NETA ETT Level 2 key terms
NETA ETT Level 2 · Get comfortable with the vocabulary.
- Arc flash boundary
- Related: Incident energy, Arc-rated PPE
The distance from energized equipment at which a person could receive second-degree burns from an arc flash. It is calculated from incident energy and marks where arc-rated protective equipment becomes mandatory.
- Incident energy
- Related: Arc flash boundary, Arc-rated PPE
The amount of thermal energy per unit area, usually stated in calories per square centimeter, that reaches a surface during an arc flash. It is used to select clothing and equipment with adequate arc ratings.
- Limited approach boundary
- Related: Restricted approach boundary, Qualified person
A shock-protection boundary set at a distance from exposed live parts where only qualified persons, or unqualified persons under escort, may proceed. Shock protection and hazard awareness are required inside it.
- Restricted approach boundary
- Related: Limited approach boundary, Minimum approach distance
A closer shock-hazard boundary around exposed live parts that only qualified persons may cross, using appropriate shock protection and usually an energized work permit.
- Lockout/tagout
- Related: Equipotential grounding, Qualified person
A formal procedure for de-energizing equipment, isolating every energy source, applying locks and tags, releasing stored energy, and verifying a zero-energy state before work starts.
- Equipotential grounding
- Related: Step potential, Touch potential
Connecting all conductors and nearby grounded metal together with temporary protective grounds so the entire work area sits at one potential and no dangerous voltage difference can appear across a worker.
- Step potential
- Related: Touch potential, Equipotential grounding
The voltage difference between two points on the earth's surface roughly one step apart, created when fault current spreads outward through the soil from a grounded or fallen conductor.
- Touch potential
- Related: Step potential, Equipotential grounding
The voltage difference between a person's hand resting on a grounded metal object and their feet standing on the earth, caused by fault current flowing through the grounding path.
- Arc-rated PPE
- Related: Incident energy, Arc flash boundary
Clothing and equipment tested to a stated arc thermal performance value, marked in calories per square centimeter, that gives a known level of protection against arc flash heat.
- Qualified person
- Related: Limited approach boundary, Lockout/tagout
A worker who has demonstrated the skills and knowledge needed to work safely on or near energized electrical equipment and who is trained to recognize and avoid the associated hazards.
- Minimum approach distance
- Related: Restricted approach boundary, Qualified person
The closest distance a qualified worker may bring any part of the body, tool, or test lead to an exposed energized conductor, determined by system voltage and required shock protection.
- Ohm's law
- Related: Impedance, Kirchhoff's current law
The relationship stating that voltage equals current multiplied by resistance in a DC circuit, or by impedance in an AC circuit, so any one value can be calculated from the other two.
- Power factor
- Related: Three-phase power, Phasor diagram
The ratio of real power in watts to apparent power in volt-amperes in an AC circuit. It runs from zero to one and shows how much of the current performs useful work.
- Impedance
- Related: Ohm's law, Phasor diagram
The total opposition an AC circuit offers to current flow, combining resistance and reactance. It is measured in ohms and treated as a phasor quantity with magnitude and angle.
- Kirchhoff's current law
- Related: Ohm's law
The principle that the total current entering a junction equals the total current leaving it, since charge cannot pile up at a node. It underpins circuit analysis and current measurements.
- Phasor diagram
- Related: Impedance, Power factor
A drawing that represents alternating voltages and currents as vectors rotating together, making their magnitudes and phase relationships visible so they can be compared and combined graphically.
- Transformer turns ratio
- Related: Turns ratio test, Three-phase power
The ratio of primary winding turns to secondary winding turns, which equals the primary-to-secondary voltage ratio in an ideal transformer and varies inversely with the current ratio.
- Three-phase power
- Related: Power factor, Phasor diagram
Power supplied by three sinusoidal voltages displaced 120 degrees apart, which delivers constant power to a balanced load and is calculated as the square root of three times line voltage times line current times power factor.
- One-line diagram
- Related: Transformer turns ratio, Three-phase power
A simplified drawing that uses single lines and standard symbols to show how power flows through generators, transformers, breakers, buses, and protective devices in a system.
- Megohmmeter
- Related: Polarization index, Dielectric absorption ratio
An instrument that applies a high direct voltage to insulation and measures the tiny resulting current, calculating and displaying insulation resistance in megohms or gigohms.
- Polarization index
- Related: Dielectric absorption ratio, Megohmmeter
The ratio of insulation resistance measured at ten minutes to the value at one minute. A result near or above 2.0 generally indicates dry insulation in acceptable condition.
- Dielectric absorption ratio
- Related: Polarization index, Megohmmeter
The ratio of insulation resistance at sixty seconds to the value at thirty seconds. It is a short version of the polarization index used to flag moisture and contamination.
- Micro-ohmmeter
- Related: Four-wire Kelvin measurement, Contact resistance
A four-wire instrument that injects a known direct current and measures the very small voltage drop produced, reading low resistances such as breaker contacts and bus joints in microhms.
- Four-wire Kelvin measurement
- Related: Micro-ohmmeter, Contact resistance
A resistance technique that uses two current-carrying leads and two separate voltage-sensing leads, canceling lead and contact resistance so very low values can be read accurately.
- Insulation power factor
- Related: Megohmmeter, Partial discharge
The ratio, expressed as a percentage, of resistive current to capacitive current through insulation at a test voltage. Rising values point to moisture, contamination, or aging.
- Partial discharge
- Related: Insulation power factor, Dielectric withstand test
Small localized electrical discharges inside insulation voids or along surfaces that do not bridge the electrodes. They slowly erode insulation and are found with acoustic or electrical sensors.
- True RMS
A meter function that computes the heating-equivalent value of a distorted waveform instead of assuming a pure sine wave, so harmonic-rich circuits are measured correctly.
- Fall-of-potential test
- Related: Step potential, Touch potential
A method of measuring earth resistance by driving a current probe and a potential probe into the ground at set spacings and comparing the voltage drop with the injected current.
- Infrared thermography
- Related: Contact resistance, Micro-ohmmeter
Using a thermal imaging camera to compare temperatures on energized equipment, where abnormal heating reveals loose connections, overloads, or failing components before failure occurs.
- Winding resistance test
- Related: Turns ratio test, Micro-ohmmeter
Measuring the DC resistance of transformer or motor windings and comparing phases or earlier readings to uncover opens, shorts, poor connections, or turn-to-turn faults.
- Turns ratio test
- Related: Transformer turns ratio, Winding resistance test
Applying a known AC voltage to one transformer winding and measuring the induced voltage on another to confirm the ratio and detect shorted turns or incorrect tap settings.
- Sweep frequency response analysis
- Related: Winding resistance test
Comparing a transformer's impedance signature across a range of frequencies with a baseline record to detect winding deformation, displacement, or core damage after a fault or during shipping.
- Circuit breaker time-travel analysis
- Related: Contact resistance
Recording contact travel against time during a trip or close operation and comparing the curve with manufacturer data to judge operating speed, damping, and mechanical condition.
- Dielectric withstand test
- Related: Partial discharge, Insulation power factor
Applying a specified high AC or DC voltage above normal operating level for a set period to prove that insulation can endure it without breakdown or excessive leakage.
- Battery conductance test
- Related: Micro-ohmmeter
A quick, non-destructive check that applies a small AC signal to a battery and estimates internal resistance and available capacity without discharging the battery.
- Contact resistance
- Related: Micro-ohmmeter, Infrared thermography
The resistance measured across mated breaker or switch contacts, which increases with pitting, corrosion, or misalignment and causes overheating when the equipment carries load.