Quick reference

Basics of Power Sector and Energy Sources

  • Energy is measured in joules (J); power is the rate of energy transfer, 1 W = 1 J/s, and 1 kWh = 3.6 MJ.

  • Primary energy sources split into conventional (coal, lignite, natural gas, oil, large hydro, nuclear) and renewable (solar, wind, small hydro, biomass, biogas, geothermal, tidal).

  • India's electricity chain has four links: generation, transmission, distribution and consumption; transmission and distribution together are called the grid.

  • Commercial energy sources are bought and sold (coal, oil, gas, electricity); non-commercial sources include firewood, agricultural residue and animal dung.

  • Load factor = average load / maximum demand over the same period; a higher load factor means the plant capacity is used more evenly.

  • Diversity factor = sum of individual maximum demands / maximum demand on the system; it is always greater than or equal to 1.

  • Per-capita electricity consumption = total annual energy consumed (kWh) / population; it is a standard development indicator.

  • A unit of electricity in billing is 1 kWh, i.e. 1000 W used for one hour; a 100 W lamp burning 10 hours consumes 1 unit.

Quick reference

Power Generation: Conventional and Renewable

  • Thermal plant efficiency chain: boiler efficiency x turbine efficiency x generator efficiency; overall efficiency of a coal plant is typically 30-38%.

  • Rankine cycle is the working cycle of steam plants; reheating and regenerative feed heating raise cycle efficiency.

  • Hydro power output P = rho x g x Q x H x eta, where Q is discharge in m3/s, H is net head in m and eta is overall efficiency.

  • Wind power available in the air stream P = 0.5 x rho x A x v^3; power varies with the cube of wind speed, and Betz limit caps extraction at 16/27 (about 59.3%).

  • Solar PV output depends on irradiance and temperature; module efficiency falls as cell temperature rises, so ventilation of modules matters.

  • A solar cell is a p-n junction; the photoelectric effect generates electron-hole pairs, and the cell is characterised by open-circuit voltage, short-circuit current and fill factor.

  • Nuclear fission of U-235 releases about 200 MeV per nucleus; heavy water and light water reactors differ mainly in moderator and coolant.

  • Biomass and biogas plants use anaerobic digestion or combustion; biogas is mainly methane (50-70%) and carbon dioxide.

  • Plant capacity factor = actual energy generated / (rated capacity x hours in period); it differs from load factor, which concerns demand.

Quick reference

Transmission and Distribution Systems

  • Transmission voltage levels in India: 66 kV, 110 kV, 132 kV, 220 kV, 400 kV, 765 kV AC, plus HVDC links such as +/-800 kV.

  • For the same power and power factor, raising voltage reduces current and therefore I^2R loss; line loss is inversely proportional to the square of voltage.

  • Standard supply frequencies and voltages: 50 Hz in India; LT distribution at 400 V three-phase, 230 V single-phase.

  • A transmission line is classified short (below 80 km), medium (80-250 km) and long (above 250 km); nominal pi and T models suit medium lines.

  • Surge impedance Zc = sqrt(L/C); surge impedance loading SIL = V^2 / Zc gives the natural power limit of a line.

  • Skin effect pushes AC current to the conductor surface and raises effective resistance; it increases with frequency and conductor diameter.

  • Corona loss increases with voltage and is reduced by using bundled conductors and larger conductor diameter.

  • Distribution feeders are radial, ring-main or interconnected; a radial feeder has no back-feed, so a fault interrupts all downstream consumers.

  • Ferranti effect raises receiving-end voltage above sending-end voltage on a lightly loaded long line, especially with capacitive charging current.

Quick reference

Electrical Machines and Equipment

  • Transformer EMF equation: E = 4.44 x f x N x Phi_max; voltage per turn is constant on both windings of an ideal transformer.

  • Transformer losses: copper loss varies as the square of load current, core loss is nearly constant; maximum efficiency occurs when copper loss equals core loss.

  • Synchronous machine speed n = 120 f / P, where P is the number of poles; a 4-pole machine at 50 Hz runs at 1500 rpm.

  • Slip of an induction motor s = (Ns - N)/Ns; rotor frequency equals s x supply frequency, and rotor EMF at standstill is the blocked-rotor value.

  • A three-phase induction motor is self-starting because the rotating field induces rotor currents; a single-phase induction motor needs an auxiliary or capacitor winding.

  • Torque of a DC motor is proportional to flux and armature current; a shunt motor is a constant-speed machine, a series motor gives high starting torque.

  • A DC generator is commutated to produce DC at the terminals; the commutator also acts as a mechanical rectifier.

  • Motor starters (DOL, star-delta, autotransformer, soft starter) limit starting current; star-delta reduces starting current to one-third of the DOL value.

  • Alternator excitation controls reactive power and terminal voltage; over-excitation supplies lagging reactive power to the grid.

Quick reference

Power System Protection and Safety

  • A protection scheme must be selective, sensitive, fast and reliable; it must also be stable against faults outside its zone.

  • A relay is defined by its pick-up value (minimum operating current) and its time-current characteristic; an IDMT relay trips faster at higher fault current.

  • Current transformer (CT) and potential transformer (PT) step down current and voltage to relay-friendly levels; CT secondary is never open-circuited under load.

  • Distance relays measure impedance Z = V/I and are set in zones: zone 1 about 80% of the line, zone 2 about 120%, zone 3 for backup.

  • Differential protection compares currents at both ends of a transformer or generator; it responds to internal faults and is immune to through-faults.

  • Circuit breakers are rated by breaking capacity in MVA or kA; an isolator must never be opened on load, only after the breaker has cleared.

  • Earthing types: TT, TN-S, TN-C, TN-C-S and IT; protective earth limits touch voltage and lets the protective device operate.

  • Earth resistance is measured by the fall-of-potential method; a low earth resistance (commonly 1-5 ohm for substations) is required for effective fault clearance.

  • First aid for electric shock: switch off the supply, use an insulated object to separate the victim, then start CPR if breathing has stopped.

Quick reference

Energy Conservation, Audit and Management

  • Energy audit types: preliminary (walk-through) audit, detailed audit and targeted audit; a detailed audit uses metered data and cost-benefit analysis.

  • Energy conservation means using less energy for the same service; energy efficiency means delivering the same output with less input energy.

  • Energy audit instruments include power analyser, lux meter, anemometer, flue gas analyser, thermal imager and ultrasonic leak detector.

  • Payback period = initial investment / annual energy cost saving; a shorter payback means a faster-returning measure.

  • Life-cycle cost adds capital, operating, maintenance and disposal costs over the equipment life; it captures savings that simple payback misses.

  • Specific energy consumption = energy input / production output; tracking it over time reveals efficiency drift in a plant.

  • Power factor improvement capacitors reduce line current and kVA demand; kVAR required = P x (tan phi1 - tan phi2).

  • Lighting efficiency is measured in lumens per watt; LED lamps commonly deliver 80-150 lm/W against about 15 lm/W for incandescent lamps.

  • The Energy Conservation Act, 2001 created the Bureau of Energy Efficiency (BEE); BEE star labels rate appliances on a 1-5 star scale.

Quick reference

Power Sector Practices and Entrepreneurship

  • The Electricity Act, 2003 unbundled generation, transmission and distribution and enabled open access and trading of electricity.

  • CERC regulates inter-state transmission and tariffs; SERCs regulate intra-state distribution tariffs and retail supply.

  • A distribution franchisee operates a utility's network in a defined area under a franchise agreement, earning a return on collection and loss reduction.

  • Energy service company (ESCO) model: the ESCO invests in efficiency measures and is paid from the measured savings, often under a performance contract.

  • A net-metering consumer with rooftop solar exports surplus units and gets credit against imported units at the retail tariff.

  • Tariff components usually include fixed or demand charges, energy charges, power factor penalty or incentive, and electricity duty.

  • Aggregate technical and commercial (AT&C) loss = (energy input - energy billed and collected) / energy input; it combines technical loss and collection loss.

  • A business plan for a power venture states the market, technical design, capital cost, revenue model, payback and regulatory approvals needed.

  • Small hydro, rooftop solar and biomass gasifier projects are common rural entrepreneurship options supported by state renewable energy policies.

Quick reference

Employability and Workplace Skills

  • A resume for a technical role lists contact details, skills, qualifications, projects and references, and is usually one to two pages.

  • A cover letter follows a three-part structure: why you are writing, what you offer, and a request for an interview.

  • The 5S workplace method: sort, set in order, shine, standardise and sustain; it is a foundation of shop-floor discipline.

  • Personal protective equipment in electrical work includes insulated gloves, safety shoes, helmet, safety glasses and arc-rated clothing.

  • Permit-to-work systems require isolation, lockout-tagout, testing for dead and formal authorisation before work on electrical equipment.

  • Communication in a team follows sender, message, channel, receiver and feedback; feedback confirms that the message was understood.

  • A job interview answer to a technical question should state the concept, give a worked example and mention a safety or practical implication.

  • Record keeping and documentation (log books, inspection reports, test certificates) support traceability and legal compliance in utility work.

  • Entrepreneurial skills for technicians include costing a job, quoting, invoicing, customer service and basic bookkeeping.