BSEH Secondary NSQF Construction flashcards
BSEH Secondary NSQF Construction · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Minimum site PPE
- Hard hat, safety footwear, high-visibility vest and eye protection are the baseline on an active site; hearing and respiratory protection are added for noisy or dusty tasks.
- Fall protection threshold
- Work at heights of 1.8 m or more requires guardrails or a full-body harness with lanyard anchored above shoulder level, plus inspected scaffolds with toe boards.
- Excavation shoring rule
- Excavations deeper than 1.5 m need shoring, benching or sloping, with spoil and plant kept at least 1 m clear of the edge and a ladder provided for access.
- RCD on portable tools
- Portable electrical tools on site should be double-insulated or supplied through a residual current device that trips on earth leakage, with cables kept off wet ground.
- Silica dust control
- Cutting, grinding and drilling concrete releases respirable crystalline silica causing silicosis; control by wet cutting, on-tool extraction and at least FFP2/N95 respiratory protection.
- Noise action level
- The action level is 85 dB(A) averaged over an 8-hour shift; each 3 dB increase roughly doubles sound intensity, so exposure time must be halved for each 3 dB rise.
- Cement dermatitis cause
- Wet cement is strongly alkaline, around pH 12 to 13, causing irritant and allergic contact dermatitis; gloves, barrier cream and washing facilities are the controls.
- Waste segregation on site
- Separate waste into recyclable, inert, hazardous and organic streams at source; hazardous items such as paint and solvent need recorded disposal, and burning waste is prohibited.
- OPC setting times
- Ordinary Portland cement has an initial setting time of at least 30 minutes and a final setting time not exceeding 600 minutes; grades 33, 43 and 53 denote 28-day strength in MPa.
- Nominal concrete mixes
- Volume proportions 1:3:6 give M10, 1:2:4 give M15 and 1:1.5:3 give M20; lower water-cement ratio raises strength and durability when concrete is fully compacted.
- Fine versus coarse aggregate
- Fine aggregate passes the 4.75 mm sieve and coarse aggregate is retained on it; well-graded combined aggregate reduces voids, water demand and segregation in concrete.
- First-class brick properties
- First-class burnt clay bricks are table-moulded, well burnt, uniform in colour, give a clear ringing sound when struck and absorb not more than about 20 percent water by weight.
- Try square and spirit level
- A try square checks that a corner is 90 degrees, while a spirit level checks level and plumb using a bubble in a curved vial; both are checked before each use.
- Rip versus crosscut saw
- A rip saw has chisel-shaped teeth and cuts along the grain, while a crosscut saw has knife-shaped teeth and cuts across the grain; set and sharpening control the kerf.
- Hammer action drilling
- Hammer action drilling is selected for masonry and concrete, rotary-only drilling for metal and wood; the bit type and rotation speed are matched to the material being drilled.
- Concrete vibrator use
- Insert the vibrator vertically at regular spacing, withdraw it slowly, and avoid over-vibration that causes segregation; never use the vibrator to spread or push concrete.
- Drawing line conventions
- Continuous thick lines show visible outlines, dashed lines show hidden edges, chain-dotted lines mark centre and grid lines, and thin lines carry dimensions and extension lines.
- Plan and section defined
- A plan is a horizontal cut about 1 m above floor level viewed downward; a section is a vertical cut showing heights, construction layers and levels of the building.
- Title block contents
- Every drawing sheet carries a title block with project name, drawing title and number, scale, date, revision status and the names of the person who drew and checked it.
- Building drawing scales
- Typical scales are 1:100 for plans, 1:50 for enlarged plans, 1:20 or 1:10 for construction details and 1:200 or 1:500 for site plans; the scale is always stated.
- Masonry measurement rule
- Brick masonry is measured in cubic metres as length times height times thickness, deducting openings above the specified area threshold and deducting lintels and beams.
- Plaster measurement rule
- Plaster is measured in square metres of finished surface, deducting openings larger than 0.5 square metres and adding jambs, soffits and reveals, with thickness and mix stated.
- Rebar unit weight formula
- The unit weight of a steel bar is d squared divided by 162 kilograms per metre, where d is the bar diameter in millimetres; total weight is bar count times length times unit weight.
- Rate analysis meaning
- Rate analysis derives the unit rate of a work item from material, labour, plant, overheads and contractor profit; the estimate is quantity times rate plus contingency and taxes.
- English versus Flemish bond
- English bond alternates whole header courses with whole stretcher courses and is strongest; Flemish bond alternates header and stretcher bricks within every course.
- Slump test purpose
- The slump test measures concrete workability; a true slump of about 25 to 75 mm suits normal reinforced concrete, while shear or collapse slump indicates an excessively wet mix.
- Concrete curing period
- Concrete must be kept damp for at least 7 days, and 10 to 14 days for harsh exposure, because curing supports strength gain and reduces shrinkage cracking and surface permeability.
- Mortise and tenon joint
- A mortise and tenon joint cuts a projecting tenon on one member into a matching mortise hole in the other, giving a strong interlocking frame joint used in doors and windows.
- Timber seasoning purpose
- Seasoning lowers timber moisture content towards equilibrium with service conditions, reducing shrinkage, warping, splitting and decay while improving strength and paint adhesion.
- Soil versus waste pipe
- A soil pipe carries foul water from water closets, a waste pipe carries sullage from sinks and basins, and a vent pipe equalises pressure to protect trap water seals.
- Trap water seal
- Every sanitary fixture needs a water seal trap of 50 to 100 mm, such as a P-trap, that blocks sewer gas; the vent stack prevents siphonage from emptying the seal.
- Earthing conductor colour
- The earth conductor is green or green-yellow and must never be used as a neutral; all metal enclosures need earth continuity, and earth resistance is tested periodically.