Quick reference

Refrigeration Principles and System Components

  • Superheat = actual suction-line temperature minus saturated suction temperature at the same pressure; it is measured at the evaporator outlet.

  • Subcooling = saturated condensing temperature minus liquid-line temperature; it is measured at the condenser outlet.

  • Saturation temperature is the temperature at which refrigerant changes phase at a given pressure; evaporator and condenser operation is near saturation.

  • Compression ratio = absolute discharge pressure divided by absolute suction pressure; ratios above roughly 10:1 raise discharge temperature and reduce volumetric efficiency.

  • A TXV modulates refrigerant flow to maintain relatively constant evaporator superheat as load changes; a fixed orifice varies superheat with load.

  • R-410A is a near-azeotropic blend and must be charged as a liquid; it operates at roughly 50 to 70 percent higher pressures than R-22.

  • A standing vacuum decay test verifies tightness and dehydration; reaching and holding below 500 microns is a common acceptance target.

  • Bubbles in a liquid-line sight glass indicate flash gas from restriction, undercharge, or loss of subcooling, not necessarily a complete lack of charge.

Quick reference

Heating Equipment and Combustion Safety

  • Complete combustion of methane: CH4 + 2 O2 produces CO2 + 2 H2O; stoichiometric air is about 9.5 cubic feet of air per cubic foot of natural gas.

  • Carbon monoxide forms from incomplete combustion caused by insufficient air, poor fuel-air mixing, flame impingement, or a blocked flue.

  • Typical natural-gas manifold pressure is about 3.5 in. w.c.; typical LP manifold pressure is about 10 to 11 in. w.c.

  • A limit switch opens the burner circuit on excessive plenum or heat-exchanger temperature; it is a safety control, not an operating control.

  • A flame rollout switch is a manual-reset device that trips when flame exits the heat-exchanger inlet, often from a blocked flue or overfiring.

  • A thermocouple generates millivolts from pilot-flame heat to hold a standing pilot valve open; a thermopile generates higher voltage for control boards.

  • Temperature rise = supply air temperature minus return air temperature; it must fall within the furnace nameplate rise range at design airflow.

  • A combustion analyzer measures O2, CO2, CO, and flue temperature; air-free CO is used to compare readings independent of dilution.

Quick reference

Air Distribution, Ventilation, and Indoor Air Quality

  • Sensible heat in Btu/h = 1.08 times standard-air CFM times dry-bulb temperature difference.

  • Total heat in Btu/h = 4.5 times standard-air CFM times enthalpy difference.

  • The equal-friction method sizes ducts so each run has approximately the same friction loss per unit length.

  • External static pressure is the sum of supply and return static pressures the blower must overcome; it is compared with the fan performance table.

  • MERV rates filter capture efficiency; higher MERV generally increases pressure drop and may reduce airflow if the fan cannot compensate.

  • ASHRAE 62.2 whole-house ventilation rate is approximately 3 CFM per 100 square feet of conditioned floor area plus 7.5 times the bedroom count plus one.

  • Duct leakage testing measures leakage to outside; sealing with mastic at joints and seams reduces loss better than tape alone.

  • A room becomes positively pressured when supply airflow exceeds return and exhaust airflow; it becomes negatively pressured when exhaust exceeds supply.

  • Flex duct pressure loss rises sharply with sag, compression, and tight bends; support and straighten runs to preserve capacity.

Quick reference

Electrical Systems, Motors, and Controls

  • Ohm's law: E = I times R; for AC single-phase loads, power in watts = E times I times power factor.

  • Locked rotor amps is current at motor standstill; running load amps is normal operating current.

  • The branch-circuit breaker protects conductors; the motor overload protects the motor winding from sustained overcurrent.

  • A run capacitor remains in the circuit during operation to improve phase angle and motor torque.

  • A potential relay removes the start capacitor from the circuit when motor back-EMF voltage rises after startup.

  • A 24-volt control transformer must have VA capacity at least equal to the connected control load.

  • A contactor coil is controlled by the thermostat; its contacts switch line-voltage power to the compressor or fan.

  • Typical furnace ignition sequence: call for heat, inducer starts, pressure switch proves, igniter heats, gas valve opens, flame sensor proves.

Quick reference

Load Calculation, Sizing, and System Design

  • Manual J calculates room-by-room heating and cooling loads from envelope, infiltration, internal gains, and solar effects.

  • Manual S selects equipment using Manual J loads and manufacturer capacity tables at design conditions.

  • Manual D sizes ducts from room airflows, available static pressure, and friction rate.

  • Q = U times A times temperature difference calculates conduction heat transfer; U = 1 divided by R-value.

  • Sensible heat ratio = sensible load divided by total load; a low ratio means more latent moisture removal is needed.

  • Cooling design typically uses 1 percent outdoor dry-bulb and indoor 75 degrees Fahrenheit at 50 percent relative humidity; heating design uses 99 percent outdoor dry-bulb and indoor 70 degrees Fahrenheit.

  • Oversizing shortens run time, reduces latent removal, and increases cycling; equipment capacity is matched to calculated load rather than a rule of thumb.

  • Duct loads and ventilation loads must be included in total equipment capacity; they are not free capacity.

Quick reference

Codes, Permits, and Business/Regulatory Practices

  • HVAC permits are issued by local code authorities before installation or alteration; work is inspected against the adopted code.

  • EPA Section 608 certification is required to service or dispose of appliances containing regulated refrigerants; intentional venting is prohibited.

  • Kentucky HVAC contractor licensing is administered by the Department of Housing, Buildings and Construction.

  • The Kentucky Building Code adopts model codes with state amendments; local jurisdictions may add permit and inspection requirements.

  • A mechanic's lien is a legal claim against property for unpaid labor or materials; notice and filing deadlines vary by state.

  • A written change order documents scope, price, and schedule changes before extra work proceeds.

  • Contract documents typically include scope, exclusions, payment terms, warranty, and insurance; they define the contractor's obligations.