- Conduction heat flow formula
- Q = U × A × ΔT, where Q is Btu/h, U is Btu/(h·ft²·°F), A is ft², and ΔT is °F. R-value is the reciprocal of U.
- Area-weighted U-factor
- For parallel paths such as framing and cavity, average U-factors weighted by area: U_avg = (U1·A1 + U2·A2)/(A1 + A2). Averaging R-values instead overstates performance.
- Sensible heat equation
- Q = 1.08 × CFM × ΔT in Btu/h at sea level. The 1.08 constant combines air density, specific heat, and unit conversions for standard air.
- Dew point
- The temperature at which air reaches saturation and water vapor begins to condense. A surface colder than the interior dew point will collect condensation.
- ACH50
- Air changes per hour at 50 Pa, calculated as CFM50 × 60 ÷ conditioned volume in ft³. It normalizes blower door leakage to house size.
- Effective leakage area
- An estimate of the equivalent hole size in the envelope, often approximated as CFM50 ÷ 10 in square inches. Use as a screening number, not a precise measurement.
- Pressure pan test
- A pressure-difference measurement across outlets while the blower door runs. Higher readings indicate leakier paths and help target air sealing.
- Air-free CO
- Measured CO corrected for dilution: air-free CO = CO × (20.9 ÷ (20.9 − O2)). It is the number compared against combustion safety limits.
- CAZ depressurization limit
- Worst-case depressurization in the combustion appliance zone. Naturally drafting appliances commonly require the CAZ to stay above about −3 Pa; Category I appliances about −5 Pa.
- Spillage test
- With the appliance firing and the CAZ at worst-case depressurization, check for flue gas escaping at the draft hood. Spillage indicates unsafe venting.
- AFUE
- Annual Fuel Utilization Efficiency: annual useful heat output divided by annual fuel energy input. It accounts for cycling and standby losses, unlike a single-point stack test.
- Heat pump balance point
- The outdoor temperature where heat pump capacity equals building load. Below it, supplemental heat runs; above it, the heat pump alone meets the load.
- ASHRAE 62.2 ventilation rate
- Whole-house ventilation ≈ 0.03 × floor area (ft²) + 7.5 × (bedrooms + 1) CFM. Local kitchen and bath exhaust is calculated separately.
- HRV versus ERV
- Both are balanced ventilation cores. An HRV transfers sensible heat only; an ERV also transfers moisture, which suits humid cooling climates.
- Thermal bridging
- Heat flow through framing or other low-R paths that bypass cavity insulation. Continuous exterior insulation reduces the penalty because it covers framing, not just cavities.
- Window U-factor and SHGC
- U-factor measures whole-product heat loss (lower is better); SHGC measures solar heat gain (lower reduces cooling load). NFRC ratings are whole-product values.
- Vapor retarder classes
- Class I ≤0.1 perm, Class II 0.1–1.0 perm, Class III 1.0–10 perm. Cold-climate assemblies generally place low-perm material on the warm side.
- Rim joist air sealing
- Rim and band joists are common cold spots and condensation sites. Seal with rigid foam plus sealant and insulate to match the adjacent wall assembly.
- Stack effect
- Buoyancy-driven pressure difference caused by indoor-outdoor temperature difference and building height. Taller buildings and colder weather increase it.
- Latent heat of vaporization
- About 970 Btu is absorbed when one pound of water evaporates and released when it condenses. This is why moisture problems often appear as heat and durability issues.
- Degree-day method
- Estimates annual heat loss from building UA and heating degree days. HDD comes from the nearest weather station and is adjusted for base temperature.
- EUI
- Energy Use Intensity: annual site energy in kBtu divided by conditioned floor area in ft². Compare to ENERGY STAR Portfolio Manager benchmarks for building type and climate.
- Simple payback
- Installed cost divided by annual savings. It ignores measure life and fuel escalation, so pair it with lifecycle cost or savings-to-investment ratio.
- Savings-to-investment ratio
- Present value of savings divided by present value of costs. Programs often require SIR ≥ 1.0, and higher SIR ranks measures higher.
- Interactive effects
- Savings from stacked measures are non-additive. Two measures each saving 20% combine to about 36%, not 40%, because envelope improvements reduce HVAC loads.
- Duct leakage to outside
- The portion of duct leakage that escapes the pressure boundary. It is the metric that matters for energy loss; leakage into conditioned space affects distribution and pressure instead.
- External static pressure
- Supply plus return pressure the blower works against. Residential blowers typically should not exceed 0.5 in. w.c.; higher values signal undersized ducts or dirty coils.
- Blower door baseline
- The house-to-outside pressure difference measured before installing the fan. Record it before and after the test to correct results for wind and stack effects.
- Infrared thermography limits
- IR imaging needs a sufficient temperature difference (generally ≥10–18°F) and steady conditions. Solar gain, wind, and emissivity differences create false anomalies.
- Combustion analyzer outputs
- Measures O2, CO, CO2, and stack temperature, then calculates excess air and air-free CO. Excess air outside roughly 3–9% for natural gas signals a problem.
- Report scope statement
- A written description of what was and was not inspected, such as no destructive testing or appliance disassembly. It limits liability and sets client expectations.
- Conflict of interest disclosure
- If the auditor or firm also installs recommended measures, disclose it clearly and keep the audit independent of sales pressure.
- Health and safety priority
- Findings such as spillage, elevated CO, mold, asbestos, or unsafe wiring are reported immediately and take precedence over energy recommendations.