Design density
The minimum water flow rate in gallons per minute per square foot applied over the design area; selected from the occupancy hazard curve and used as the starting point for hydraulic calculations.
Remote area
The hydraulically most demanding area of sprinkler operation, typically 1,500 to 2,500 square feet depending on hazard, used as the assumed simultaneous operating area for calculations.
K-factor
A dimensionless discharge coefficient relating sprinkler flow to pressure by Q = K times the square root of P; larger K means more flow at the same pressure.
Wet pipe system
A system in which automatic sprinklers are connected to piping containing water under pressure at all times, so a fused head discharges water immediately.
Dry pipe system
Piping contains pressurized air or nitrogen; a dry pipe valve holds water back until a sprinkler fuses and air escapes, allowing water to enter and reach the heads.
Preaction system
A dry-pipe arrangement in which a supplemental detection system must operate before water fills the piping; single-interlock admits water on detection, double-interlock requires detection plus a fused head.
Deluge system
A system using open sprinklers or nozzles connected to piping that is dry until a deluge valve opens, then discharges water from all heads over the protection area at once.
Hose stream allowance
The water flow, in gallons per minute, reserved in the hydraulic calculation for fire department hose lines, added to sprinkler demand and varying with hazard classification.
Light hazard
An occupancy classification for low-combustibility contents and low heat release, such as offices, churches, and schools, permitting wider sprinkler spacing and lower design density.
Ordinary Hazard Group 2
An occupancy with moderate quantities of combustibles producing moderate heat release, such as machine shops and mercantile areas; requires higher density and closer spacing than Group 1.
Extra Hazard Group 1
An occupancy where combustibles are present in high quantity or with dust, lint, or flammable liquids producing rapid heat release; requires high density and large hose allowance.
Standard spray sprinkler
A sprinkler with a defined discharge pattern and spacing rule, installed upright or pendent, with a minimum operating pressure of 7 psi under the applicable standard.
Control mode density area
The traditional design method in which a specified density is applied over a specified remote area, assuming a limited number of sprinklers operate simultaneously.
Design area increase for dry systems
Dry pipe and double-interlock preaction systems require the remote area to be increased, commonly by 30 percent, because water travel time delays control of the fire.
Sprinkler coverage area
The floor area protected by one sprinkler, determined by the spacing between branch lines and between heads on a line; maximum area decreases as hazard increases.
Deflector distance
The required clearance between the sprinkler deflector and the ceiling, typically 1 to 12 inches for standard spray heads, ensuring the spray pattern develops properly.
Riser and base of riser
The vertical supply pipe feeding the system; hydraulic calculations must show required flow and pressure at the base of the riser, including hose stream allowance.
Fire pump
A pump installed to boost water supply pressure and flow to meet sprinkler demand; its rated point must satisfy the system demand curve, and churn pressure affects static loading.
Backflow preventer
A device preventing reverse flow from the sprinkler system into the potable water supply, often required by the authority having jurisdiction and adding friction loss to calculations.
Waterflow switch
A device that senses water movement in the sprinkler piping and initiates an alarm signal, typically required on each riser and on the alarm line of a wet system.
Dry pipe valve
A valve with a clapper held closed by air pressure on the system side; when air escapes through a fused sprinkler, the clapper opens and admits water.
Accelerator
A device attached to a dry pipe system that speeds the release of air pressure, allowing the dry pipe valve to open faster and reducing water delivery time to the heads.
Inspection test and maintenance
Periodic activities required by NFPA 25, including weekly or monthly gauge checks, annual main drain tests, and trip tests of dry valves, distinct from installation design rules.
Main drain test
A test conducted by opening the main drain on the riser and recording static and residual pressures to verify that the water supply and control valves are unobstructed.
Design area adjustment for high-temperature sprinklers
Where sprinklers with a high temperature rating are installed, the remote area may be reduced, reflecting the slower activation and fewer heads expected to operate at once.
Minimum sprinkler pressure
Seven psi is the lowest pressure at which a standard spray sprinkler may be designed to operate, regardless of calculated results, under the applicable installation standard.
Pipe schedule design
A prescriptive method assigning pipe sizes by the number of sprinklers served; permitted only for light and ordinary hazard occupancies within specified size and length limits.
Branch line
The pipe on which sprinklers are spaced; its size and the number of heads it carries are limited by hydraulic calculation or by the pipe schedule tables.
Cross main
The main pipe supplying branch lines on a single level; friction loss through the cross main must be included in the hydraulic calculation to the riser.
Hazard classification
The categorization of an occupancy by expected fire severity, which determines design density, remote area, sprinkler spacing, and hose stream allowance in the design.
Flow test
A test of the water supply, such as from a hydrant, measuring static and residual pressure and flow to establish the available supply curve for the hydraulic calculation.
Hydraulic junction method
The calculation technique of summing flows and computing friction loss from the remote area back to the supply, accounting for elevation and fitting losses along each path.