32 cards. Read the term and the definition here. The deck at the top of this page is optional.

Reversing valve function
A four-way solenoid valve that swaps the roles of the indoor and outdoor coils, allowing the same refrigerant circuit to provide both heating and cooling.
Balance point
The outdoor temperature at which heat pump heating capacity equals the building heat loss; below this point, supplementary heat is required to maintain indoor temperature.
Coefficient of performance
The ratio of heat delivered to electrical energy consumed, expressed as a dimensionless number; higher COP means more efficient heating at a given outdoor temperature.
Accumulator purpose
A vessel on the suction line that traps liquid refrigerant and oil, releasing them gradually to the compressor to prevent liquid slugging during heating operation.
Crankcase heater function
An electrical resistance heater wrapped around the compressor sump that keeps oil warm and drives off migrated refrigerant while the compressor is off, preventing startup slugging.
Zeotropic blend glide
The temperature difference between bubble and dew points of a refrigerant blend during phase change; affects charging accuracy and evaporator performance.
Evacuation target
A vacuum of 500 microns or lower held for 10 minutes with the pump isolated; a rising reading indicates moisture or a leak in the system.
Nitrogen purge brazing
Flowing dry nitrogen through the piping while brazing to displace oxygen and prevent internal oxidation scale that can later clog metering devices.
Line set sizing rule
Suction and liquid line diameters must follow manufacturer tables; undersized lines raise pressure drop, oversized lines reduce velocity and oil return.
Condensate in heating
In heating mode the outdoor coil runs below ambient and produces condensate; the drain path must slope away and not refreeze under the unit.
Commissioning baseline data
Recorded static pressure, delta-T, superheat, subcooling, and amp draw at startup; these values become the reference for future diagnostics.
Defrost initiation logic
Demand defrost starts when the coil temperature sensor and accumulated compressor run time both reach set thresholds, signaling frost buildup on the outdoor coil.
Defrost cycle sequence
The reversing valve shifts to cooling, the outdoor fan stops, and auxiliary heat energizes indoors; termination occurs when the coil temperature rises above the set point.
Anti-short-cycle delay
A time-delay relay or control board lockout, typically five minutes, that prevents the compressor from restarting too quickly after shutdown.
Low-voltage fuse location
A 3 A or 5 A fuse on the control board protects the 24 V circuit; a blown fuse usually indicates a shorted thermostat wire or contactor coil.
High-pressure switch role
A safety control that opens on excessive discharge pressure; tripping indicates airflow restriction, overcharge, or noncondensables, not a defective switch.
Superheat formula
Superheat equals suction line temperature minus the saturation temperature at suction pressure; high superheat with low suction pressure indicates undercharge or restriction.
Subcooling formula
Subcooling equals the saturation temperature at liquid pressure minus the liquid line temperature; low subcooling with bubbles suggests undercharge.
Cooling delta-T range
The temperature drop across the indoor coil in cooling is typically 16 to 22 F; a low value with normal airflow points to low charge or a dirty coil.
Heating delta-T range
The temperature rise across the indoor coil in heating is typically 25 to 40 F; compare measured value to the manufacturer chart for the outdoor temperature.
Restricted drier symptom
A temperature drop across the liquid line filter drier plus low subcooling downstream indicates a restriction; the drier should be replaced.
Airflow before charging
Always correct airflow before charging; low airflow depresses suction pressure and raises superheat, mimicking an undercharged system.
TXV charging method
Thermostatic expansion valve systems are charged by subcooling in cooling mode; target subcooling is typically 8 to 12 F at design conditions.
Fixed-orifice charging method
Piston systems are charged by superheat, adjusted for indoor wet-bulb and outdoor dry-bulb temperatures using the manufacturer charging chart.
Weigh-in charging
The most accurate charging method when line set length and indoor coil volume are known; add refrigerant per the manufacturer chart for line length.
Total external static pressure
Measured across the blower; residential target is typically 0.5 in. w.c. or less; higher readings indicate duct restriction or dirty filter.
400 CFM per ton rule
A common residential airflow target of 400 cubic feet per minute per ton of cooling capacity; heating airflow may be set higher per manufacturer.
Sensible capacity estimate
Sensible Btu/h is estimated by multiplying delta-T by 1.08 times the airflow in CFM; useful for verifying delivered capacity.
AHRI certificate check
The AHRI certificate lists rated SEER2 and HSPF2 for the matched system; compare installed performance to these values during efficiency verification.
Outdoor unit clearance
Manufacturer-specified distance from walls and obstructions that prevents air recirculation; insufficient clearance reduces capacity and raises head pressure.
Defrost sensor failure
A faulty coil temperature sensor prevents defrost termination or initiation; symptoms include heavy frost buildup or repeated short defrost cycles.
Noncondensable symptom
Air or moisture in the system raises head pressure and subcooling while suction pressure stays normal; indicates poor evacuation during installation.