NETA ETT Level 1 key terms
NETA ETT Level 1 · Get comfortable with the vocabulary.
- Arc flash boundary
- Related: Incident energy, Limited approach boundary, Shock hazard
The approach limit distance from exposed energized conductors at which a person could receive a second-degree burn from an arc flash. It is calculated from incident energy analysis or the arc flash PPE category tables.
- Incident energy
- Related: Arc flash boundary, Arc-rated PPE
The amount of thermal energy impressed on a surface at a given distance from an arc, usually expressed in calories per square centimeter or joules per square centimeter. It determines the required arc-rated PPE.
- Limited approach boundary
- Related: Restricted approach boundary, Arc flash boundary
A shock protection boundary that unqualified persons must not cross unless escorted by a qualified person. Only qualified persons may cross it, and only with appropriate shock protection measures.
- Restricted approach boundary
- Related: Limited approach boundary, Arc-rated PPE
A shock protection boundary that only qualified persons may cross, and only while wearing shock-protective equipment and using insulated tools. It lies closer to exposed energized parts than the limited approach boundary.
- Arc-rated PPE
- Related: Incident energy, Arc flash boundary
Clothing and equipment assigned an arc rating, such as calories per square centimeter, that indicates its resistance to thermal energy from an electric arc. Arc rating differs from flame resistance because it quantifies withstand energy.
- LOTO (lockout/tagout)
- Related: Absence-of-voltage verification, Shock hazard
A formal procedure for de-energizing, isolating, locking, and tagging equipment so it cannot be re-energized while work is performed. Each worker applies a personal lock, and the equipment is verified de-energized before work begins.
- Absence-of-voltage verification
- Related: LOTO (lockout/tagout), Voltage detector
The step of testing a circuit with a known-good voltage detector to confirm it is de-energized before grounding or touching conductors. The tester is proven on a known live source before and after the test.
- Shock hazard
- Related: Limited approach boundary, Absence-of-voltage verification
The risk of electric current passing through the body because of contact with energized parts or inadequate insulation. It is managed through isolation, grounding, distance, and shock-protective equipment rather than arc-rated clothing alone.
- Voltage detector
- Related: Absence-of-voltage verification, Proving unit
A device used to verify the presence or absence of voltage on a conductor. It must be rated for the system voltage, tested on a known source before and after use, and checked for function.
- True RMS meter
- Related: Crest factor, Current clamp
A multimeter that measures the root-mean-square value of a waveform by sampling and computing it, so it reads non-sinusoidal currents and voltages correctly. Average-responding meters can be significantly wrong on distorted waveforms.
- Crest factor
- Related: True RMS meter
The ratio of a waveform's peak value to its RMS value. A pure sine wave has a crest factor of about 1.414, and meters are rated to a maximum crest factor beyond which readings become inaccurate.
- Current clamp
- Related: True RMS meter, Hall effect clamp
An instrument that measures current by surrounding a conductor with a magnetic core and sensing the induced field. It measures current without breaking the circuit and must be rated for the system voltage and frequency.
- Hall effect clamp
- Related: Current clamp
A clamp meter that senses the magnetic field with a semiconductor sensor, allowing measurement of both AC and DC current, including DC current in a conductor without breaking the circuit.
- Proving unit
- Related: Voltage detector, Absence-of-voltage verification
A portable source of known voltage used to verify that a voltage detector or tester is functioning before and after an absence-of-voltage check. It substitutes for a known live source when none is available.
- Category rating (CAT III / CAT IV)
- Related: Voltage detector, True RMS meter
A safety classification for test instruments indicating the transient overvoltage environment in which they may be used. CAT III covers distribution-level circuits and CAT IV covers service entrances and utility connections.
- Insulation resistance (IR) test
- Related: Polarization index (PI), Dielectric absorption ratio (DAR), Guard terminal
A test that applies a DC voltage across insulation and measures the resulting resistance, indicating moisture, contamination, or deterioration. Results are read after a defined electrification time, typically one minute.
- Polarization index (PI)
- Related: Insulation resistance (IR) test, Dielectric absorption ratio (DAR)
The ratio of insulation resistance measured at ten minutes to the value measured at one minute, using the same test voltage. It indicates insulation condition independent of temperature and size, with values above 2.0 generally considered acceptable.
- Dielectric absorption ratio (DAR)
- Related: Polarization index (PI), Insulation resistance (IR) test
The ratio of insulation resistance at sixty seconds to the value at thirty seconds. It is a faster indicator of insulation condition than the polarization index and is useful when a ten-minute test is impractical.
- Guard terminal
- Related: Insulation resistance (IR) test, Surface leakage current
A terminal on an insulation tester that diverts leakage current across the insulation surface away from the measurement circuit. Using it removes surface contamination effects and gives a truer reading of internal insulation resistance.
- Surface leakage current
- Related: Guard terminal, Insulation resistance (IR) test
Current that flows along the outside surface of insulation because of moisture or contamination rather than through the insulation volume. It can falsely depress insulation resistance readings and is reduced by cleaning or guarding.
- Dielectric test (withstand test)
- Related: Insulation resistance (IR) test, Hipot test
An overvoltage test that stresses insulation above normal operating voltage for a defined time to confirm it can withstand the electrical field. It is a pass/fail proof test, not a diagnostic measurement like insulation resistance.
- Hipot test
- Related: Dielectric test (withstand test), Insulation resistance (IR) test
A high-potential test that applies an elevated AC or DC voltage to insulation to verify dielectric strength. It is a pass/fail proof test that can damage deteriorated insulation, so it follows insulation resistance testing.
- Contact resistance test (micro-ohmmeter)
- Related: Ductor test, Trip unit
A test that injects a DC current through closed breaker contacts and measures the voltage drop to calculate resistance in micro-ohms. It reveals pitted contacts, loose connections, and poor contact pressure.
- Ductor test
- Related: Contact resistance test (micro-ohmmeter)
A common name for a low-resistance measurement of breaker contacts or busbar joints using a micro-ohmmeter, typically injecting 100 A or more DC. Results are compared with previous baseline values rather than a single absolute limit.
- Trip unit
- Related: Time-current curve (TCC), Primary injection test
The component of a low-voltage circuit breaker that senses current and initiates tripping, providing long-time, short-time, instantaneous, and ground-fault protection functions. Its settings must match the coordination study.
- Primary injection test
- Related: Secondary injection test, Trip unit
A test in which current is injected through the breaker's main current path to verify the entire tripping system, including current sensors and trip unit. It confirms performance that secondary injection alone cannot.
- Secondary injection test
- Related: Primary injection test, Protective relay
A test that injects a simulated current or voltage signal into the relay or trip unit's secondary terminals to verify its logic and settings. It does not prove the current transformers or trip coil circuit.
- Time-current curve (TCC)
- Related: Trip unit, Coordination (selectivity)
A graph plotting trip time against current for a protective device, showing its long-time, short-time, and instantaneous regions. Curves of series devices are compared to confirm selective coordination.
- Coordination (selectivity)
- Related: Time-current curve (TCC), Protective relay
The arrangement of protective devices so that the device nearest a fault trips first, limiting the outage to the smallest affected section. It is verified by comparing time-current curves and pickup settings.
- Protective relay
- Related: Secondary injection test, Current transformer (CT)
A device that monitors current, voltage, or other quantities and initiates a trip when conditions exceed settings. It is tested by secondary injection to verify pickup, timing, and output contacts.
- Current transformer (CT)
- Related: Potential transformer (PT/VT), CT ratio and polarity test, Burden
An instrument transformer that steps primary current down to a standard secondary level, typically 5 A or 1 A, for metering and relaying. Its polarity and ratio must be verified before protective settings are applied.
- Potential transformer (PT/VT)
- Related: Current transformer (CT), Burden
An instrument transformer that steps high voltage down to a standard secondary value, typically 120 V, for metering and protection. Its ratio and burden must be correct for accurate measurement.
- CT ratio and polarity test
- Related: Current transformer (CT), Protective relay
A test that confirms the current transformer's turns ratio and the relative polarity of its secondary terminals. Correct polarity is essential so differential and directional relays see currents in the proper direction.
- Burden
- Related: Current transformer (CT), Potential transformer (PT/VT)
The total impedance connected to an instrument transformer's secondary, including wiring, relays, and meters. Excessive burden causes ratio and phase-angle errors and can saturate a current transformer.
- Turns ratio test
- Related: Winding resistance test, Excitation current test
A test that applies a known voltage to one winding of a transformer and measures the induced voltage on another to confirm the winding ratio. Results are compared with nameplate ratio to detect shorted turns.
- Winding resistance test
- Related: Turns ratio test, Temperature correction
A DC measurement of each winding's resistance, used to detect loose connections, broken strands, or shorted turns. Readings are corrected to a reference temperature and compared between phases and with prior results.
- Excitation current test
- Related: Turns ratio test, Winding resistance test
A test that applies AC voltage to one winding with the others open and measures the current drawn, revealing core condition and shorted turns. Results are compared phase-to-phase and with previous tests.
- Temperature correction
- Related: Winding resistance test, Insulation resistance (IR) test
The adjustment of measured resistance or insulation values to a standard reference temperature, commonly 20 degrees Celsius for insulation and 75 degrees Celsius for winding resistance, so results are comparable.
- Grounding electrode
- Related: Fall-of-potential test, Bonding
A conductive element, such as a rod, plate, or pipe, in direct contact with the earth that provides a path to ground. Its resistance is measured to confirm it meets the installation requirements.
- Bonding
- Related: Grounding electrode, Ground-fault protection
The intentional electrical connection of metallic parts to ensure they remain at the same potential, preventing dangerous voltage differences. It is distinct from grounding, which connects to earth.
- Fall-of-potential test
- Related: Grounding electrode, Clamp-on ground resistance test
A method of measuring grounding electrode resistance by driving reference stakes and measuring voltage drop as the current stake is moved. The resulting curve confirms the true resistance plateau.
- Clamp-on ground resistance test
- Related: Fall-of-potential test, Grounding electrode
A test that measures the resistance of a grounding conductor loop without disconnecting it, by inducing a voltage and sensing the resulting current. It requires a parallel ground path to be valid.
- Ground-fault protection
- Related: Bonding, Trip unit
A protective scheme that detects current flowing to ground outside the intended path and trips the circuit to limit damage and shock. It is tested by injecting a simulated ground-fault current.
- Insulation resistance profile (step voltage test)
- Related: Insulation resistance (IR) test, Hipot test
A test that applies insulation test voltage in steps and plots resistance against voltage to reveal insulation weaknesses that a single-voltage test might miss. A falling resistance trend indicates deterioration.
- Motor circuit test
- Related: Insulation resistance (IR) test, Winding resistance test
A set of tests on a motor branch circuit covering winding insulation resistance, winding resistance, and supply cable condition. Results help distinguish motor faults from cable or starter faults.
- Surge comparison test
- Related: Motor circuit test, Insulation resistance (IR) test
A test that applies identical voltage surges to each motor winding and compares the resulting waveforms to detect turn-to-turn or phase-to-phase insulation faults. It is used on motors and coils.
- Test record
- Related: Baseline (trending), Temperature correction
A documented set of measurements, conditions, and instrument details captured during a test. It must include ambient temperature, humidity, test voltage, and instrument identification so results can be reproduced and compared.
- Baseline (trending)
- Related: Test record, Temperature correction
The initial or previous set of test results against which later measurements are compared. Trending detects gradual deterioration that a single pass/fail limit might not reveal.
- Acceptance criteria
- Related: Test record, Baseline (trending)
The specified limits or conditions a test result must meet to be considered passing, taken from standards, manufacturer data, or engineering specifications. They must be cited in the test report.