Quick reference

Lighting Practice: Metrics, Sources, and Design Rules

  • Illuminance E (lux) = luminous flux incident per unit area; E = Φ/A for uniform flux on a surface, and E = I/d² for a point source at perpendicular distance d (inverse-square law).

  • Luminance L (cd/m²) = luminous intensity per projected area; L = I/(A·cosθ). Luminance, not illuminance, drives perceived brightness and glare sensation.

  • Illuminance falls off with the cosine of the incidence angle: E = I·cosθ/d². Doubling distance to a point source reduces illuminance to one quarter.

  • Luminous efficacy (lm/W) ranks sources: LED retrofit lamps commonly 100–150 lm/W, linear fluorescent roughly 90–100 lm/W, halogen near 20 lm/W, incandescent near 15 lm/W. Efficacy excludes ballast/driver losses unless system efficacy is stated.

  • Correlated color temperature (CCT) describes tint (warm <3300 K, neutral 3300–5300 K, cool >5300 K); CRI (Ra) describes color fidelity with 100 as reference. CCT and CRI are independent attributes.

  • IES illuminance recommendations are task-based maintained values: offices ~300–500 lx on the task, circulation ~100 lx, and precision inspection far higher. Design to maintained illuminance, then add maintenance factor.

  • Maintenance factor (MF) = LLMF × LSF × LMF × RSMF (lamp lumen, luminaire/surface, lamp survival, room surface maintenance). Design illuminance = initial illuminance × MF, so MF below 1 forces more initial light.

  • Uniformity criteria: max/min illuminance ratio and min/average ratio (often ≥0.7 for task areas). Spacing-to-mounting-height ratio (S/MH) controls overlap; exceeding the luminaire's rated S/MH produces scalloping and dark bands.

  • Glare control: UGR limits (e.g., ≤19 for offices, ≤16 for drafting) and VCP/glare rating apply; disability glare reduces visibility, discomfort glare causes annoyance. Shield bright sources with cut-off angles.

Quick reference

Lighting Practice: Controls, Codes, and Verification

  • Power density check: LPD (W/m² or W/ft²) = total connected lighting power ÷ floor area. Compare to the code allowance for the space type; controls and reduced wattage lower LPD.

  • LENI (kWh/m²/yr) = total lighting energy ÷ area; it captures controls and hours, unlike LPD which captures only connected load.

  • Automatic shutoff is generally required in most commercial spaces; occupancy/vacancy sensors suit intermittently used rooms, and time-switch plus override suits scheduled spaces.

  • Daylight-responsive controls: photosensor dimming or stepped switching in daylit zones; calibrate setpoints to avoid hunting and false switching.

  • Demand response and dimming: 0–10 V, DALI, and phase-cut are common interfaces; verify compatibility and minimum load per dimmer.

  • Emergency egress illumination is typically ~10.8 lx (1 fc) minimum at floor along the path of egress for 90 minutes; exit signs must be illuminated and visible.

  • Commissioning verifies illuminance, controls sequences, and sensor calibration against design values; record measured footcandles/lux and control settings for the owner.

  • Color shift and lumen depreciation: LED luminaires are rated by L70 (hours to 70% lumen output) and sometimes L90; match rated life to maintenance cycles.

  • Harmonic and power quality: LED drivers and electronic ballasts can inject harmonics; total harmonic distortion limits and power factor (≥0.9 typical) affect compliance.

Quick reference

Lighting Practice: Calculations and Field Work

  • Zonal cavity method: CU (coefficient of utilization) depends on room cavity ratio, surface reflectances, and luminaire photometrics. RCR = 5·h·(L+W)/(L·W) with h as cavity height.

  • Lumen method: N = (E × A)/(Φ_lamp × CU × MF), where N is number of luminaires, E target maintained illuminance, A area, Φ per-lamp lumens. Round up and recheck uniformity.

  • Room index (metric) K = (L×W)/(h_m×(L+W)); higher K means more interreflection and generally higher utilization.

  • Point-by-point calculation is required for non-uniform layouts, high-bay spaces, and facades; average methods understate peaks and valleys.

  • Field measurement: use a calibrated illuminance meter, cosine-corrected and color-corrected; take readings on the work plane grid, avoid shadowing the sensor, and record date, lamp hours, and voltage.

  • Lamp/fixture inventory audits record type, wattage including ballast factor, quantity, and control type; ballast factor multiplies lamp lumens and wattage for fluorescent systems.

  • Retrofit economics: simple payback (years) = installed cost ÷ annual savings; annual savings = (old W − new W) × hours × quantity × energy rate ÷ 1000.

  • Color consistency in the field: specify a tight CCT tolerance (e.g., within 3–5 SDCM) and verify against a sample to avoid visible batch mismatch.

Quick reference

Lighting Practice: Standards, Safety, and Documentation

  • Follow the locally adopted energy code (e.g., ASHRAE 90.1 or IECC) for LPD allowances, mandatory controls, and lighting alterations; verify the edition in force for the jurisdiction.

  • Lighting power allowances are space-by-space or building-area methods; trade-offs are limited, and decorative or display lighting often has separate allowances.

  • IES recommended practices give target maintained illuminance and uniformity per task; they are design guidance, while codes are enforceable minimums.

  • Safety: lockout/tagout before servicing; capacitors in HID ballasts retain charge; LED drivers and lamps may remain hot. Verify circuit de-energized with a tester.

  • Ladder and lift safety: maintain three points of contact, inspect harnesses, and do not exceed ladder duty rating; never work alone on energized equipment.

  • Photometric files (IES/LDT) contain intensity distributions, lumens, and spacing criteria; verify the file matches the exact luminaire and optics before calculating.

  • Deliverables: lighting layout, luminaire schedule with photometrics and wattages, control narrative and sequence of operations, and calculation summary with maintenance factor stated.

  • Warranty and rated life: confirm lumen maintenance, color maintenance, and driver warranty terms; note that L70 is a statistical rating, not a guaranteed failure time.

  • Recycling and disposal: fluorescent lamps contain mercury and require regulated disposal; HID lamps and ballasts may also require special handling under local rules.

Quick reference

Lighting Practice: Applications and Quality of Light

  • Vertical illuminance and cylindrical illuminance govern face recognition and wall brightness; horizontal illuminance alone can leave a space feeling dim.

  • Modeling and shadow: a key-to-fill ratio around 2:1 to 4:1 produces pleasing three-dimensional rendering; pure downlighting flattens faces.

  • Flicker: percent flicker and flicker index quantify modulation; high modulation at low frequencies can cause headaches and stroboscopic effects, especially with rotating machinery.

  • Glare from windows and luminaires: evaluate with DGP or DGI for daylight; position luminaires outside the 45° cone of sight where feasible.

  • Task-ambient design lowers energy by raising ambient levels modestly and adding local task light where needed; avoid excessive contrast between task and surround (keep surround within roughly 1:3 of task luminance).

  • Color rendering matters most where color judgments occur (retail, healthcare, printing); specify R9 (red) values for skin tones and food.

  • Outdoor and site lighting: control light trespass and skyglow with full cut-off optics, backlight/uplight ratings, and curfew dimming; BUG ratings summarize these.

  • Emergency and egress design: verify path of egress illumination, exit sign visibility, and that battery units are tested and logged per the code cycle.

  • Controls zoning should follow daylight availability, occupancy patterns, and task needs; separate perimeter daylit zones from core zones to capture savings.

Quick reference

Lighting Practice: Exam-Style Decision Rules

  • If asked for energy compliance, compute LPD and compare to the adopted code allowance; if asked for energy use, compute LENI or annual kWh including hours and controls.

  • If the question mentions point source, distance, and intensity, apply inverse-square and cosine correction; if it mentions area and flux, use E = Φ/A.

  • If uniformity is failing, reduce spacing-to-mounting-height ratio, raise mounting height, or add perimeter luminaires before increasing wattage.

  • If a space looks bright but objects are hard to see, suspect veiling reflections or glare, not insufficient illuminance; reposition or shield sources.

  • If color mismatch is reported after a retrofit, check CCT binning and SDCM tolerance, not just CRI.

  • If maintenance is deferred, the maintained illuminance drops; either raise initial design level or specify longer-life, lower-depreciation sources.

  • If controls fail to save energy, verify sensor sensitivity, time delays, and daylight setpoints with a meter before replacing hardware.

  • If a calculation seems too good, check ballast factor, luminaire dirt depreciation, and whether the photometric file matches the installed optic.