it must be accessible for inspection and testing.

  • A soundness (tightness) test must be carried out on any new or altered installation before it is commissioned and the result recorded.

Quick reference

Meters, Emergency Control Valves and Supply Connections

  • A domestic natural gas meter is installed by the gas transporter; the installer must not break the meter seals or remove the meter unless authorised, and must check the meter regulator outlet pressure is within tolerance (typically 19-23 mbar for natural gas).

  • The meter inlet and outlet must be fitted with an emergency control valve (ECV) on the outlet side, accessible and clearly labelled; the ECV is the primary means of isolating gas to the installation.

  • The meter installation must be in a ventilated position, with specified clearances from electrical fittings and openings, and protected from corrosion and mechanical damage.

  • An emergency control valve must be fitted at the point where the service pipe enters the premises and be readily accessible; it must be capable of being operated without the use of a tool.

  • Where a meter is installed in a meter box, the box must be ventilated, the ECV must be accessible, and the installation must comply with the relevant standard for meter housings.

  • The meter outlet pipe must be sized for the total load of the installation; the meter size and pipework must accommodate the maximum gas rate with an acceptable pressure drop.

  • A meter must be earthed/bonded in accordance with the IET Wiring Regulations where metallic pipework enters the premises; main protective bonding must be within 600 mm of the meter outlet on the consumer side.

  • Gas escape procedures: if a leak is suspected at the meter or service, the ECV should be turned off, the area ventilated, and the gas transporter notified; no flames or electrical switches should be operated.

Quick reference

Domestic Gas Appliances: Installation, Commissioning and Servicing

  • Every appliance must be installed in accordance with the manufacturer's instructions; the installer must check the appliance is suitable for the gas family and supply pressure at the premises.

  • Commissioning includes a gas rate check (meter reading over a timed period), operating pressure check at the appliance test point, and combustion analysis where the appliance has a flue.

  • A gas rate check is calculated from the meter dial reading over 2 minutes and converted to kW using the calorific value of the gas and the meter conversion factor.

  • Servicing must include inspection of the heat exchanger, burner, seals and flue, cleaning where necessary, checking safety devices, and confirming combustion performance with an analyser.

  • Room-sealed appliances draw combustion air directly from outside and discharge products outside; they must be installed with the correct terminal position and must not be modified without manufacturer approval.

  • Open-flued appliances require a draught diverter and a flue with sufficient pull; a spillage test must be performed on commissioning and after any service or installation change.

  • Appliances must be electrically safe and cross-bonded where required; the installer must check the appliance is suitable for the location, including bathroom restrictions under Regulation 36.

  • A warning notice or unsafe situation classification must be applied where an appliance fails a safety check, and the customer must be informed in writing.

Quick reference

Flues, Chimneys and Combustion Product Discharge

  • Flue terminal positions are specified in BS 5440 Part 1: minimum distances from openings, windows, doors, vents and boundaries, e.g. 300 mm from an opening window or door, 600 mm from a boundary or neighbouring building (check current table).

  • A flue must be of the correct diameter and type for the appliance, adequately supported, and must not have more than the permitted number of bends specified by the manufacturer.

  • Flues must terminate in the open air and must not discharge into a covered area, lightwell, or internal space; terminal guards are required where accessible to the public.

  • A draught diverter is required on open-flued appliances to prevent down-draught affecting combustion and to allow spillage of products if the flue is blocked.

  • Flue flow and spillage tests confirm the flue is clear and drawing correctly; a smoke pellet is used to check flue flow, and a flame or smoke at the draught diverter checks for spillage.

  • Shared flues and chimneys must be checked for integrity and correct termination; a flue serving a gas appliance must not serve any other fuel appliance unless it is a suitably designed shared flue.

  • Chimneys must be swept and checked before a new appliance is connected; a flue liner may be required where the existing chimney is unsuitable.

  • Combustion products must not enter another dwelling; flue terminals must be positioned so products cannot re-enter the building through windows, vents or air bricks.

Quick reference

Safety Checks, Tightness Testing and Purging

  • A tightness test must be carried out on new pipework and after any alteration; the test medium is air or inert gas, never gas, and the test pressure and permissible drop are taken from BS 6891.

  • Before a tightness test, a let-by test is performed to confirm the meter or test valve is not passing; a pressure rise during the let-by test indicates a passing valve.

  • For natural gas low-pressure installations, the test pressure is typically 20-30 mbar with a stabilisation period, and the permissible drop is calculated from the installation volume and test duration.

  • Purging is required before commissioning new pipework: the volume of gas needed is calculated from the pipe volume and the number of purge volumes required to displace air safely.

  • A gas rate check and operating pressure check are part of commissioning; the burner pressure must match the data plate value within tolerance, and the gas rate must match the rated input.

  • A combustion analysis records CO, CO2, O2 and CO/CO2 ratio; a ratio above 0.004 is a potential unsafe situation requiring investigation.

  • Safety devices such as flame supervision devices (FSD), overheat thermostats and pressure switches must be function-tested during servicing and commissioning.

  • Records of tightness tests, purge volumes and commissioning results must be kept and provided to the customer where required.

Quick reference

Unsafe Situations, Warning Notices and Emergency Procedures

  • An Immediately Dangerous (ID) situation is one where there is an immediate risk to life or property; gas must be shut off, the appliance isolated, and a warning notice attached with the customer informed not to use the appliance.

  • An At Risk (AR) situation is one where a fault could become dangerous; the appliance should be isolated and a warning notice issued, with the customer advised of the defect and the action required.

  • Warning notices must record the defect, the date, the engineer's details and the action taken; the customer should sign to acknowledge receipt where possible.

  • If a gas escape is suspected, the ECV should be turned off, the area ventilated, no flames or electrical switches operated, and the gas transporter or emergency service contacted.

  • Carbon monoxide alarms should be fitted in rooms containing open-flued appliances and in sleeping areas where required by current guidance; an alarm is not a substitute for correct servicing.

  • Where an appliance is classified ID, the gas supply to that appliance must be disconnected and capped or the ECV turned off if the escape is upstream.

  • The engineer must inform the responsible person (landlord, homeowner or occupier) in writing of any unsafe situation and retain a copy of the warning notice.

  • Reconnection after an ID classification must only occur once the defect has been rectified and the appliance has been retested and found safe.