NH Water/Wastewater Operator study materials
NH Water/Wastewater Operator study resources

NH Water/Wastewater Operator cheat sheet

NH Water/Wastewater Operator · Keep the key ideas within reach.

Quick reference

Drinking Water Treatment and Distribution

  • CT (contact time) = disinfectant residual concentration (mg/L) × contact time (min); CT required rises as temperature falls and pH rises for free chlorine.

  • Free chlorine: raise dose or contact time to hit required CT; chloramine forms when ammonia is added, giving a weaker but more persistent residual.

  • Conventional surface water train: coagulation → flocculation → sedimentation → filtration → disinfection; filtration must reduce turbidity to ≤0.3 NTU in 95% of monthly samples (and never exceed 1 NTU).

  • Detention time (h) = tank volume (gal) ÷ flow (gal/h); overflow rate (gpm/ft²) = flow ÷ clarifier surface area.

  • Distribution minimum pressure is 20 psi under normal conditions; a boil-water notice is triggered by pressure loss or confirmed contamination.

  • Head loss in pipe rises with flow squared (Hazen-Williams); flushing velocity should exceed 2.5 ft/s to scour sediment.

  • Pump horsepower = (flow in gpm × head in ft) ÷ (3,960 × pump efficiency); brake horsepower adds motor efficiency.

  • Backflow prevention: air gap is the highest protection; reduced-pressure-zone assemblies protect against both backsiphonage and backpressure.

Quick reference

Wastewater Treatment and Collection

  • BOD5 measures oxygen consumed over 5 days at 20°C; typical domestic wastewater BOD5 is 200–250 mg/L and TSS 200–250 mg/L.

  • F/M ratio = (food, lb BOD/day) ÷ (microorganism mass, lb MLVSS); low F/M favors nitrification, high F/M favors bulking risk.

  • Sludge age (MCRT) = mass of solids in aeration tank ÷ mass wasted plus effluent solids per day.

  • Return activated sludge (RAS) rate is set to keep mixed liquor suspended solids (MLSS) in the 2,000–4,000 mg/L range for conventional plants.

  • Collection system: minimum self-cleansing velocity is about 2 ft/s; infiltration and inflow raise treatment costs and can cause sanitary sewer overflows.

  • Gravity sewer slope is set so flow achieves scour velocity; manholes are placed at grade changes, direction changes, and maximum spacing.

  • Chlorine disinfection of effluent uses CT; fecal coliform limits are typically 200 cfu/100 mL (monthly geometric mean) with chlorine residual maintained.

  • Anaerobic digestion reduces volatile solids; typical volatile solids destruction is 40–60% and biogas (methane ~60–65%) is recoverable.

Quick reference

Water Quality Analysis, Sampling, and Reporting

  • Turbidity is measured in NTU with a nephelometer calibrated against formazin standards; report to two significant figures below 1 NTU.

  • Total coliform presence triggers repeat sampling; E. coli confirmation requires public notification within 24 hours under the Total Coliform Rule.

  • Chlorine residual is measured by DPD colorimetric or amperometric titration; record free and total chlorine to 0.01 mg/L.

  • pH is measured with a calibrated electrode using pH 4, 7, and 10 buffers; calibrate before each sampling day.

  • Sample holding times: chlorine and pH are analyzed immediately (15 min); nitrate 48 hours; metals 6 months after preservation with HNO3 to pH <2.

  • Chain of custody must record sampler, date/time, location, preservation, and transfer signatures for legal defensibility.

  • Nitrate is analyzed by ion chromatography or cadmium reduction; MCL is 10 mg/L as N; nitrite MCL is 1 mg/L as N.

  • Lead and copper sampling uses first-draw 1-L samples after 6 hours of no use; 90th percentile action level is 0.015 mg/L lead, 1.3 mg/L copper.

Quick reference

Regulations, Safety, and Administration

  • Safe Drinking Water Act sets MCLs, Treatment Techniques, and monitoring; states with primacy enforce and report to EPA.

  • Stage 2 Disinfectants/Disinfection Byproducts Rule: TTHM MCL 80 µg/L and HAA5 MCL 60 µg/L, based on locational running annual averages.

  • Consumer Confidence Report must be delivered to customers annually by July 1 and include source water, detected contaminants, and health effects language.

  • Clean Water Act NPDES permits limit effluent parameters and require monthly discharge monitoring reports (DMRs).

  • Confined space entry requires atmospheric testing (O2 19.5–23.5%, LEL <10%, H2S <10 ppm), a permit, attendant, and rescue plan.

  • Chlorine gas is heavier than air; use SCBA and evacuate upwind; never use ammonia to neutralize a chlorine release.

  • Operator certification requires state exam plus continuing education (often 2.0 CEUs per 2-year cycle); Grade level tied to system classification.

  • Hazard communication requires SDS access, labeling, and training; lockout/tagout applies before servicing pumps and blowers.