Using a Fire Barrier as a Fire Wall to Avoid Sprinklers

NFPA CFPE · Put your knowledge to work in context.

All case studies

Using a Fire Barrier as a Fire Wall to Avoid Sprinklers

A single-story, 48,000 sq ft Type II(000) building is being converted from warehouse to Group M mercantile. The designer proposes a 2-hour gypsum-and-steel-stud assembly across the building at mid-span with a pair of 90-minute fire doors and argues this creates two separate 24,000 sq ft "buildings," so neither exceeds the unsprinklered allowable area for the construction type and no sprinkler system is needed. The barrier stops at the underside of the steel roof deck, is laterally supported by the existing bar joists on both sides, and the roof deck runs continuously over it. The east half has one exit door at its far corner, roughly 260 ft from the barrier door along the line of travel. Separately, the east exterior wall sits 12 ft from the lot line and contains 35 percent unprotected openings.

1. Is the 'two buildings' theory supportable on the facts given? Walk through what the proposed assembly must do to qualify.

Read the worked answer

Step 1 - What a fire wall must do. A fire wall divides a building into separate buildings. It must have sufficient structural integrity to remain standing under fire conditions with collapse of construction on either side, which in practice means it is structurally independent, or it is designed and detailed (and analyzed) so that the collapse of either side does not pull it down. It must be continuous from the foundation through the roof.

Step 2 - Test the proposed assembly. This wall stops at the roof deck, is supported by the joists it is meant to protect against, and the deck continues over it. On any collapse of the joists on one side, the wall loses lateral support and the roof diaphragm still ties the two halves together. The assembly is therefore a fire barrier, not a fire wall.

Step 3 - Consequence. With no fire wall, the building is one 48,000 sq ft building of Type II(000) mercantile, and the allowable-area table for the adopted edition, unsprinklered, is almost certainly exceeded. The fix is not to relabel the wall; it is to provide sprinkler protection, or to construct a code-compliant fire wall (independent foundation, continuous through the roof, with the roof terminating at the wall), which is usually more expensive.

Note: fire barriers still have real uses - separating occupancies or protecting exits - but they do not divide buildings for area purposes.

2. What is wrong with the egress from the east half, and what does that tell you about the design's internal logic?

Read the worked answer

Step 1 - Count the exits. If the east half is treated as an independent building or tenant space, it has one exit serving an area that will hold hundreds of occupants in mercantile use. Independent buildings and single-exit spaces both require either a second remote means of egress or a demonstration that the space falls within the single-exit allowances of the adopted edition (occupant load and travel distance within the limits for the occupancy and sprinkler status).

Step 2 - Measure travel. Travel distance is measured along the line of travel from the most remote point to an exit. At 260 ft, even before checking the table, this is beyond the exit access travel limits for unsprinklered mercantile in any edition.

Step 3 - Read the argument for what it is. The designer is treating the barrier door as the second exit from the east half. Doors in a fire barrier are not exits for the other side unless the path beyond them is a protected exit or exit access that meets remoteness and capacity - and here the path beyond leads back into the west half's own exit access.

Conclusion: Even if the fire wall argument were accepted, the east half fails egress on travel distance and single-exit grounds. That failure is itself evidence that the two halves are functionally one space.

3. On the exterior wall 12 ft from the lot line with 35 percent unprotected openings, what must the reviewer require?

Read the worked answer

Step 1 - Frame the issue. Exterior wall fire resistance and permitted unprotected opening area are functions of the fire separation distance to the lot line and to other buildings. As the distance shrinks, the required rating rises and the permitted percentage of unprotected openings falls, because radiant heat and flame impingement on the neighbor is the hazard being controlled.

Step 2 - Get the actual values. Read the exterior wall table in the adopted edition of NFPA 101 for the construction type and occupancy, and confirm the assumed lot line with a survey. Twelve feet is a short separation; at that distance the table and the local zoning setback both come into play, and 35 percent unprotected is likely above the allowance.

Step 3 - What to require. Either reduce the unprotected opening area, protect openings with rated assemblies (fire shutters, listed glazing in rated frames with the appropriate hose-stream rating), increase the rating of the wall, or install sprinklers if the adopted table grants a trade-off for sprinkler protection. Do not allow the designer to average openings across the whole wall if the table is applied to the wall plane facing the lot line.

Step 4 - Document. Record the assumed lot line location, because this finding changes if the adjacent parcel is replatted.