NABCEP PV Associate: Electrical safety and the National Electrical Code (NFPA 70)

NABCEP PV Associate · Work through your exam, one topic at a time.

All guide sections

Electrical safety and the National Electrical Code (NFPA 70)

What the exam tests

Electrical safety and the NEC domain tests Article 690 and related articles as they apply to PV: maximum voltage and current calculations, disconnects, overcurrent protection, rapid shutdown, grounding, and safe work practices.

Core rules

  • Treat PV source and output circuits as energized whenever the array is illuminated. There is no single upstream breaker that de-energizes the DC side; use lockout/tagout, insulated tools, and rated PPE.
  • 690.7: maximum PV system voltage is the temperature-corrected Voc sum. 690.8(A): maximum current is 125% of Isc (or the sum for parallel strings). 690.8(B): conductor ampacity is at least 125% of that maximum current before adjustment. 690.9: required overcurrent devices are also sized from the 690.8(A) current with the 125% factor.
  • 690.12 rapid shutdown: controlled conductors must be reduced to a safe voltage within 30 seconds after shutdown; the threshold depends on location relative to the array boundary (commonly 80 V inside, 30 V outside under the 2017/2020 NEC; verify the edition in force).
  • 690.13 and 690.15 require disconnecting means for PV circuits; 690.31 governs wiring methods, and 690.47 addresses grounding electrode connections. Article 250 and 310 apply for equipment grounding and ampacity.
  • Only qualified persons should work on PV electrical systems; use a properly rated meter and verify zero energy before touching conductors.

Worked example

Two parallel strings each have Isc = 10 A. Under 690.8(A), maximum current = 2 × 10 A × 1.25 = 25 A. Conductors must have an ampacity of at least 125% of 25 A = 31.25 A before adjustment; any required overcurrent device is selected with the same 125% factor. Do not apply the 125% factor to Voc; voltage and current calculations use different inputs.

Traps

  • Applying the 125% factor to voltage instead of current.
  • Assuming opening the inverter DC disconnect de-energizes the array conductors.
  • Confusing rapid-shutdown voltage and time thresholds, or forgetting the array boundary.
  • Using AC breaker sizing rules for DC circuits without checking DC ratings.