Iran Nezam Mechanical Supervision Exam study materials
Iran Nezam Mechanical Supervision Exam study resources

Iran Nezam Mechanical Supervision Exam flashcards

Iran Nezam Mechanical Supervision Exam · Build recall with a focused review session.

37 cards. Read the term and the definition here. The deck at the top of this page is optional.

Sensible heat equation for air
Qs = 1.21 × airflow in L/s × temperature difference in °C, yielding watts. Used to size coils, ducts, and terminal units when moisture change is negligible.
Total coil load
Sum of sensible and latent loads. Latent heat equals 3.0 × airflow in L/s × humidity ratio difference in g/kg, giving watts.
Fan affinity laws
Flow varies linearly with speed, pressure with speed squared, and power with speed cubed. A ten percent speed reduction cuts power about twenty-seven percent.
Equal friction duct method
Select duct sizes so friction loss per unit length is constant across the system. Fan pressure is set by the index run and branches are balanced with dampers.
VAV minimum airflow
Typically thirty percent of design airflow, set to satisfy ventilation requirements. Verify outdoor air at the breathing zone per ASHRAE 62.1 at minimum flow.
Composite wall U-value
Reciprocal of the sum of inside surface resistance, layer resistances (thickness divided by conductivity), and outside surface resistance. Mabhas 19 limits maximum values.
Degree-day method
Annual heating energy approximately equals U×A times heating degree-days times twenty-four, divided by one thousand, in kilowatt-hours. Base temperature commonly eighteen degrees Celsius.
Cooling load versus solar gain
Peak solar gain through glass does not equal peak cooling load because of thermal storage and time lag. Use CLTD or transfer function methods for hourly loads.
Air-side economizer
Free cooling using outdoor air when its enthalpy is below return air enthalpy. Controlled by dry-bulb or enthalpy changeover; common in mild Iranian seasons.
Fixture unit method
Hunter method assigning water supply fixture units per fixture, summing them, and applying a probability curve to estimate probable peak flow.
Trap seal depth
Minimum fifty millimeters and maximum one hundred millimeters of water seal. Each fixture requires a trap except where the code explicitly lists an exception.
Drainage slope rule
Horizontal drainage branches up to one hundred millimeters diameter slope one to two percent; larger pipes at least one percent, per Mabhas 16 tables.
Residual pressure at fixture
Minimum one hundred to one hundred fifty kilopascals at the furthest fixture. If street pressure is insufficient, use a booster pump or gravity tank.
Hazen-Williams formula
Head loss equals 10.67 × length × flow^1.852 divided by C^1.852 × diameter^4.87 in SI units. C is about 140 for new plastic pipe.
Rational method
Storm flow equals runoff coefficient times rainfall intensity times catchment area. Use Iranian intensity-duration curves and minimum roof drain sizes per Mabhas 16.
Water hammer control
Use surge arrestors, slow-closing valves, and adequate pipe support. Limit supply main velocity to about one and a half to two and a half meters per second.
Roof tank head
Available pressure equals static height above the fixture minus friction losses. Check at peak flow using Hazen-Williams or Darcy-Weisbach calculations.
Sprinkler design density
Discharge rate per unit area over a specified remote area, set by occupancy hazard. Light hazard is typically 2.05 mm per minute over 140 square meters.
Fire pump churn pressure
Shutoff pressure must not exceed one hundred forty percent of rated pressure. At one hundred fifty percent flow, pressure must remain at least sixty-five percent of rated.
Stairwell pressurization
Maintain twenty-five to fifty pascals differential in the stairwell and about twelve and a half pascals in the lobby. Door opening force must not exceed 133 newtons.
Hydrant flow test
Measure static, residual, and pitot pressures, then extrapolate available flow at twenty pounds per square inch residual using the standard one-point conversion formula.
Natural gas heating value
Iranian natural gas typically has a lower heating value of thirty-five to thirty-eight megajoules per cubic meter. LPG vapor is about ninety-three megajoules per cubic meter.
Stoichiometric air demand
One cubic meter of natural gas needs about ten cubic meters of air for complete combustion. Boilers typically operate with twenty-five to fifty percent excess air.
Gas pipe pressure drop
Mabhas 17 sizing tables allow about one millibar loss in low-pressure residential systems. Use black steel indoors and buried, polyethylene only for buried exterior lines.
LPG vapor density
LPG vapor is heavier than air and accumulates at low points. Install leak detectors near the floor, unlike natural gas detectors which go near the ceiling.
Refrigeration COP
Cooling effect divided by compressor work. Carnot COP equals cold temperature divided by the difference between hot and cold temperatures, both in kelvin.
Chiller efficiency ranges
Water-cooled chillers typically draw 0.6 to 0.7 kilowatts per ton; air-cooled units about 0.9 to 1.1. Part-load IPLV values matter more than full-load ratings.
Cooling tower approach
Leaving condenser water temperature minus entering wet-bulb temperature, usually three to five kelvin at design. Condenser water is commonly supplied at twenty-nine to thirty-five degrees Celsius.
Evaporator superheat
Typically five to eight kelvin at the evaporator outlet, set by the thermostatic expansion valve. Excessive superheat signals undercharge or a restricted valve.
Mabhas 14 scope
Iranian national code chapter covering HVAC design: outdoor design conditions, ventilation rates, load calculation methods, and duct and pipe sizing criteria.
Mabhas 22 scope
Iranian national code chapter on energy efficiency in buildings: envelope thermal limits, HVAC equipment efficiency, lighting power density, and commissioning requirements.
Code hierarchy rule
Where the national building code and project specification differ, the stricter requirement governs. Always confirm the current edition and official amendments before approval.
Supervising engineer duties
Review shop drawings, approve materials, inspect installation, witness tests, and issue non-conformance reports. Only the registered engineer may seal drawings within their competence.
Conflict of interest disclosure
An engineer holding a financial interest in a contractor or supplier must disclose it and recuse from approval decisions involving that party.
Retention in payment certificates
Typically five to ten percent withheld from each payment until taking-over. Deduct advance payments according to the contract amortization schedule.
Mechanical quantity takeoff
Pipe measured along centerline excluding fittings; duct measured by surface area; equipment counted by unit. Apply the contract's standard method of measurement.
Variation order requirements
Must be issued in writing, priced at contract rates or agreed rates, and granted a time extension only if the critical path is affected.