Arc flash boundary
The distance from live parts at which incident energy equals 1.2 cal/cm²; inside it, workers must wear arc-rated PPE appropriate to the calculated incident energy.
Energized electrical work permit
A documented authorization required for work on or near exposed energized conductors at 50 V or more, listing hazards, shock and arc boundaries, PPE, and justification for energized work.
Limited approach boundary
A shock-protection boundary that unqualified persons may not cross unless escorted by a qualified person; only qualified persons may cross the restricted boundary.
Lockout/tagout verification
After isolating and locking a circuit, a qualified person tests for absence of voltage with a meter rated for the circuit, verifying the tester on a known live source before and after.
Arc-rated PPE
Clothing and equipment with an arc rating at least equal to the calculated incident energy; nonmelting natural-fiber garments are worn under arc-rated layers to prevent burns.
Qualified person
A person who has demonstrated skills and knowledge in electrical safety and construction and has received training to identify and avoid electrical hazards.
Minimum approach distance
The closest distance a qualified worker may approach exposed energized parts; it increases with voltage and requires voltage-rated tools and PPE when crossed.
Shock protection boundaries
Limited and restricted approach boundaries defined by voltage; limited restricts unqualified persons, while restricted permits only qualified workers using shock protection.
Ohm's law
For a resistive circuit, voltage equals current times resistance (V = IR); it is used with power equations P = VI, P = I²R, and P = V²/R.
Three-phase power formula
For a balanced three-phase load, real power is P = √3 × line-to-line voltage × line current × power factor; reactive power uses the sine of the angle.
Power factor
The ratio of real power in kilowatts to apparent power in kilovolt-amperes, equal to the cosine of the impedance angle for sinusoidal waveforms.
Transformer turns ratio
The primary-to-secondary voltage ratio equals the turns ratio; current ratio is inverse, so a step-down voltage transformer steps current up.
Wye connection relationships
In a balanced wye, line-to-line voltage is √3 times line-to-neutral voltage, and line current equals phase current.
Delta connection relationships
In a balanced delta, line-to-line voltage equals phase voltage, and line current is √3 times phase current.
One-line diagram
A schematic using single lines and standard symbols to show major power equipment, buses, and protective devices without every conductor.
IEEE device number 87
The ANSI/IEEE device number for differential protection, which compares currents entering and leaving a zone to detect internal faults.
Insulation resistance test
A DC test that applies a selected voltage to insulation and measures resistance; readings are temperature-corrected and compared with baseline and minimum acceptance values.
Polarization index
The ratio of 10-minute insulation resistance to 1-minute insulation resistance; a low value can indicate moisture, contamination, or insulation deterioration.
Four-wire resistance measurement
A Kelvin method using separate current and voltage leads so lead resistance is excluded, giving accurate low-resistance readings of bus joints and contacts.
Fall-of-potential test
A ground resistance method using current and potential stakes; the potential probe is placed at about 62% of the distance to the current stake.
Clamp-on ground tester
An instrument that measures ground loop resistance by inducing a signal; it requires a bonded system with parallel return paths and is not valid on an isolated electrode.
True RMS meter
A meter that calculates the root-mean-square value of a distorted waveform; average-responding meters can underread or overread non-sinusoidal currents and voltages.
CAT rating
A safety category and voltage rating for test instruments; the meter's CAT rating must equal or exceed the circuit's category and voltage.
Phase sequence meter
An instrument that indicates the order of phase rotation; it is used before connecting motors or parallel sources to verify clockwise or counterclockwise sequence.
Turns ratio test
A transformer test that applies voltage to one winding and measures the other to verify ratio and polarity against nameplate values.
Contact resistance test
A low-resistance measurement across closed breaker or switch contacts; elevated values indicate pitting, contamination, or insufficient contact pressure.
Primary injection test
A test that injects current through a circuit breaker or current transformer primary to verify ratio, wiring, and trip characteristics at realistic currents.
Secondary injection test
A test that injects voltage or current into a protective relay's secondary circuits to verify pickup, timing, and logic without primary current.
Thermographic survey
An infrared inspection performed under load to find loose connections, overloaded conductors, and other hotspots by comparing phase temperatures.
Torque check
Verification that bus and cable terminations are tightened to manufacturer-specified torque using a calibrated torque wrench; loose joints overheat.
Battery float voltage
The steady voltage maintained across each cell during float charging; it is checked to detect cells that are weak, sulfated, or overcharging.
Motor surge comparison
A test that compares impedance or pulse responses among motor windings to detect turn-to-turn shorts, opens, or winding asymmetry.