Arc flash boundary
The distance from exposed live parts where incident energy equals 1.2 cal/cm², the level that causes a second-degree burn on unprotected skin.
Live-dead-live test
A verification sequence in which the voltage tester is proven on a known live source, applied to the isolated circuit, then proven again to confirm it still functions.
Lockout/tagout
A procedure that isolates hazardous energy, applies a personal lock and tag, and verifies absence of voltage before work begins on the equipment.
Restricted approach boundary
The distance from exposed live parts that only qualified persons wearing appropriate shock protection may cross, and only with justification for the task.
Ohm's law
The relationship V = I × R, stating that voltage across a resistive element equals current through it multiplied by its resistance.
Three-phase power formula
For a balanced three-phase load, real power equals the square root of three times line voltage times line current times power factor.
Power factor
The ratio of real power in watts to apparent power in volt-amperes; a lagging value indicates inductive loads such as motors.
Kirchhoff's current law
The principle that the algebraic sum of currents entering and leaving any node in a circuit equals zero at all times.
Transformer turns ratio
The ratio of primary to secondary voltage equals the ratio of primary to secondary turns, and is the inverse of the current ratio.
Conductor ampacity
The maximum continuous current a conductor can carry under stated conditions, adjusted for ambient temperature and the number of bundled current-carrying conductors.
Box fill calculation
A code method that counts conductors, device yokes, and grounding conductors to confirm the box volume is sufficient for its contents.
Equipment grounding conductor
A conductor, colored green or bare, that provides a low-impedance fault path back to the source to facilitate overcurrent device operation.
NM-B cable
A nonmetallic-sheathed cable permitted in dry interior locations but prohibited in wet locations, embedded in masonry, or where exposed to physical damage.
Conduit fill
A limit on the total cross-sectional area of conductors inside a raceway, expressed as a percentage of the conduit interior area.
Terminal torque
The manufacturer-specified tightening value for a lug or terminal; insufficient torque causes overheating and is a leading cause of electrical failure.
Working clearance
The minimum depth, width, and height of clear space required in front of electrical equipment, typically 36 inches deep for most panelboards.
Motor overload protection
A protective device sized from the motor nameplate current and service factor that protects the motor winding from sustained overcurrent, separate from branch-circuit protection.
Contactor versus overload relay
A contactor switches load current on command but provides no overload protection; an overload relay protects the motor but does not switch the load.
Star-delta starting
A reduced-voltage starting method that lowers starting current to one-third of direct-on-line values while reducing starting torque by the same proportion.
Variable frequency drive
Equipment that controls motor speed by varying supply frequency and voltage, often requiring shielded cable and attention to grounding to limit induced currents.
Switchgear interrupting rating
The maximum fault current the equipment can safely interrupt; it must equal or exceed the available fault current at the point of installation.
Transformer kVA rating
The apparent power capacity of a transformer, which sets primary and secondary currents according to the respective winding voltages.
Insulation resistance test
A DC test voltage applied to insulation to measure resistance; low readings indicate moisture, contamination, or deterioration of the insulation system.
Clamp meter principle
The instrument senses the magnetic field around a single conductor; it must encircle only the conductor of interest to give a meaningful current reading.
Voltage drop under load
A measurement taken while the circuit carries current, which reveals high-resistance connections that a no-load voltage reading would not show.
Phase rotation test
A check of the sequence of three-phase voltages performed before connecting a motor, because reversed rotation can damage the driven equipment.
Fall-of-potential test
A method for measuring earth electrode resistance using auxiliary current and potential probes placed at specified distances from the electrode under test.
NFPA 70E
The standard for electrical safety in the workplace, covering shock and arc flash risk assessment, approach boundaries, and required personal protective equipment.
Listed and labeled equipment
Equipment evaluated by a recognized testing laboratory and installed in accordance with its listing and the manufacturer's instructions; field modification may void the listing.
Authority having jurisdiction
The organization or individual responsible for enforcing the code, who may adopt amendments stricter than the model code and who approves installations.
As-built drawings
Project documents updated to show the actual installed conditions, including routing changes, added circuits, and revised panel schedules after construction.
Panel schedule
A table recording each circuit's number, breaker rating, conductor size, and connected load description, updated whenever circuits are added or changed.