Iran Nezam Electrical Supervision Exam flashcards
Iran Nezam Electrical Supervision Exam · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- Lumen method formula
- N = (E × A) / (Φ × CU × LLF). E is target illuminance in lux, A is room area in square metres, Φ is lumens per luminaire, CU is coefficient of utilization, LLF is light loss factor.
- Receptacle spacing rule
- In dwelling habitable rooms, no point along the floor line may be more than 1.8 metres from a general-purpose receptacle; kitchen countertop outlets are spaced at intervals not exceeding 1.2 metres.
- Continuous load factor
- Continuous loads, operating three hours or more, are taken at 125 percent of nameplate current when sizing branch circuits, feeders, overcurrent devices, and panel busbars.
- Voltage drop limits
- Branch circuits are limited to 3 percent voltage drop and the total from service to load to 5 percent; motor starting drop at terminals is commonly limited to 15 percent.
- Conduit fill percentages
- Maximum conductor fill of conduit interior area is 53 percent for one conductor, 31 percent for two conductors, and 40 percent for three or more conductors, per standard fill tables.
- Bundling derating factors
- More than three current-carrying conductors in one raceway require derating: 80 percent for four to six, 70 percent for seven to nine, and 50 percent for ten to twenty conductors.
- Conductor colour code
- Phase conductors are brown, black, and grey for L1, L2, L3; neutral is blue; protective earth is green-yellow. A PEN conductor is green-yellow with blue marking at terminations.
- Minimum dwelling conductor sizes
- Typical minimum copper sizes are 1.5 square millimetres for lighting, 2.5 for general receptacles, and 4 for kitchen, laundry, and water-heater circuits, subject to local code amendments.
- Breaker and cable coordination
- The protective device rating must be at least the design current and no greater than the corrected cable ampacity; the tripping current must not exceed 1.45 times that ampacity.
- Earth-fault loop impedance
- Disconnection is verified by Zs ≤ U0 / Ia, where U0 is line-to-earth voltage and Ia is the current that trips the protective device within the required disconnection time.
- RCD Type A versus B
- Type AC responds only to sinusoidal alternating residual current; Type A also responds to pulsating direct current; Type B is required for smooth direct residual current from chargers and inverters.
- TN-C-S earthing system
- The supply neutral also serves as protective conductor (PEN) up to the origin of the installation, where it is split into separate neutral and protective earth conductors downstream.
- Main equipotential bonding size
- The main bonding conductor is at least half the cross-section of the largest protective conductor and not less than 6 square millimetres copper, or 10 where the supply requires it.
- IEC 60364 scope
- The IEC 60364 series sets requirements for protection against shock, thermal effects, overcurrent, earthing, conductor sizing, and verification of low-voltage electrical installations.
- Iranian building code Part 13
- Part 13 of the Iranian national building code governs electrical installations of buildings, adopts IEC 60364 principles, and requires licensed-engineer design and supervision above the small-installation threshold.
- Completion verification tests
- Before energizing, verify protective conductor continuity, insulation resistance, earth electrode resistance, RCD trip time and current, polarity, and earth-fault loop impedance, and record results.
- Standards conflict resolution
- Where documents conflict, the mandatory national code and utility regulations prevail, followed by referenced IEC standards, then manufacturer instructions; the more stringent safety requirement is applied.
- Three-phase power formula
- Real power equals the square root of three times line voltage times line current times power factor; rearrange to find current from known power, voltage, and power factor.
- Copper resistivity values
- Copper resistivity is about 0.0175 ohm square millimetre per metre at 20 degrees Celsius and about 0.0225 at 70 degrees, the value used for voltage-drop calculations.
- Demand versus diversity factor
- Demand factor is the ratio of maximum demand to connected load for one load group; diversity factor relates the sum of individual maximum demands to the installation's coincident maximum demand.
- Transformer sizing rule
- Transformer kilovolt-amperes equals total demand in kilowatts divided by power factor and loading limit, typically 0.8, with 20 to 25 percent spare capacity added for growth.
- Hazardous area zones
- Zone 0, 1, and 2 denote continuous, likely, and unlikely presence of explosive gas; Zone 20, 21, and 22 apply the same logic to combustible dust atmospheres.
- Ex protection concepts
- Ex d is flameproof enclosure, Ex e increased safety, Ex i intrinsic safety, Ex p pressurization, and Ex n non-sparking; temperature classes T1 to T6 limit surface temperature, T6 being 85 degrees.
- Emergency lighting performance
- Escape routes require at least 1 lux on the centreline and open areas 5 lux; 50 percent output within 5 seconds, full output within 60 seconds, and 90 minutes duration minimum.
- Firestopping penetrations
- Every cable penetration of a fire-rated wall or floor must use a listed firestop system with the same fire resistance as the element, including internal and external sealing of trays.
- Fire alarm cable separation
- Fire alarm and detection cables use fire-resistant types in dedicated conduit and are separated from power circuits by at least 300 millimetres or a grounded barrier.
- Elevator supply requirements
- A dedicated feeder supplies the lift machine room, with an isolator within sight of the controller, separate car lighting, and a two-way communication supply independent of normal power.
- PV inverter breaker sizing
- The PV inverter output circuit breaker is rated at least 1.25 times the inverter maximum output current, with a DC isolator at the array and an RCD type suited to the inverter topology.
- Data cable separation
- Communication and IT cables are routed at least 300 millimetres from power circuits or behind a grounded divider, with a bend radius of at least four times the cable diameter.
- Supervisor statutory duty
- The licensed supervisor certifies that executed work conforms to approved drawings, the building code, and the permit, filing stage reports that gate the occupancy certificate.
- Report submission stages
- Supervision reports are filed at defined stages, typically foundation, structure, and completion; withholding a report suspends further permits and blocks the occupancy certificate.
- Contract document hierarchy
- Order of precedence is agreement, conditions of contract, specification, drawings, and bill of quantities; for safety and code compliance the more stringent document prevails.