NFPA CFPE · Keep the key ideas within reach.

Quick reference

Plan Review Fundamentals and Code Administration

  • NFPA documents establish minimum requirements; the authority having jurisdiction (AHJ) may require additional protection where conditions warrant.

  • Plan review of water-based suppression systems typically requires hydraulic calculations, shop drawings, and equipment data sheets submitted before installation begins.

  • Performance-based designs permitted by NFPA 101 Chapter 5 must document design fire scenarios, occupant response assumptions, and acceptance criteria for AHJ approval.

  • An equivalency request must demonstrate that the proposed alternative provides a level of safety at least equivalent to the literal code requirement.

  • Acceptance tests (hydrostatic, flow, alarm, and trip tests) precede final approval; NFPA 25 then governs inspection, testing, and maintenance.

  • The owner must retain as-built drawings and inspection, testing, and maintenance records and make them available to the AHJ on request.

  • Any change to approved construction documents requires a revised submittal and re-review before the changed condition is installed.

  • Occupancy classification under NFPA 101 determines which occupancy chapter applies and drives egress, sprinkler, and detection requirements.

  • Construction, alteration, and demolition safeguards follow NFPA 241, including site protection, hot work permitting, and fire watch provisions.

Quick reference

Building Construction and Fire Resistance

  • NFPA 220 defines Types I through V: Type I is noncombustible with the highest fire resistance, while Type V is combustible with the least.

  • Type II is noncombustible but permits lower fire resistance than Type I; Type III permits noncombustible exterior walls with combustible interior framing.

  • Type IV heavy timber requires minimum member dimensions and prohibits concealed combustible spaces within the assembly.

  • Fire resistance ratings are established by ASTM E119 or UL 263 furnace tests and are expressed in hours, such as 1-hour or 2-hour ratings.

  • Assemblies carry restrained or unrestrained ratings; for the same design, the unrestrained rating is often lower than the restrained rating.

  • Fire walls per NFPA 221 must be structurally stable and resist fire from either side, subdividing a building into separate building areas.

  • Smoke barriers must be at least 1/2-hour rated with protected openings; fire barriers separating fire areas are typically 1 or 2 hours.

  • Vertical openings such as stairways and shafts must be enclosed with fire-resistance-rated construction in accordance with NFPA 101 Chapter 8.

  • Roof coverings are classified Class A, B, or C by external fire exposure testing, with Class A providing the highest resistance.

Quick reference

Means of Egress and Life Safety

  • A means of egress comprises exit access, exit, and exit discharge; each component must be continuous and unobstructed.

  • Required egress capacity is 0.2 in (5 mm) per occupant on level components and ramps; stairs require a greater width per occupant.

  • Business occupancy uses 100 ft² gross per occupant; assembly unconcentrated is 15 ft² net and concentrated is 7 ft² net.

  • Where two exits are required, they must be separated by at least one-half the diagonal of the area served, or one-third where sprinklered.

  • Dead-end corridors are limited to 20 ft, increased to 50 ft where the building is protected throughout by automatic sprinklers.

  • Travel distance is measured along the actual path of egress travel from the most remote point in the area to the nearest exit.

  • Emergency lighting must provide at least 1 ft-candle average and 0.1 ft-candle minimum at the floor for a duration of 90 minutes.

  • Egress doors must provide at least 32 in clear width and must swing in the direction of travel where serving 50 or more occupants.

  • Guards are required at least 42 in high where the drop exceeds 30 in; handrails on stairs are set 34 in above tread nosings.

Quick reference

Fire Protection, Detection, and Suppression Systems

  • Light hazard design density is 0.10 gpm/ft² over 1,500 ft²; Ordinary Hazard Group 1 is 0.15/1,500 and Group 2 is 0.20/1,500.

  • Extra Hazard Group 1 is 0.30 gpm/ft² over 2,500 ft²; Extra Hazard Group 2 is 0.40 gpm/ft² over 2,500 ft².

  • Sprinkler temperature ratings: ordinary 135–170°F, intermediate 175–225°F, high 250–300°F, very high 325–375°F.

  • Sprinklers require at least 18 in of clearance between the deflector and the top of storage.

  • Fire pumps must deliver at least 65 percent of rated head at 150 percent of rated flow (NFPA 20).

  • Standpipe classes per NFPA 14: Class I provides 2½ in outlets, Class II provides 1½ in outlets, and Class III provides both.

  • Spot-type smoke detectors on smooth ceilings: 30 ft maximum spacing and 21 ft maximum distance from a sidewall.

  • Fire alarm audible signals must be at least 15 dBA above average ambient and not more than 110 dBA at the minimum hearing distance.

  • Class A portable extinguishers: 75 ft maximum travel distance; Class B: 30 ft for high hazard and 50 ft for other than high hazard.

Quick reference

Hazardous Materials and Special Processes

  • NFPA 704 marking: blue = health, red = flammability, yellow = instability, white = special hazards; hazard quadrants are rated 0 through 4.

  • NFPA 30 Class I liquids have flash points below 100°F: IA (FP < 73°F, BP < 100°F), IB (FP < 73°F, BP ≥ 100°F), IC (FP 73–100°F).

  • Class II liquids have flash points ≥ 100°F and < 140°F; Class IIIA is ≥ 140°F and < 200°F; Class IIIB is ≥ 200°F.

  • A single flammable liquid storage cabinet may hold up to 60 gal of Class I or II liquids, or 120 gal of Class III liquids.

  • Hot work requires a 35 ft clearance from combustibles, a written permit, and a fire watch in accordance with NFPA 51B.

  • Spray application of flammable finishes follows NFPA 33; dip tanks follow NFPA 34; ovens and furnaces follow NFPA 86.

  • Combustible dust programs use the fundamentals of NFPA 652, including a dust hazard analysis, plus commodity standards such as NFPA 654.

  • NFPA 70 Article 500 classifies locations as Class I (gases/vapors), Class II (dusts), or Class III (fibers/flyings); Division 1 means the hazard is normally present.

  • NFPA 58 governs LP-Gas storage and handling, including container separation distances and maximum quantity limits.