Quick reference

Drinking Water Treatment

  • CT (contact time) = disinfectant residual concentration (mg/L) × effective contact time (min); CT requirements rise as temperature falls and pH rises for chlorine.

  • Chlorine demand = dose applied − free chlorine residual remaining after the contact period; it reflects oxidizable matter in the water.

  • Turbidity limits under the Surface Water Treatment Rule: 0.3 NTU in 95% of monthly samples, never above 1 NTU; combined filter effluent monitored continuously.

  • Log inactivation credit for Giardia and viruses depends on disinfectant type, residual, contact time, pH, and temperature; Crypto is only creditable with UV or ozone.

  • Coagulation optimum pH is generally 5.5–7.5 for alum; jar tests determine the lowest dose producing settled and filtered clarity.

  • Filter loading rate = flow (gpm) ÷ filter area (ft²); rapid sand filters typically operate at 2–5 gpm/ft².

  • Backwash rate must expand the bed roughly 20–30%; typical rapid sand backwash is 12–20 gpm/ft².

  • Langelier Saturation Index near 0 means balanced water; negative is corrosive, positive is scale-forming.

  • Fluoride is dosed to about 0.7 mg/L; the MCL is 4.0 mg/L and the secondary standard is 2.0 mg/L.

Quick reference

Drinking Water Distribution

  • Minimum residual: 0.2 mg/L free chlorine (or 0.5 mg/L chloramine) at points of entry and throughout the distribution system in Missouri.

  • Pressure must remain at least 20 psi at all points under normal conditions; a main break or pump failure that drops below 20 psi triggers a boil order.

  • Theoretical water horsepower = (gpm × head in ft) ÷ 3960; brake horsepower = water hp ÷ pump efficiency.

  • Detention time in a storage tank = tank volume ÷ flow rate; use consistent units (e.g., gallons ÷ gpm = minutes).

  • Hydrant flow test: static pressure, residual pressure, and pitot pressure determine available flow; a 20 psi residual is the standard reference point.

  • Coliform rule: total coliform positive triggers repeat sampling; E. coli-positive or repeat-positive results require public notice within 24 hours.

  • Water main flushing velocities of about 2.5–3 ft/s and above are needed to scour sediment; dead ends are flushed on a routine schedule.

  • Cross-connection protection: an air gap is the only true backflow prevention; RPZ, double check, and PVB devices protect specific hazard levels.

  • Pipe velocity = flow ÷ cross-sectional area; convert gpm to cfs by dividing by 448.8 before dividing by area.

Quick reference

Wastewater Treatment

  • BOD5 measures oxygen consumed over 5 days at 20°C; typical domestic wastewater is about 200–250 mg/L BOD and 200–250 mg/L TSS.

  • F/M ratio = (lbs BOD applied per day) ÷ (lbs MLVSS in aeration); typical conventional activated sludge runs 0.2–0.5.

  • MCRT (sludge age) = lbs MLSS in aeration ÷ lbs solids leaving per day; controls sludge blanket and effluent quality.

  • Solids loading rate on secondary clarifiers = lbs/day ÷ (surface area × 1,000); typical design is 12–30 lbs/day/1,000 ft².

  • Hydraulic detention time = tank volume ÷ flow; aeration basins typically hold 4–8 hours.

  • Return activated sludge rate typically runs 50–150% of influent flow; high SVI (>150) indicates poor settling (bulking).

  • Chlorine disinfection CT for wastewater uses fecal coliform limits (typically 200/100 mL monthly geometric mean in Missouri); ammonia interferes with chlorine demand.

  • Anaerobic digesters reduce volatile solids and produce methane; typical operating temperature is 95–98°F (mesophilic).

  • Effluent limits often include BOD 30 mg/L, TSS 30 mg/L, and ammonia; Missouri uses both monthly averages and weekly averages.

Quick reference

Wastewater Collection

  • Minimum gravity sewer slope for 8-inch pipe is typically 0.40% (about 0.004 ft/ft); smaller pipe needs steeper slopes, larger pipe can be flatter.

  • Use Manning's equation: velocity = (1.486/n) × R^(2/3) × S^(1/2), where n ≈ 0.013 for new vitrified clay or PVC.

  • Self-cleansing velocity is about 2 ft/s; below that, solids settle and cause blockages.

  • Infiltration is groundwater entering through defects; inflow is direct stormwater entering through manholes, roof drains, or illegal connections.

  • Lift station wet well detention time should stay under 30 minutes to prevent septic conditions and odor.

  • Sewer cleaning: high-velocity jetting (1,000–2,000 psi) for grease and roots; bucket machines for heavy debris.

  • Confined space entry requires atmospheric testing for oxygen (19.5–23.5%), LEL (<10%), and H2S (<10 ppm) before entry.

  • Sewer smoke testing reveals inflow sources and illegal connections; dye testing confirms specific connections.

  • Manhole inspection frequency depends on pipe condition; CCTV inspection rates pipes on a condition scale of 1–5.