NABCEP PVSI key terms
NABCEP PVSI · Get comfortable with the vocabulary.
- Rapid Shutdown
- Related: NEC 690.12, Module-Level Power Electronics, Array Disconnect
A code-required function that reduces conductor voltage at the array to a safe level, typically 30 volts or less within 30 seconds, for firefighters and first responders. It applies to roof-mounted PV systems on buildings.
- NEC 690.12
- Related: Rapid Shutdown, Module-Level Power Electronics, Labeling Requirements
The National Electrical Code section governing rapid shutdown of PV systems, defining controlled conductors, the 1-foot boundary, and voltage and time limits for array shutdown initiation.
- Module-Level Power Electronics
- Related: Rapid Shutdown, String Inverter, DC Optimizer
Devices such as microinverters or DC optimizers mounted at or near each module that provide per-module conversion or control, often enabling rapid shutdown compliance and module-level monitoring.
- DC Optimizer
- Related: Module-Level Power Electronics, Maximum Power Point Tracking, Rapid Shutdown
A DC-to-DC converter installed per module that performs maximum power point tracking and can reduce array voltage on command, commonly used to satisfy rapid shutdown requirements.
- String Inverter
- Related: Module-Level Power Electronics, DC-to-AC Ratio, Maximum Power Point Tracking
A central inverter that converts DC power from one or more series-connected module strings into grid-compatible AC power, typically with integrated disconnects, monitoring, and protective functions.
- Maximum Power Point Tracking
- Related: String Inverter, DC Optimizer, Irradiance
An inverter control algorithm that continuously adjusts operating voltage and current to extract the greatest available power from a PV array as irradiance and temperature change.
- Irradiance
- Related: Maximum Power Point Tracking, Performance Ratio, Standard Test Conditions
The instantaneous power density of solar radiation falling on a surface, usually expressed in watts per square meter. It drives array output and is measured with a pyranometer or reference cell.
- Standard Test Conditions
- Related: Irradiance, Temperature Coefficient, Nameplate Rating
The reference conditions used to rate PV modules: 1,000 watts per square meter irradiance, 25 degrees Celsius cell temperature, and a specified air mass spectrum. Ratings appear on module nameplates.
- Temperature Coefficient
- Related: Standard Test Conditions, Nameplate Rating, Cell Temperature
The rate at which a module's power, voltage, or current changes per degree Celsius of cell temperature, usually negative for power. It predicts output loss on hot roofs.
- Nameplate Rating
- Related: Standard Test Conditions, Temperature Coefficient, DC-to-AC Ratio
The manufacturer's labeled electrical values for a component, such as module maximum power or inverter AC output, used as the basis for code calculations and system sizing.
- DC-to-AC Ratio
- Related: Nameplate Rating, String Inverter, Clipping
The ratio of array DC nameplate capacity to inverter AC rated output. A ratio above one indicates intentional oversizing to improve production during low-irradiance periods and reduce clipping losses.
- Clipping
- Related: DC-to-AC Ratio, Performance Ratio, String Inverter
The loss of harvestable energy that occurs when array DC output exceeds the inverter's maximum AC capacity, causing the inverter to limit power during high-irradiance periods.
- Performance Ratio
- Related: Irradiance, Clipping, Monitoring Portal
The ratio of actual energy produced to the theoretical energy expected from measured irradiance and nameplate capacity, expressed as a percentage. It normalizes for weather and location.
- NEC Article 690
- Related: NEC 690.12, NEC 705.12, Labeling Requirements
The primary National Electrical Code article covering solar photovoltaic systems, including circuit sizing, disconnects, grounding, marking, and interconnection requirements for PV power systems.
- NEC 705.12
- Related: NEC Article 690, Supply-Side Connection, Load-Side Connection
The code section governing interconnection of power production sources to premises wiring, including busbar and feeder load-side connection rules and the 120 percent busbar allowance.
- Supply-Side Connection
- Related: Load-Side Connection, NEC 705.12, Service Disconnect
A PV interconnection made on the line side of the main service disconnect, typically requiring a dedicated disconnect and utility coordination rather than relying on busbar capacity rules.
- Load-Side Connection
- Related: Supply-Side Connection, NEC 705.12, Busbar Rating
A PV interconnection made on the load side of the service disconnect, commonly a backfed breaker, subject to busbar and feeder ampacity limits in the code.
- Busbar Rating
- Related: Load-Side Connection, NEC 705.12, Main Breaker
The ampere capacity of a panelboard's internal bus, used with breaker ratings to verify that a backfed PV breaker does not overload the panel under the applicable code allowance.
- Main Breaker
- Related: Busbar Rating, Load-Side Connection, Overcurrent Protection Device
The primary overcurrent device protecting a service panel, whose rating is a key input when calculating allowable PV backfeed capacity on a load-side interconnection.
- Overcurrent Protection Device
- Related: Main Breaker, Series Fuse Rating, Combiner Box
A fuse or circuit breaker that interrupts excessive current to protect conductors and equipment. In PV circuits it must be rated for DC and for the array's fault-current characteristics.
- Series Fuse Rating
- Related: Overcurrent Protection Device, Combiner Box, String Sizing
The maximum overcurrent protection value specified by a module manufacturer for a single string, used to size string fuses and verify reverse-current protection adequacy.
- Combiner Box
- Related: Series Fuse Rating, String Sizing, Array Disconnect
An enclosure where multiple PV source circuits are paralleled, often containing string fuses, a DC disconnect, and busbars, providing a single output to the inverter or charge controller.
- String Sizing
- Related: Open-Circuit Voltage, Temperature Coefficient, Combiner Box
The calculation of modules per series string so that cold-temperature open-circuit voltage stays below equipment limits and hot-temperature operating voltage stays within inverter tracking range.
- Open-Circuit Voltage
- Related: String Sizing, Temperature Coefficient, Maximum System Voltage
The voltage measured across a PV source with no load connected. It rises as cell temperature falls and is used to verify maximum system voltage compliance.
- Maximum System Voltage
- Related: Open-Circuit Voltage, String Sizing, Labeling Requirements
The highest voltage a module or system component is rated to withstand, such as 600 or 1,500 volts. String voltage at record low temperature must not exceed it.
- Array Disconnect
- Related: Rapid Shutdown, Combiner Box, Labeling Requirements
A switch or breaker that isolates the PV array from the rest of the system, required to be readily accessible and clearly labeled for service and emergency use.
- Labeling Requirements
- Related: Rapid Shutdown, Array Disconnect, Maximum System Voltage
Code-mandated placards and markings identifying PV disconnects, maximum voltages, rapid shutdown equipment, and power sources, ensuring responders and service personnel can operate safely.
- Grounding Electrode Conductor
- Related: Equipment Grounding Conductor, Bonding Jumper, Ground Fault Protection
The conductor that connects the system's grounding point to the grounding electrode, providing a path for fault current and stabilizing voltage reference for the electrical system.
- Equipment Grounding Conductor
- Related: Grounding Electrode Conductor, Bonding Jumper, Ground Fault Protection
The conductor that bonds non-current-carrying metal parts of equipment, such as module frames and racking, to the grounding system to clear faults safely.
- Bonding Jumper
- Related: Equipment Grounding Conductor, Grounding Electrode Conductor, Ground Fault Protection
A conductor that ensures electrical continuity between metal parts, such as module frames and rails, so they remain at the same potential and can carry fault current.
- Ground Fault Protection
- Related: Equipment Grounding Conductor, Insulation Resistance Test, Commissioning
A system that detects unintended current flow to ground in PV circuits and interrupts or isolates the fault, required for many grounded and ungrounded array configurations.
- Insulation Resistance Test
- Related: Ground Fault Protection, Commissioning, Megohmmeter
A measurement of resistance between energized conductors and ground, performed during commissioning or troubleshooting to detect damaged cable, moisture intrusion, or degraded insulation.
- Megohmmeter
- Related: Insulation Resistance Test, Commissioning, IV Curve Tracer
An instrument that applies a high test voltage to measure insulation resistance in megohms, used to verify conductor and equipment insulation integrity before energizing a PV system.
- IV Curve Tracer
- Related: Megohmmeter, Open-Circuit Voltage, Performance Ratio
A diagnostic instrument that sweeps a PV string's current-voltage characteristic to compare actual performance against expected values and identify shading, soiling, or module faults.
- Commissioning
- Related: Insulation Resistance Test, Punch List, As-Built Drawings
The documented process of verifying that an installed PV system meets design intent and code requirements through inspection, testing, and functional performance checks before handover.
- Punch List
- Related: Commissioning, Site Inspection, As-Built Drawings
A written record of deficiencies found during inspection that must be corrected before project acceptance, tracked to closure and referenced in the final inspection report.
- Site Inspection
- Related: Punch List, As-Built Drawings, Plan Review
A structured on-site review of installed work against approved plans and code, covering structural attachment, clearances, labeling, wiring methods, and safety access.
- As-Built Drawings
- Related: Plan Review, Site Inspection, Single-Line Diagram
Construction documents revised to reflect actual installed conditions, including equipment locations, routing, and ratings, used for inspection, maintenance, and future service.
- Plan Review
- Related: As-Built Drawings, Single-Line Diagram, Site Plan
The pre-construction examination of permit drawings for code compliance, checking structural loads, electrical calculations, clearances, and labeling before work begins.
- Single-Line Diagram
- Related: As-Built Drawings, Plan Review, Load-Side Connection
A schematic showing the electrical topology of a PV system with one line per circuit, including disconnects, overcurrent devices, grounding, and interconnection points.
- Site Plan
- Related: Plan Review, Setback, As-Built Drawings
A scaled drawing showing the property, building footprint, array layout, equipment locations, setbacks, and access paths, used for permitting and inspection planning.
- Setback
- Related: Site Plan, Roof Access Pathway, Plan Review
The required distance between PV equipment and roof edges, ridges, or access pathways, set by fire or building code to preserve firefighter access and ventilation.
- Roof Access Pathway
- Related: Setback, Site Plan, Rapid Shutdown
A clear, code-specified path on a roof allowing firefighters to move safely around and above PV arrays, affecting array layout and module placement.
- Structural Load Calculation
- Related: Plan Review, Structural Attachment, Site Plan
An engineering assessment of dead, live, wind, and snow loads imposed by PV racking on a building, confirming the roof structure can safely carry the added weight.
- Structural Attachment
- Related: Structural Load Calculation, Site Inspection, Flashing
The method and hardware connecting PV racking to the building structure, such as lag screws, adhesives, or ballast, verified during inspection for correct type and spacing.
- Flashing
- Related: Structural Attachment, Site Inspection, Punch List
A weatherproofing detail around roof penetrations that directs water away from fasteners and mounts, preventing leaks at structural attachment points.
- Monitoring Portal
- Related: Performance Ratio, Commissioning, String Inverter
A web or app platform that collects inverter and sensor data to display production, alarms, and historical trends, supporting performance verification and warranty claims.
- Service Disconnect
- Related: Supply-Side Connection, Load-Side Connection, Main Breaker
The switch or breaker that disconnects the building's service conductors from the utility, serving as the reference point for supply-side and load-side PV interconnections.