NATE Low-GWP study materials
NATE Low-GWP study resources

NATE Low-GWP key terms

NATE Low-GWP · Get comfortable with the vocabulary.

Global Warming Potential (GWP)

A number that compares how much heat a gas traps in the atmosphere over a set period, usually 100 years, to the same mass of carbon dioxide, which is assigned a value of 1.

Related: Carbon Dioxide Equivalent (CO2e), Ozone Depletion Potential (ODP), A2L Refrigerant
Carbon Dioxide Equivalent (CO2e)

A common unit for expressing total climate impact, calculated by multiplying the mass of a refrigerant released by its GWP so different gases can be compared on one scale.

Related: Global Warming Potential (GWP), Refrigerant Charge, Total Equivalent Warming Impact (TEWI)
Ozone Depletion Potential (ODP)

A relative score for how strongly a substance destroys stratospheric ozone compared with CFC-11, which is set at 1.0. HFCs and HFOs have zero ODP.

Related: Global Warming Potential (GWP), Hydrofluoroolefin (HFO), Montreal Protocol
Hydrofluorocarbon (HFC)

A refrigerant family containing only hydrogen, fluorine, and carbon. HFCs do not deplete ozone but many carry high GWP values, which is why they are being phased down.

Related: AIM Act, Kigali Amendment, Hydrofluoroolefin (HFO)
Hydrofluoroolefin (HFO)

A refrigerant family with a carbon-carbon double bond that makes the molecule break down quickly in the atmosphere, giving very low GWP and zero ODP. Often mildly flammable.

Related: A2L Refrigerant, Global Warming Potential (GWP), R-1234yf
A2L Refrigerant

A safety classification for refrigerants that are mildly flammable, burn slowly, and need a higher concentration and energy to ignite than A3 refrigerants. Common low-GWP HFOs and blends carry this rating.

Related: Lower Flammability Limit (LFL), A3 Refrigerant, ASRAE 34 Classification
A3 Refrigerant

A safety classification for highly flammable refrigerants such as propane and isobutane. They ignite easily and require stricter charge limits and ignition-source controls than A2L products.

Related: A2L Refrigerant, Lower Flammability Limit (LFL), Refrigerant Charge Limit
ASHRAE 34 Classification

The standard safety grouping that assigns refrigerants a letter for toxicity (A or B) and a number for flammability (1, 2L, 2, or 3), such as A1, A2L, or B2.

Related: A2L Refrigerant, A3 Refrigerant, Lower Flammability Limit (LFL)
Lower Flammability Limit (LFL)

The minimum concentration of refrigerant vapor in air, expressed as a percentage by volume or in kilograms per cubic meter, that will support combustion at standard test conditions.

Related: A2L Refrigerant, Upper Flammability Limit (UFL), Ignition Source Control
Upper Flammability Limit (UFL)

The highest concentration of refrigerant vapor in air that will still burn. Above this level the mixture is too rich to ignite, which matters when evaluating leaks in small enclosed spaces.

Related: Lower Flammability Limit (LFL), A2L Refrigerant
Minimum Ignition Energy (MIE)

The smallest spark energy, measured in millijoules, needed to ignite a flammable refrigerant-air mixture. A2L refrigerants generally need far more energy than A3 products.

Related: A2L Refrigerant, Ignition Source Control, Lower Flammability Limit (LFL)
Ignition Source Control

Design and service practices that remove sparks, hot surfaces, open flames, and energized switching devices from areas where flammable refrigerant could collect, reducing the chance of ignition during a leak.

Related: Minimum Ignition Energy (MIE), A2L Refrigerant, Mitigation
R-32

A single-component HFC refrigerant with a GWP of about 675, roughly one-third that of R-410A. It is classified A2L and is widely used in small split systems.

Related: R-410A, A2L Refrigerant, Global Warming Potential (GWP)
R-454B

A zeotropic blend of R-32 and R-1234yf with a GWP near 466, designed as a lower-GWP replacement for R-410A in residential and light commercial equipment. Classified A2L.

Related: R-410A, Zeotropic Blend, Temperature Glide
R-1234yf

A low-GWP HFO refrigerant with a GWP of less than 1, used mainly in automotive and some commercial cooling. It is classified A2L and has zero ozone depletion potential.

Related: Hydrofluoroolefin (HFO), R-1234ze, A2L Refrigerant
R-1234ze

An HFO refrigerant with a GWP below 1, used in chillers and some commercial systems. It is classified A2L and is often chosen where a very low climate impact is required.

Related: Hydrofluoroolefin (HFO), R-1234yf, Chiller
R-410A

A near-azeotropic HFC blend of R-32 and R-125 with a GWP of about 2,088, long the standard for residential air conditioning and now the target of low-GWP replacements.

Related: R-32, R-454B, Global Warming Potential (GWP)
R-134a

A single-component HFC refrigerant with a GWP of about 1,430, once common in chillers, vehicles, and appliances. Its high GWP has driven replacement with lower-impact alternatives.

Related: R-1234yf, Global Warming Potential (GWP), Retrofit
Zeotropic Blend

A refrigerant mixture whose components boil at different temperatures, so its composition and properties shift as it evaporates or condenses. Charging must be done as a liquid.

Related: Temperature Glide, Fractionation, R-454B
Temperature Glide

The difference between the bubble point and dew point of a zeotropic blend at a given pressure. It affects superheat, subcooling, and coil performance calculations.

Related: Zeotropic Blend, Fractionation, Bubble Point
Fractionation

The tendency of a blend's components to separate when it leaks or is charged as a vapor, because the more volatile component leaves first. This can change the remaining mixture's composition and performance.

Related: Zeotropic Blend, Temperature Glide, Liquid Charging
Liquid Charging

Adding refrigerant to a system as a liquid rather than a vapor, required for zeotropic blends so the cylinder contents stay at the intended composition and glide is preserved.

Related: Fractionation, Zeotropic Blend, Charging
Bubble Point

The temperature at which the first bubble of vapor forms in a liquid refrigerant mixture at a given pressure. It is used as the saturated liquid reference for zeotropic blends.

Related: Dew Point, Temperature Glide, Zeotropic Blend
Dew Point

The temperature at which the first drop of liquid forms as a refrigerant vapor mixture is cooled at a given pressure. It is the saturated vapor reference for zeotropic blends.

Related: Bubble Point, Temperature Glide, Superheat
Superheat

The number of degrees a refrigerant vapor is above its saturation temperature. With blends, superheat is measured from the dew point rather than a single saturation value.

Related: Dew Point, Subcooling, Temperature Glide
Subcooling

The number of degrees a liquid refrigerant is below its saturation temperature. With blends, subcooling is measured from the bubble point, and it confirms a solid liquid seal at the metering device.

Related: Bubble Point, Superheat, Charging
AIM Act

The 2020 U.S. law that directs the EPA to phase down production and consumption of HFCs on a national schedule and to manage refrigerant recovery, reclaim, and leak reporting rules.

Related: Kigali Amendment, HFC Phase-Down, Section 608
Kigali Amendment

An amendment to the Montreal Protocol that sets a global schedule for cutting HFC production and consumption, with different phase-down steps for developed and developing countries.

Related: AIM Act, HFC Phase-Down, Montreal Protocol
HFC Phase-Down

A scheduled reduction in the amount of high-GWP HFCs produced and consumed, measured in CO2e against a baseline year, which pushes the market toward lower-GWP refrigerants and equipment.

Related: AIM Act, Kigali Amendment, Carbon Dioxide Equivalent (CO2e)
Montreal Protocol

The international treaty that first phased out ozone-depleting substances and now also governs the HFC phase-down through its Kigali Amendment.

Related: Kigali Amendment, Ozone Depletion Potential (ODP), HFC Phase-Down
Section 608

The part of the U.S. Clean Air Act rules covering refrigerant handling, leak repair, recovery, and technician certification for stationary refrigeration and air-conditioning equipment.

Related: AIM Act, Refrigerant Recovery, Leak Rate
EPA Section 608 Certification

The credential a technician must hold to buy or handle regulated refrigerants and to service stationary equipment, obtained by passing a proctored exam on refrigerant rules and safe practice.

Related: Section 608, Refrigerant Recovery, Technician Safety
Refrigerant Recovery

Removing refrigerant from a system into a container for reuse, recycling, or destruction instead of venting it to the atmosphere, as required by law and by good environmental practice.

Related: Reclaim, Recycling, Section 608
Reclaim

Reprocessing used refrigerant to meet new-product purity specifications, verified by chemical analysis, so it can be returned to service in any system, including those under warranty.

Related: Refrigerant Recovery, Recycling, A2L Refrigerant
Recycling

Cleaning recovered refrigerant by removing oil, moisture, and particulates, usually on site, without restoring it to new-product purity. Recycled refrigerant is typically reused in the same owner's equipment.

Related: Reclaim, Refrigerant Recovery
Total Equivalent Warming Impact (TEWI)

A measure that adds the direct global warming effect of refrigerant leaked over a system's life to the indirect effect of the energy used to run it.

Related: Carbon Dioxide Equivalent (CO2e), Global Warming Potential (GWP), Energy Efficiency
Life Cycle Climate Performance (LCCP)

A broader analysis than TEWI that also counts emissions from manufacturing, transporting, and disposing of the equipment and refrigerant, giving a fuller picture of climate impact.

Related: Total Equivalent Warming Impact (TEWI), Global Warming Potential (GWP), Energy Efficiency
Energy Efficiency

The ratio of cooling delivered to energy consumed. Lower-GWP refrigerants can change efficiency, so equipment design and charge size must be balanced against climate impact.

Related: Total Equivalent Warming Impact (TEWI), Life Cycle Climate Performance (LCCP)
Refrigerant Charge Limit

The maximum mass of flammable refrigerant allowed in a space or system, set by safety standards based on room volume, LFL, and whether mitigation is provided.

Related: A2L Refrigerant, Lower Flammability Limit (LFL), Mitigation
Mitigation

Engineering or procedural measures, such as ventilation, refrigerant detection, or shutoff valves, that reduce the risk or concentration of a flammable refrigerant leak in an occupied space.

Related: Refrigerant Charge Limit, Ignition Source Control, A2L Refrigerant
Refrigerant Detection System

Sensors and controls that sense a flammable refrigerant leak, then alarm, ventilate, or shut off equipment to keep concentrations below hazardous levels in occupied or enclosed spaces.

Related: Mitigation, Ignition Source Control, A2L Refrigerant