NABCEP PVIS flashcards
NABCEP PVIS · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- STC vs NMOT
- STC: 1000 W/m², 25 °C cell, AM 1.5. NMOT/PTC: ~800 W/m², 20 °C ambient, 1 m/s wind, open rack. NMOT ratings are typically 10–15% lower than STC.
- Temperature coefficient of Voc
- Negative value (about −0.25 to −0.35%/°C for c-Si) used to calculate cold-temperature maximum string voltage. Cold increases Voc, so size strings for record-low temperature.
- Cold-temperature string sizing
- Vmax_string = N × Voc × [1 + βVoc × (Tmin − 25)]. N must keep this value below inverter max DC input voltage and any 600/1000/1500 V system limit.
- Hot-temperature string sizing
- Vmp_string = N × Vmp × [1 + βVmp × (Thot − 25)]. The result must remain above the inverter MPPT lower voltage limit to avoid derating or dropout.
- NEC 690.8 continuous current
- PV source and output circuits are continuous; multiply by 1.25 for conductor ampacity and overcurrent device sizing. Inverter output circuits also use 1.25× rated output current.
- Rapid shutdown 690.12
- Conductors within 1 ft of the array boundary must be limited to 30 V or less within 30 seconds of shutdown initiation. Module-level or string-level electronics typically provide compliance.
- DC/AC ratio (clipping)
- Array STC kW divided by inverter AC kW. Fixed-tilt systems commonly use 1.1–1.3; higher ratios clip more at peak but harvest more at low irradiance and diffuse conditions.
- Voltage drop formula
- Vdrop = 2 × L × I × R for two-wire DC circuits, where L is one-way length and R is conductor resistance at operating temperature. Keep DC drop ≤ 2–3%.
- String fuse rating
- Fuse must be ≥ 1.25 × Isc (per 690.8) and ≤ the module maximum series fuse rating. Parallel strings of three or more require string overcurrent protection.
- Irradiance vs irradiance units
- Irradiance is instantaneous power density in W/m²; irradiation (insolation) is energy per area in kWh/m²/day. Design uses irradiance for power and irradiation for energy yield.
- Air mass (AM)
- Ratio of path length through atmosphere to vertical path. AM 1.5 is the reference spectrum for STC; higher AM (low sun) shifts spectrum and reduces output.
- Shading analysis tools
- Solmetric SunEye, Solar Pathfinder, and 3D modeling (Helioscope, PVsyst, Aurora) quantify horizon shading. Use hourly simulation for inter-row and object shading losses.
- Row spacing calculation
- Minimum row spacing = collector height × cos(azimuth tilt) / tan(solar altitude at winter solstice). Use 9 a.m.–3 p.m. window to avoid inter-row shading.
- Grounding electrode system
- NEC 250 requires bonding PV module frames, racking, and inverter enclosures to the equipment grounding conductor; array mounting structures need a grounding electrode conductor sized per 250.66.
- GFCI vs GFDI
- GFCI protects personnel from ground faults on AC circuits. GFDI (ground-fault detection and interruption) is required on grounded PV arrays by NEC 690.5 to detect DC ground faults.
- Arc-fault circuit protection
- NEC 690.11 requires DC arc-fault circuit protection on PV systems operating at 80 V or more. Listed AFCI devices detect series arcs and interrupt the circuit.
- Module IV curve
- Plot of current vs voltage. Key points: Isc (short circuit), Vmp (max power voltage), Imp, Voc. Fill factor = (Vmp × Imp)/(Voc × Isc); higher FF means better cell quality.
- Bypass diode function
- Allows current to bypass a shaded or failed cell substring, preventing hot spots and reducing mismatch loss. Typically one diode per 20–24 cells in a module.
- Blocking diode function
- Prevents reverse current from flowing into a lower-voltage string or battery. Rarely needed with modern string inverters that have integrated reverse-current protection.
- Inverter efficiency (CEC)
- California Energy Commission weighted efficiency accounts for part-load performance. Typical string inverters: 96–98%; microinverters: 95–97%. Use CEC value for energy yield estimates.
- Performance ratio (PR)
- Ratio of actual AC energy to theoretical DC energy at STC irradiance. PR of 0.75–0.85 is typical; losses include temperature, soiling, mismatch, wiring, and inverter.
- Soiling loss
- Energy lost to dirt, dust, bird droppings, and snow on modules. Typical 2–5% annually in moderate climates; higher in arid or agricultural areas. Cleaning schedule based on measured loss.
- Module mismatch
- Power loss when series-connected modules have different current or voltage due to shading, soiling, or manufacturing tolerance. String sizing and sorting by flash-test data reduce mismatch.
- Battery depth of discharge
- Percentage of capacity withdrawn from a battery. Lead-acid typically limited to 50% DoD for cycle life; lithium-ion can often reach 80–100% DoD with BMS protection.
- Charge controller MPPT vs PWM
- MPPT controllers track the array's max power point and convert voltage, giving 10–30% more harvest in cold or low-irradiance conditions. PWM is simpler and less efficient.
- Article 690 vs 705
- NEC 690 covers PV source and output circuits. Article 705 covers interconnections of power production sources with primary or secondary distribution systems, including load-side taps.
- Supply-side connection
- PV system connected on the line side of the main service disconnect. Requires a dedicated disconnect and often utility approval; no 120% busbar rule applies.
- 120% busbar rule
- NEC 705.12(B): sum of main breaker plus backfed PV breaker must not exceed 120% of busbar rating, unless the PV breaker is at the opposite end of the busbar.
- Line-side tap
- Connection made between the utility meter and the main service disconnect. Must comply with NEC 230.82 and utility interconnection requirements; typically requires a visible disconnect.
- Inverter anti-islanding
- Required by UL 1741: inverter must detect loss of grid and stop exporting within 2 seconds. Prevents backfeeding during outages and protects line workers.
- Module-level power electronics
- Microinverters or DC optimizers mounted at each module. Enable per-module MPPT, rapid shutdown compliance, and module-level monitoring, at higher cost and component count.
- Structural dead load
- Flush-mounted PV adds roughly 2–4 lb/ft² to a roof; ballasted flat-roof systems add 3–7 lb/ft². Verify against structural engineer's allowable load and local snow/wind loads.