Iran Nezam Electrical Supervision Exam key terms
Iran Nezam Electrical Supervision Exam · Get comfortable with the vocabulary.
- Nezarat (Supervision) Endorsement
- Related: Design Verification Report, As-Built Documentation
The formal stamp and signature a licensed electrical supervisor places on design drawings and execution reports to certify conformity with approved standards, without which the installation may not legally be energized.
- Design Verification Report
- Related: Nezarat (Supervision) Endorsement, Load Schedule
A written supervisory document in which the licensed engineer records the checks performed on calculations, single-line diagrams, and equipment selection, and states whether the design is approved, conditionally approved, or rejected.
- As-Built Documentation
- Related: Design Verification Report, Panel Schedule
The final drawing set and equipment records updated to reflect the installation as actually constructed, handed to the owner and used by the supervisor to confirm that field changes were technically acceptable.
- Supervisor of Record
- Related: Nezarat (Supervision) Endorsement, Work Stoppage Order
The licensed engineer whose name appears on the permit and who carries legal responsibility for the electrical work's compliance, including duty to inspect, to order correction, and to report serious hazards.
- Work Stoppage Order
- Related: Supervisor of Record, Punch List
A written instruction by the supervising engineer halting electrical work that endangers life or property or departs from approved drawings, remaining in force until the defect is corrected and re-inspected.
- Punch List
- Related: Work Stoppage Order, As-Built Documentation
A itemized record of incomplete or nonconforming work identified at inspection, each item tracked to closure before provisional acceptance and energization of the installation.
- Illuminance (Lux)
- Related: Luminous Efficacy, Maintenance Factor
The luminous flux arriving per unit area on a working surface, expressed in lux, used to select lighting levels for offices, corridors, workshops, and escape routes according to the room's task.
- Maintenance Factor
- Related: Illuminance (Lux), Luminous Efficacy
A multiplier below one applied to calculated illuminance to account for lamp lumen depreciation and dirt accumulation on luminaires, ensuring maintained illuminance stays adequate between cleaning cycles.
- Luminous Efficacy
- Related: Illuminance (Lux), Power Density Limit
The ratio of luminous flux produced by a lamp to the electrical power it consumes, expressed in lumens per watt, and a primary input when comparing lamp technologies for an energy-compliant design.
- Power Density Limit
- Related: Luminous Efficacy, Load Schedule
The maximum permitted connected lighting or total electrical load per unit of floor area, used by the national code to cap energy use and checked by the supervisor against the lighting layout.
- Voltage Drop
- Related: Demand Factor, Load Schedule
The reduction in voltage along a circuit caused by conductor impedance under load, calculated from current, length, and conductor resistance and reactance, and kept within code limits at the furthest outlet.
- Demand Factor
- Related: Load Schedule, Diversity Factor
The ratio of the maximum demand over a period to the total connected load, applied to grouped loads such as receptacles or ranges so that feeders and service equipment are not oversized.
- Diversity Factor
- Related: Demand Factor, Load Schedule
The ratio of the sum of individual peak demands to the coincident maximum demand of the whole installation, used to size upstream transformers and main feeders realistically.
- Load Schedule
- Related: Panel Schedule, Demand Factor
A tabulation of every circuit and connected load with its demand factor, current, breaker rating, and cable size, forming the basis for panel, feeder, and service sizing.
- Panel Schedule
- Related: Load Schedule, Phase Balancing
A drawing of a distribution board showing circuit numbers, phase allocation, breaker ratings, connected loads, and spare ways, used to balance phases and to plan future expansion.
- Phase Balancing
- Related: Panel Schedule, Voltage Drop
The distribution of single-phase loads among the phases of a three-phase system so that phase currents and neutral current remain acceptably close, reducing losses and voltage unbalance.
- Ampacity
- Related: Derating Factor, Conductor Cross-Section
The maximum current a conductor can carry continuously under stated installation conditions without exceeding its rated temperature, determined from tables and then adjusted for ambient temperature and grouping.
- Derating Factor
- Related: Ampacity, Grouping Factor
A multiplier below one applied to tabulated current-carrying capacity to account for high ambient temperature, grouped cables, thermal insulation, or buried depth, reducing the permissible continuous current.
- Grouping Factor
- Related: Derating Factor, Ampacity
The correction applied when several loaded circuits run together in one conduit, trunking, or duct, because mutual heating prevents each cable from dissipating heat as if installed alone.
- Conductor Cross-Section
- Related: Ampacity, Voltage Drop
The nominal metallic area of a conductor in square millimetres, selected from ampacity, voltage drop, short-circuit withstand, and mechanical strength requirements rather than current alone.
- Conduit Fill
- Related: Conductor Cross-Section, Cable Tray
The proportion of a raceway's internal cross-section occupied by conductors, limited so that cables can be pulled without damage and heat can dissipate during operation.
- Cable Tray
- Related: Conduit Fill, Firestop Penetration Seal
A rigid metallic or non-metallic support system carrying cables in an accessible route, requiring consideration of fill, support spacing, fire barriers at wall penetrations, and bonding of sections.
- Equipotential Bonding
- Related: Earthing Electrode Resistance, Residual Current Device
The deliberate connection of exposed conductive parts, extraneous conductive parts, and the main earthing terminal so that dangerous potential differences cannot develop between them during a fault.
- Earthing Electrode Resistance
- Related: Equipotential Bonding, Earth Fault Loop Impedance
The resistance between a buried earth electrode and remote earth, measured to confirm that fault current has a low-impedance path and that touch voltages remain safe.
- Earth Fault Loop Impedance
- Related: Earthing Electrode Resistance, Overcurrent Protective Device
The total impedance of the path taken by fault current from the source through the live conductor, the fault, and the protective conductor back to the source, governing disconnection time.
- Residual Current Device
- Related: Equipotential Bonding, Selectivity
A protective device that trips when the vector sum of currents in the live conductors indicates earth leakage above its rated residual operating current, providing additional protection against electric shock.
- Overcurrent Protective Device
- Related: Earth Fault Loop Impedance, Selectivity
A breaker or fuse that interrupts current above its rating, and which must be coordinated with conductor ampacity so that it protects the cable against overload and short circuit.
- Selectivity
- Related: Overcurrent Protective Device, Short-Circuit Withstand Rating
The coordination of protective devices so that the device nearest a fault operates first, leaving upstream devices closed and limiting the outage to the smallest possible part of the installation.
- Short-Circuit Withstand Rating
- Related: Selectivity, Overcurrent Protective Device
The maximum prospective fault current a device or assembly can safely interrupt or withstand for a stated time, which must exceed the calculated fault level at its point of installation.
- Firestop Penetration Seal
- Related: Cable Tray, Emergency Lighting
A tested assembly restoring the fire resistance of a wall or floor where cables, conduits, or trays pass through it, installed and inspected as part of fire protection supervision.
- Emergency Lighting
- Related: Firestop Penetration Seal, Fire Alarm Zone
Battery-backed or centrally supplied lighting that maintains escape route illumination and exit signage for a defined duration when normal supply fails, subject to periodic discharge testing.
- Fire Alarm Zone
- Related: Emergency Lighting, Intrinsically Safe Circuit
A defined area of a building monitored by a detection circuit, arranged so that a fire can be located quickly and so that alarm and evacuation logic act on the correct part of the premises.
- Intrinsically Safe Circuit
- Related: Hazardous Area Classification, Fire Alarm Zone
A circuit designed so that its energy, including stored energy in capacitance and inductance, cannot ignite a flammable atmosphere under normal or specified fault conditions in a hazardous area.
- Hazardous Area Classification
- Related: Intrinsically Safe Circuit, Explosion-Protected Enclosure
The division of a space into zones according to the likelihood and duration of a flammable gas, vapour, or dust atmosphere, which then determines the permitted equipment protection concept.
- Explosion-Protected Enclosure
- Related: Hazardous Area Classification, Intrinsically Safe Circuit
An enclosure designed either to contain an internal explosion without transmitting flame or to prevent ignition by limiting surface temperature, breathing, and spark energy, marked with its protection concept and gas group.
- Uninterruptible Power Supply
- Related: Emergency Lighting, Structured Cabling
A system combining rectifier, battery, and inverter to supply loads without interruption during mains failure, with transfer time and autonomy matched to the criticality of the connected equipment.
- Structured Cabling
- Related: Uninterruptible Power Supply, Firestop Penetration Seal
A standardized hierarchy of copper and fibre cabling linking work areas, telecommunications rooms, and equipment rooms, with separation from power cabling to control interference and fire spread.
- Grid-Connected Inverter
- Related: Uninterruptible Power Supply, Short-Circuit Withstand Rating
Power conversion equipment synchronizing a renewable source with the utility supply, requiring anti-islanding protection, visible isolation, and coordination with the main protective devices.
- Protection Coordination Study
- Related: Selectivity, Short-Circuit Withstand Rating
An engineering analysis of time-current characteristics of fuses and breakers confirming that ratings, settings, and selectivity achieve safe disconnection while minimizing unnecessary outages.