NATE Low-GWP flashcards
NATE Low-GWP · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- GWP definition
- Global Warming Potential: the 100-year integrated radiative forcing of 1 kg of a substance relative to 1 kg of CO2, whose GWP is defined as 1. Always cite the IPCC assessment report used.
- ODP versus GWP
- ODP measures ozone-depletion potential relative to CFC-11; GWP measures climate forcing relative to CO2. HFCs have zero ODP but high GWP; HFOs have near-zero GWP and zero ODP.
- R-410A GWP
- R-410A, a 50/50 blend of R-32 and R-125, has a 100-year GWP of about 2088 (AR4). It is an A1 refrigerant being replaced by lower-GWP A2L options.
- R-32 GWP
- R-32 (difluoromethane) is a single-component HFC with a 100-year GWP of about 675 (AR4). It is classified A2L and has higher volumetric capacity than R-410A.
- R-454B composition
- A zeotropic blend of 68.9% R-32 and 31.1% R-1234yf with GWP near 466 (AR4). It is A2L and used as an R-410A replacement; charge as liquid.
- R-1234yf properties
- An HFO with GWP below 1 (about 4 by AR5), classified A2L, with volumetric capacity close to R-134a. Used in automotive and small commercial systems; mildly flammable.
- R-1234ze(E) properties
- An HFO with GWP below 1, classified A2L, with lower volumetric capacity than R-134a. Common in chillers and foam blowing; often used with larger displacement compressors.
- A2L classification meaning
- ASHRAE 34 designation for lower toxicity and lower flammability. Burning velocity is low (about 5-10 cm/s), ignition energy is high, and flammable concentrations are narrow, so charge limits and ventilation apply.
- A3 classification meaning
- ASHRAE 34 designation for lower toxicity and higher flammability, such as R-290 and R-600a. Burning velocity and flame speed are much higher than A2L, so strict charge limits and ignition-source controls apply.
- R-290 GWP and class
- Propane: GWP 3, ODP 0, ASHRAE A3. It has excellent thermodynamic efficiency and high latent heat but is highly flammable, so many codes cap system charge.
- R-717 GWP and class
- Ammonia: GWP 0, ODP 0, ASHRAE B2L. It is toxic and slightly flammable, has high efficiency, is incompatible with copper, and requires ventilation and leak detection.
- R-744 critical point
- CO2 has a critical temperature of 31 C (87.8 F) and critical pressure of 73.8 bar (1070 psia). Above that temperature a system runs transcritical and efficiency depends on gas-cooler approach.
- R-744 triple point
- CO2 triple point is -56.6 C at 5.18 bar. Below this pressure solid dry ice can form, so systems must not be vented or pumped down below the triple point.
- Zeotropic blend definition
- A mixture whose components boil at different temperatures at a given pressure, producing temperature glide. Charge as liquid and account for glide in superheat and subcooling measurement.
- Temperature glide
- The difference between bubble and dew temperatures of a zeotropic blend at constant pressure. R-454B glide is about 1.5 K; R-410A about 0.1 K, effectively near-azeotropic.
- Kigali Amendment purpose
- An amendment to the Montreal Protocol that schedules phase-down of HFC production and consumption worldwide, using CO2-equivalent baselines and stepped reduction targets by country group.
- AIM Act
- The US American Innovation and Manufacturing Act of 2020 authorizes EPA to phase down HFCs, manage allowances, and set use restrictions and leak-management rules for high-GWP refrigerants.
- EPA SNAP program
- Significant New Alternatives Policy: EPA lists acceptable refrigerant substitutes by end use, with use conditions such as charge limits, A2L requirements, and required leak detection.
- CO2 equivalent calculation
- Charge mass in kg multiplied by GWP gives CO2-equivalent mass in kg. Example: 10 kg of R-410A at GWP 2088 equals 20,880 kg CO2e, or about 20.9 metric tons.
- A2L charge limit basis
- Safety standards such as ASHRAE 15 and IEC 60335-2-40 set maximum A2L charge from room volume, lower flammability limit, and installation height; larger charges require mitigation.
- Lower flammability limit
- The minimum refrigerant concentration in air that will sustain a flame. For A2L refrigerants it is typically above 100,000 ppm, much higher than for A3 refrigerants such as propane.
- Minimum ignition energy
- The smallest spark energy that can ignite a flammable mixture. A2L refrigerants require far more energy (millijoules) than A3 refrigerants, which is central to their lower risk profile.
- Burning velocity comparison
- A2L refrigerants burn at roughly 5-10 cm/s versus about 40 cm/s for propane. Lower burning velocity reduces overpressure risk and underpins the relaxed A2L requirements.
- R-452B composition
- A blend of R-32, R-125, and R-1234yf (67/7/26) with GWP near 676. It is A2L and a near-drop-in R-410A replacement with similar capacity.
- Transcritical CO2 cycle
- A cycle where heat rejection occurs above the CO2 critical temperature, so the condenser becomes a gas cooler and pressure is controlled for best efficiency rather than fixed by saturation.
- TFA from HFO breakdown
- HFO refrigerants degrade in the atmosphere to trifluoroacetic acid, which deposits in rain and water bodies. This is a separate environmental concern from GWP.
- Flammability of A2L
- A2L refrigerants will burn only when concentration is within the flammable range and a sufficiently energetic ignition source is present; leaks in occupied spaces must be diluted below the LFL.
- R-134a replacement options
- R-1234yf is the common low-GWP replacement for R-134a in automotive and small systems, with similar capacity and pressure but A2L classification requiring updated service practice.
- R-404A GWP
- A blend of R-125, R-143a, and R-134a with GWP about 3922 (AR4). It is a high-GWP A1 refrigerant targeted for phase-out in commercial refrigeration.
- Cascade system
- Two refrigeration circuits with separate refrigerants coupled by a heat exchanger. Common with CO2: a high-stage HFC or HFO circuit condenses the low-stage CO2, avoiding transcritical operation.
- Refrigerant recovery requirement
- Refrigerant must be recovered rather than vented during service, especially HFCs and HFOs. Recovery reduces CO2-equivalent emissions and is required by EPA Section 608 rules.
- Section 608 leak rules
- EPA rules set leak-rate thresholds and repair timelines by appliance type and refrigerant GWP. Higher-GWP and larger-charge systems face lower thresholds and stricter reporting.