NE Fire Sprinkler key terms
NE Fire Sprinkler · Get comfortable with the vocabulary.
- Automatic Sprinkler
- Related: Sprinkler Temperature Rating, Design Density
A heat-actuated device that discharges water over a designed area when its temperature-sensitive element operates, and that opens individually so only sprinklers near the fire flow water.
- Design Density
- Related: Design Area, Hazard Classification
The minimum water flow rate, in gallons per minute per square foot, that must be delivered over the design area for the hazard classification being protected.
- Design Area
- Related: Design Density, Remote Area
The assumed worst-case floor area, measured horizontally, over which sprinkler discharge is calculated; it is not the same as the total floor area of the building.
- Remote Area
- Related: Design Area, Hydraulic Calculation
The hydraulically most demanding area of sprinkler operation, where pressure losses from friction and elevation are greatest relative to available supply.
- Hydraulic Calculation
- Related: Remote Area, Safety Margin
A pressure-and-flow analysis proving the water supply can deliver the required density to the most demanding sprinklers while leaving adequate residual pressure at the base of the riser.
- Safety Margin
- Related: Hydraulic Calculation, Water Supply Curve
The extra pressure or flow reserved above the calculated system demand so that the supply still satisfies the design when pipes age, valves open, or conditions change.
- Water Supply Curve
- Related: Flow Test, Safety Margin
A graph of available pressure versus flow at a point in the water system, derived from a flow test and used to judge whether the supply meets the sprinkler demand.
- Flow Test
- Related: Water Supply Curve, Residual Pressure
A field measurement of static and residual pressure at two known flow rates, used to construct the water supply curve for hydraulic design.
- Residual Pressure
- Related: Flow Test, Static Pressure
The pressure remaining at a gauge while water is flowing, as opposed to static pressure measured with no flow; it reflects friction losses in the supply main.
- Static Pressure
- Related: Residual Pressure
The pressure measured at a point when no water is moving, representing only elevation head and the pressure maintained in the supply main.
- Hazard Classification
- Related: Design Density, Ordinary Hazard Occupancy
The categorization of occupancy contents and combustibility, such as light, ordinary, or extra hazard, that determines design density, spacing, and other sprinkler rules.
- Ordinary Hazard Occupancy
- Related: Hazard Classification, Design Density
An occupancy where combustibility is low to moderate and stockpiles do not exceed about twelve feet in height, requiring moderate design densities and protection.
- Sprinkler Temperature Rating
- Related: Automatic Sprinkler, Thermal Element
The nominal temperature at which a sprinkler's heat-responsive element is designed to operate, selected to be above expected ceiling temperatures but low enough for prompt action.
- Thermal Element
- Related: Sprinkler Temperature Rating, Automatic Sprinkler
The fusible link, glass bulb, or solder component that fails at its rated temperature to release the sprinkler's cap and allow water to discharge.
- K-Factor
- Related: Orifice, Hydraulic Calculation
A discharge coefficient relating sprinkler flow to pressure through the orifice, so that flow equals the K-factor times the square root of pressure.
- Orifice
- Related: K-Factor
The opening in a sprinkler through which water passes; its size, expressed through the K-factor, governs flow at a given pressure.
- Sprinkler Spacing
- Related: Coverage Area, Branch Line
The maximum permitted distance between sprinklers on a branch line and between branch lines, set by hazard and ceiling construction to ensure overlapping coverage.
- Coverage Area
- Related: Sprinkler Spacing, Design Density
The floor area protected by one sprinkler, calculated from spacing dimensions and limited by the maximum area allowed for the hazard classification.
- Branch Line
- Related: Cross Main, Sprinkler Spacing
The smaller pipe that carries sprinklers along a run and feeds into a cross main; its size and the number of heads it serves affect hydraulic performance.
- Cross Main
- Related: Branch Line, Riser
The larger pipe that supplies branch lines in a tree or gridded arrangement and connects back to the riser or feed main.
- Riser
- Related: Riser Assembly, Cross Main
The vertical supply pipe that carries water from the source or main up to the sprinkler piping, usually fitted with a control valve, check valve, and alarm connections.
- Riser Assembly
- Related: Riser, Alarm Valve
The complete vertical arrangement at the system supply point, including control valve, check valve, pressure gauge, drain, flow switch, and alarm test connections.
- Alarm Valve
- Related: Riser Assembly, Flow Switch
A valve that opens on water flow to the sprinklers and simultaneously transmits an alarm, often through a retard chamber or pressure switch.
- Flow Switch
- Related: Alarm Valve, Vane Type
A device that detects movement of water in the piping and sends an alarm or supervisory signal, commonly used on wet systems and dry pipe systems.
- Wet Pipe System
- Related: Dry Pipe System, Preaction System
A sprinkler system with water under pressure in the piping at all times, so that a sprinkler operates immediately on fusion of its thermal element.
- Dry Pipe System
- Related: Wet Pipe System, Dry Pipe Valve
A system holding air or nitrogen under pressure in the piping, with water admitted only after a sprinkler opens and the resulting pressure drop trips the dry pipe valve.
- Dry Pipe Valve
- Related: Dry Pipe System, Trip Time
A differential or latched valve that keeps water out of the dry piping until air pressure drops, then opens to admit water and trip the alarm.
- Preaction System
- Related: Deluge System, Wet Pipe System
A system where detection must operate before water fills the piping, providing an extra safeguard against accidental discharge in areas where water damage is costly.
- Deluge System
- Related: Preaction System, Deluge Valve
A system with open sprinklers or nozzles and a deluge valve that opens on detection, discharging water from all heads at once over the protected area.
- Deluge Valve
- Related: Deluge System, Preaction System
A valve held closed by pressure or a latch and released by the detection system, admitting water to open nozzles or sprinklers in a deluge or preaction arrangement.
- Accelerator
- Related: Dry Pipe System, Trip Time
A device that speeds the drop of air pressure in a dry system, shortening the time between sprinkler operation and water arrival at the fire.
- Trip Time
- Related: Dry Pipe System, Accelerator
The interval between a sprinkler opening in a dry system and water reaching that sprinkler, limited by code because fire growth continues during the delay.
- Fire Department Connection
- Related: Riser, Check Valve
An exterior pipe fitting where the fire department can pump water into the sprinkler or standpipe system to supplement the supply during a fire.
- Check Valve
- Related: Fire Department Connection, Riser Assembly
A one-way valve that permits flow in the intended direction only, preventing backflow and keeping water from draining out through the supply connection.
- Main Drain
- Related: Riser Assembly, Flow Test
A valve and pipe connection at the low point of the system used to drain the piping and to conduct the main drain flow test that verifies supply adequacy.
- Inspector's Test Valve
- Related: Flow Switch, Alarm Valve
A test connection at the end of the most remote branch line that simulates a single sprinkler opening to verify alarm and flow switch operation.
- Sprinkler Escutcheon
- Related: Automatic Sprinkler, Deflector
The decorative plate that covers the gap between a sprinkler and the ceiling or wall surface, which must not obstruct the spray pattern.
- Deflector
- Related: Sprinkler Escutcheon, Pendent Sprinkler
The metal plate or vane at the sprinkler outlet that shapes the water discharge into a designed spray pattern for the intended installation orientation.
- Pendent Sprinkler
- Related: Upright Sprinkler, Deflector
A sprinkler designed to hang below the pipe with its deflector facing down, producing an umbrella-shaped spray for protection beneath a ceiling.
- Upright Sprinkler
- Related: Pendent Sprinkler, Deflector
A sprinkler mounted above the pipe with its deflector facing up, used where the spray must be thrown upward or where piping is exposed.