Haryana BSEH Senior Secondary NSQF Power flashcards
Haryana BSEH Senior Secondary NSQF Power · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Kilowatt-hour
- The commercial unit of electrical energy, equal to 1000 watts used for one hour or 3.6 megajoules. Electricity bills charge consumers per kWh consumed.
- Load factor
- Ratio of average load to maximum demand over a given period. A high value shows the plant capacity is used evenly and lowers the cost per unit generated.
- Diversity factor
- Ratio of the sum of individual maximum demands to the maximum demand of the whole system. It is always at least one because consumers peak at different times.
- Primary energy source
- A source available in nature before conversion, such as coal, natural gas, wind or sunlight. Secondary energy is the converted form, for example electricity or refined fuel.
- Rankine cycle
- The thermodynamic cycle of a steam power plant, with boiler heating, turbine expansion, condenser rejection and pump compression. Reheating and feed heating improve its efficiency.
- Betz limit
- The maximum fraction of wind power a turbine can extract from an air stream, equal to 16/27 or about 59.3 percent. No practical turbine exceeds this theoretical value.
- Plant capacity factor
- Actual energy generated divided by the energy the plant would produce running at rated capacity for the whole period. It measures how fully the plant is used.
- Solar cell
- A p-n junction semiconductor device that converts light into electricity. Its performance is described by open-circuit voltage, short-circuit current and fill factor.
- Hydro power equation
- Power equals density times gravity times discharge times net head times overall efficiency. Doubling the head or the flow doubles the output of the plant.
- Skin effect
- The tendency of alternating current to concentrate near the conductor surface, raising effective resistance. It grows with frequency and conductor diameter and is ignored at DC.
- Surge impedance loading
- The power a lossless line delivers when terminated in its surge impedance, equal to voltage squared divided by surge impedance. It indicates the natural loading of the line.
- Ferranti effect
- The rise of receiving-end voltage above sending-end voltage on a long, lightly loaded line, caused by the line charging current flowing through line inductance.
- Radial feeder
- A distribution feeder connected from a single source with no back-feed path. A fault near the source interrupts all consumers downstream of the fault point.
- Corona loss
- Power lost as ionisation of air around high-voltage conductors, producing hiss, glow and ozone. Bundled conductors and larger diameters reduce it.
- Transformer EMF equation
- Induced EMF equals 4.44 times frequency times turns times peak flux. It shows that the voltage per turn is the same in both windings.
- Synchronous speed
- The speed of the rotating magnetic field, equal to 120 times frequency divided by the number of poles. A four-pole machine on 50 Hz supply runs at 1500 rpm.
- Slip
- The difference between synchronous speed and rotor speed, expressed as a fraction of synchronous speed. Rotor frequency equals slip times the supply frequency.
- Star-delta starter
- A starter that runs the motor windings in star during starting and delta during run. Starting current falls to one-third of the direct-on-line value.
- Transformer maximum efficiency
- A transformer reaches maximum efficiency when its variable copper loss equals its constant core loss. This occurs at a specific load fraction, not necessarily full load.
- Distance relay
- A relay that measures the impedance from voltage and current to locate a fault. Zones are set by reach, with zone one covering about 80 percent of the protected line.
- Differential protection
- A scheme comparing currents entering and leaving a protected transformer or generator. It trips on internal faults but stays stable for faults and load outside the zone.
- Current transformer
- A measuring transformer that reduces line current to a standard secondary value for relays and meters. Its secondary must never be open-circuited while primary current flows.
- Isolator
- A switch that provides a visible isolation gap in a circuit but has no arc-quenching capability. It must be operated only after the circuit breaker has cleared the load.
- Protective earthing
- Connecting exposed metal parts to earth so that fault current flows and the protective device trips quickly. It also limits touch voltage to a safe level.
- Energy audit
- A systematic study of energy use in a facility to identify waste and cost-saving measures. It may be preliminary, detailed or targeted, and uses metered data.
- Payback period
- The time needed for annual savings from an efficiency measure to recover its initial investment. It ignores savings after payback, so life-cycle costing is often preferred.
- Specific energy consumption
- Energy input divided by production output, for example kWh per tonne of product. Tracking it over time shows whether plant efficiency is improving or drifting.
- Power factor correction
- Adding capacitors to supply reactive power locally, reducing line current and kVA demand. Required kVAR equals active power times the difference of the two tangent values.
- BEE star label
- A rating from one to five stars awarded by the Bureau of Energy Efficiency to appliances, based on energy performance. More stars mean lower running energy consumption.
- Electricity Act 2003
- The Indian law that unbundled generation, transmission and distribution, created open access and electricity trading, and set up regulatory commissions for tariffs.
- ESCO performance contract
- An arrangement where an energy service company funds efficiency improvements and is paid from the measured savings, sharing the benefit with the client.
- AT&C loss
- Aggregate technical and commercial loss, the gap between energy input and energy billed and collected. It combines technical losses with billing and collection shortfalls.