Occupancy Classification: Daycare, Assembly, and Office in Type VB

PSB LBO · Put your knowledge to work in context.

All case studies

Occupancy Classification: Daycare, Assembly, and Office in Type VB

A single-story Type VB building (wood frame, unprotected) contains three tenant spaces: a daycare for 30 children ages 2–5, a community room with 49 occupants (no fixed seats), and a real estate office with 15 occupants. The building is not sprinklered. The owner wants to add a 2,000-square-foot second story for storage (Group S-2). The building has one exit door. The daycare has a fenced outdoor play area. The assembly room has a 3-foot-wide exit door; the office has a 2-foot-8-inch door. The building is 6,000 square feet on the first floor. The owner argues that the daycare is an accessory to the office. The local code official must classify the occupancies, determine allowable height and area for the existing building and proposed addition, and identify egress issues.

1. How should the building official classify each tenant space and the building overall?

Read the worked answer

The daycare for 30 children older than 2.5 years is Group E, not an accessory to the office. The code classifies child-care facilities for more than five children older than 2.5 years as Group E because of the occupants' limited ability to self-evacuate. The community room with 49 occupants and no fixed seats is Group A-3, an assembly occupancy. The real estate office with 15 occupants is Group B. The building overall is a mixed-occupancy building unless the tenant spaces are separated by fire barriers as required for separated occupancies. The owner's argument that the daycare is accessory to the office fails because the daycare is not subordinate in area, does not serve only the office, and introduces a distinct occupancy with a different hazard profile. The official should require the applicant to either provide code-compliant fire separations between the occupancies or treat the building as a single mixed occupancy using the most restrictive provisions. The official should also check whether the daycare has the required fire separation from the other tenants and whether the assembly room's occupant load is correctly calculated.

2. Evaluate allowable height and area for the existing building and proposed second story under Type VB.

Read the worked answer

Type VB construction is unprotected wood frame, so the allowable height and area are limited. For Group E, the allowable height is one story and the allowable area is 4,000 square feet. For Group A-3, the allowable height is one story and the allowable area is 4,000 square feet. For Group B, the allowable height is two stories and the allowable area is 9,000 square feet. For Group S-2, the allowable height is two stories and the allowable area is 9,000 square feet. The existing first floor is 6,000 square feet, which already exceeds the 4,000-square-foot limit if Group E or Group A-3 controls. Adding a second story would make the building two stories, but Group E and Group A-3 are limited to one story in Type VB. The proposed storage story would not be allowed above those occupancies unless the building is sprinklered or the occupancies are separated in a way that changes the analysis. The official should not approve the second story based on the Group B or S-2 limits alone, because the most restrictive occupancy governs unless the building is divided into separate buildings by fire walls. The official should require a code analysis showing how the height and area limits are satisfied, including any allowable increases for frontage or sprinklers.

3. Identify egress deficiencies and required corrections.

Read the worked answer

The building has only one exit door, which is insufficient for the combined occupant load of 30 children, 49 assembly occupants, and 15 office occupants. Even if the daycare is considered separately, Group E with 30 children may require two exits depending on the travel distance and the common path of egress travel. Group A-3 with 49 occupants is allowed a single exit only if the travel distance and common path limits are met; however, the building's total occupant load of 94 means the single exit cannot serve the whole building unless the occupancies are separated by fire barriers and each space is independently evaluated. The 3-foot-wide assembly door is 36 inches, which is wide enough for 49 occupants, but the door must swing in the direction of egress if the occupant load is 50 or more; at 49 it is not required, but the official should check the actual calculated load. The office door is 32 inches, which is the minimum clear width, so it may be acceptable if the clear opening is maintained. The daycare and assembly room likely need a second remote exit, and the exit path must be continuous and unobstructed. The official should require a revised egress plan showing two exits, proper door widths, panic hardware where required, and a compliant outdoor play area exit.