General Electrical Knowledge and Code Administration

  • The NEC is arranged in nine chapters: Chapters 1-4 contain general rules, Chapters 5-7 supplement or modify them for special occupancies, conditions, and equipment, Chapter 8 covers communications systems, and Chapter 9 contains reference tables.

  • Informational Notes are explanatory only and are not enforceable; mandatory requirements are stated with 'shall' (Article 90).

  • Ampacities in Table 310.16 assume a 30 degrees C ambient temperature and no more than three current-carrying conductors in the raceway or cable.

  • Terminations for circuits rated 100 A or less are limited to the 60 degrees C ampacity column unless the equipment is listed and marked for a higher termination temperature (110.14(C)).

  • Table 110.26(A)(1) working-space depth: 3 ft for 0-150 V to ground, 3.5 ft for 151-600 V, 4 ft for 601-2500 V; minimum width 30 in.; minimum height 6 ft 6 in.

  • The working space in front of electrical equipment must be clear and the footprint must be dedicated exclusively to electrical equipment (110.26(E)).

  • Section 90.4 gives the authority having jurisdiction responsibility for interpreting the code, approving listed materials and methods, and granting written approval of alternate installations.

  • In Michigan, electrical contractors, master and journeyman electricians, and apprentices are licensed under the Electrical Administrative Act, Public Act 217 of 1956, administered through the Bureau of Construction Codes.

  • Michigan adopts the NEC by reference with state amendments as the Michigan Electrical Code; the edition currently in effect governs plan review and field inspection.

Quick reference

Services, Feeders, and Branch Circuits

  • 230.79(C): the service disconnecting means for a one-family dwelling must have a rating of not less than 100 A.

  • 230.71: service disconnecting means must be grouped in one location, and where multiple means are permitted no more than six are allowed.

  • 310.12: 120/240 V single-phase service and feeder conductors supplying a dwelling unit may be sized at 83 percent of the service rating, with a 100 A minimum service.

  • 220.12: the general lighting load for a dwelling unit is calculated at 3 VA per square foot of floor area.

  • 210.11(C)(1): at least two 20 A small-appliance branch circuits are required for kitchen, dining, pantry, and similar receptacle outlets, and no other outlets may be supplied from them (210.52(B)(2)).

  • 210.52(A)(1): in dwelling units, no point along the floor line of any wall space may be more than 6 ft from a receptacle outlet (the 6 ft / 12 ft rule).

  • 210.52(C)(1): no point along a kitchen countertop wall line may be more than 24 in. from a receptacle outlet; islands and peninsulas require at least one receptacle.

  • Informational Notes to 210.19(A) and 215.2(A): voltage drop should not exceed 3 percent on a branch circuit or 5 percent total for feeder plus branch circuit.

  • 210.20(A): the branch-circuit overcurrent device rating must not be less than the branch-circuit conductor ampacity, and the conductors must have an ampacity not less than the load.

Quick reference

Wiring Methods, Materials, and Raceways

  • Chapter 9 Table 1 raceway fill: 53 percent for one conductor, 31 percent for two conductors, and 40 percent for three or more conductors of the interior cross-sectional area.

  • 358.30: electrical metallic tubing must be fastened within 3 ft of each box or termination and supported at intervals not exceeding 10 ft.

  • 334.30: nonmetallic-sheathed cable must be secured within 12 in. of each box and supported at intervals not exceeding 4.5 ft.

  • 300.4(A): cable or raceway through bored framing members must be at least 1-1/4 in. from the nearest edge, or protected by a steel plate at least 1/16 in. thick.

  • 314.16(B) box-fill volume per conductor: 14 AWG = 2.00 cu in., 12 AWG = 2.25 cu in., 10 AWG = 2.50 cu in.; each yoke or device counts as one conductor, and all equipment grounding conductors count together as one.

  • 314.28(A): pull-box length must be at least 8 times the trade size of the largest raceway for straight pulls, and 6 times for angle or U pulls measured between raceway entries.

  • 200.6: grounded conductors 6 AWG and smaller must be white or gray, or identified with white or gray marking at terminations.

  • 250.119: equipment grounding conductors must be bare, green, or green with one or more yellow stripes; white and gray are not permitted.

  • 310.15(B)(3)(a) ampacity adjustment for more than three current-carrying conductors in a raceway or cable: 4-6 conductors 80 percent, 7-9 conductors 70 percent, 10-20 conductors 50 percent.

Quick reference

Equipment, Devices, and Utilization Equipment

  • 430.22: motor branch-circuit conductors must have an ampacity of at least 125 percent of the motor full-load current from Table 430.248 or 430.250.

  • Table 430.52 maximum branch-circuit short-circuit protection for motors: inverse-time breaker 250 percent, dual-element fuse 175 percent, non-time-delay fuse 300 percent of full-load current.

  • 430.32: motor overload protection is sized from the nameplate service factor and temperature rise, generally 115 to 125 percent of full-load current.

  • 440.6 and 440.32: air-conditioning equipment is wired using the nameplate minimum circuit ampacity for conductors and the nameplate maximum overcurrent rating for the protective device.

  • 404.8(A): switches and circuit breakers used as switches must not be located more than 6 ft 7 in. above the floor or working platform.

  • 406.12: listed tamper-resistant receptacles are required in dwelling units, guest rooms, and specified child-care and educational occupancies.

  • 410.8: luminaires in clothes closets require 12 in. of clearance from storage space for surface-mounted incandescent types and 6 in. for recessed incandescent types.

  • 450.3(B): where only primary protection is provided for a transformer rated 1000 V or less, the primary overcurrent device may not exceed 125 percent of primary current when primary current is 9 A or more.

  • 210.21(B)(1): a single receptacle on an individual branch circuit must have a rating not less than the rating of the branch circuit.

Quick reference

Grounding, Bonding, Overcurrent Protection, and Special Occupancies

  • 250.52(A): grounding electrodes include metal underground water pipe (10 ft or more of contact), metal building frame, concrete-encased electrode (20 ft of 1/2 in. rebar), ground ring (20 ft), rod or pipe electrode (8 ft), and plate electrodes.

  • 250.53(A)(2): a single rod, pipe, or plate electrode must have a resistance to earth of 25 ohms or less, or a supplemental electrode must be added.

  • Table 250.66 copper grounding electrode conductor: 2 AWG or smaller service conductors = 8 AWG; 2/0-3/0 = 4 AWG; over 350 through 600 kcmil = 1/0; over 1100 kcmil = 3/0.

  • Table 250.122 copper equipment grounding conductor: 15 A = 14 AWG, 20 A = 12 AWG, 30-60 A = 10 AWG, 100 A = 8 AWG, 200 A = 6 AWG, 300 A = 4 AWG, 400 A = 3 AWG, 600 A = 1 AWG.

  • 250.122(B): where phase conductors are increased in size above the code minimum, the equipment grounding conductor must be increased proportionally by circular mil area.

  • 240.4(D): small conductor overcurrent limits are 15 A for 14 AWG copper, 20 A for 12 AWG copper, and 30 A for 10 AWG copper, unless specifically permitted elsewhere.

  • 240.4(B): the next higher standard overcurrent device is permitted where conductor ampacity does not exceed 800 A, the device rating does not exceed 800 A, and the circuit is not a multioutlet receptacle branch circuit.

  • Class I Division 1 locations are those where ignitable concentrations of flammable gases, vapors, or liquids exist under normal operating conditions; Division 2 locations have them only in abnormal conditions (500.5).

  • 501.15: in Class I locations, a sealing fitting must be installed within 18 in. of the enclosure boundary on raceways leaving the classified area.