NETA ETT Level 1: Cables, Switches, and Motor Circuit Testing

NETA ETT Level 1 · Work through your exam, one topic at a time.

All guide sections

Cables, Switches, and Motor Circuit Testing

Cables, Switches, and Motor Circuit Testing covers insulation, continuity, contact condition, and motor winding balance. Cable tests include insulation resistance and, where specified, time-domain reflectometry or high-voltage proof testing. Switch tests include contact resistance and insulation. Motor tests include winding resistance, insulation resistance, rotation, and no-load current.

Core rules

  • Isolate both ends of a cable before insulation testing and discharge it afterward; capacitance can hold a charge.
  • Disconnect VFDs, surge suppressors, and sensitive electronics before megging a motor circuit.
  • Measure motor winding resistance phase-to-phase and compare balance. A common field guide is to investigate deviations beyond about 5-10%, but manufacturer criteria control.
  • Check switch contact resistance with a micro-ohmmeter and inspect contacts for pitting or misalignment.
  • Verify motor rotation uncoupled where possible and record no-load current against nameplate.

Worked example

A three-phase motor reads 1.20 Ω, 1.20 Ω, and 1.80 Ω. Average is 1.40 Ω; the high phase deviates by 0.40 / 1.40 = 28.6%, far beyond a typical balance limit. The technician checks lead placement, connection tightness, and temperature, then investigates the winding or internal connections. The reasoning is that a large phase imbalance is a red flag even when the motor still runs.

Traps

Megging a circuit with a VFD connected; not discharging a cable after test; testing motor windings at unequal temperatures; and accepting a running motor as proof of winding balance.