The 'Just Change the Refrigerant' Request on an R-410A Rooftop

NATE Low-GWP · Put your knowledge to work in context.

All case studies

The 'Just Change the Refrigerant' Request on an R-410A Rooftop

A 5-ton R-410A packaged rooftop unit, 11 years old and with a nameplate charge of 11 lb, serves a 2,000 ft² office. The customer read that R-410A is being phased down and asks you to 'swap in R-454B - it has to be cheaper than a new unit.' The unit has a reciprocating compressor, POE oil, and a TXV; the condenser coil is clean. The evaporator has a documented leak that was topped off twice this summer. The office has a drop ceiling, no refrigerant detection, and the unit sits in a 9 ft × 12 ft × 10 ft closet with a louvered door. The customer has not had a permit pulled and wants the work done over a weekend.

1. Explain why this is not a drop-in conversion. Give at least four technical reasons and one regulatory or listing reason.

Read the worked answer

Technical reasons: (1) Capacity and mass flow - R-454B has different volumetric capacity and about 1.5 K of glide, so the existing compressor, TXV, and distributor will not deliver rated capacity at the same superheat and subcooling. (2) Safety listing - the unit was listed for an A1 refrigerant; an A2L charge requires A2L evaluation, nameplate, markings, and in many spaces a listed detection or mitigation system that this unit does not have. (3) Materials - lubricant, elastomer seal, and motor insulation compatibility with the new blend is not established for this compressor; both use POE, but that alone is not sufficient. (4) Serviceability - without written OEM approval there is no charging chart, no warranty, and no defined leak or repair procedure.

Regulatory/listing reason: R-410A's GWP of about 2,088 exceeds the 700 limit for new residential and light-commercial equipment under the AIM Act Technology Transitions rule, but that rule covers new equipment, not field conversions. The unit's UL listing remains R-410A only, and a field conversion would void it.

2. If the customer instead replaces the condensing section with an A2L unit of the same nominal capacity, what else must be evaluated?

Read the worked answer

Evaluate: the evaporator coil and TXV match - the existing evaporator already leaks, so plan on a matched coil; line-set sizes and equivalent length; whether the new charge plus line-set adjustment fits the closet volume and the A2L charge-limit table, which in a 1,080 ft³ closet will probably require a listed detection or mitigation system; the control board's sensor input, alarm, and shutdown logic; electrical supply and disconnect; condensate; curb and weight; and A2L nameplates and markings.

Also confirm the new equipment meets the applicable GWP limit and is listed for the application, pull the permit, and get the inspection. If the evaporator and line set are reused, document that the OEM approved them for use with the new refrigerant. Do not energize until the detection, markings, and permit items are closed out.

3. How do you handle the leaking evaporator and the existing R-410A charge?

Read the worked answer

The evaporator leak is the real decision. Two top-offs in one summer means the leak must be found and repaired or the coil replaced. Topping off again repeats the problem, and on a blend it can shift the charge composition. Recover the existing R-410A with a Section 608-certified recovery machine into a labeled cylinder, weigh it, and either reclaim it or send it to a reclaimer; never vent.

If the customer repairs, pressure-test with dry nitrogen, evacuate, and recharge by weight with reclaimed or virgin R-410A. If the customer replaces, recover the charge first and dispose of it properly. Explain the economics: an 11-year-old R-410A unit with a leaking coil is a replacement candidate, and a new A2L unit adds detection and marking requirements. Check the current federal leak-repair thresholds for this charge size and document the customer's decision in writing.