NH Water/Wastewater Operator study materials
NH Water/Wastewater Operator study resources

NH Water/Wastewater Operator flashcards

NH Water/Wastewater Operator · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

CT concept
Product of disinfectant residual concentration and contact time used to demonstrate pathogen inactivation; required CT increases with colder water and higher pH for free chlorine.
Turbidity limit
Combined filter effluent must be at or below 0.3 NTU in at least 95 percent of monthly measurements and never exceed 1 NTU for conventional filtration.
Detention time formula
Detention time equals tank volume divided by flow rate; keep units consistent, such as gallons divided by gallons per hour to yield hours.
Overflow rate
Surface overflow rate is flow divided by clarifier surface area, expressed in gallons per day per square foot; it governs particle settling performance.
Minimum distribution pressure
Twenty psi must be maintained throughout the distribution system under normal operating conditions; loss of pressure triggers notification and corrective action.
Air gap backflow protection
A physical separation between a potable supply and a receiving vessel; it is the highest level of backflow protection against backsiphonage and backpressure.
Pump horsepower
Water horsepower equals flow in gallons per minute times head in feet divided by 3,960; divide by pump efficiency for brake horsepower.
Chloramine residual
Formed by adding ammonia to chlorinated water; it is a weaker disinfectant than free chlorine but persists longer in distribution systems.
BOD5 definition
Biochemical oxygen demand measured over five days at 20 degrees Celsius; it estimates biodegradable organic matter in wastewater, typically 200 to 250 mg/L domestic.
F/M ratio
Food-to-microorganism ratio equals pounds of BOD entering per day divided by pounds of MLVSS in the aeration tank; it controls sludge bulking and nitrification.
Sludge age (MCRT)
Mean cell residence time equals solids mass in the aeration tank divided by solids leaving daily in waste sludge plus effluent; it controls biomass inventory.
RAS purpose
Return activated sludge recycles settled biomass from the clarifier to the aeration tank, maintaining mixed liquor suspended solids in the treatment range.
Self-cleansing velocity
About two feet per second in gravity sewers keeps solids suspended and prevents deposition; lower velocities allow grit and grease to accumulate.
Infiltration and inflow
Groundwater entering through defects is infiltration; stormwater entering through illicit connections is inflow. Both add clear water load to treatment.
Fecal coliform limit
Typical effluent limit of 200 colony-forming units per 100 milliliters as a monthly geometric mean, with chlorine residual maintained to ensure disinfection.
Anaerobic digestion
Bacteria break down volatile solids without oxygen, reducing sludge mass 40 to 60 percent and producing biogas containing roughly 60 to 65 percent methane.
Turbidity measurement
Nephelometry measures light scattered by suspended particles in NTU; instruments are calibrated with formazin primary standards and results below 1 NTU use two significant figures.
Total coliform trigger
A positive total coliform sample requires repeat sampling at the site; E. coli confirmation requires public notification within 24 hours.
DPD chlorine test
Colorimetric method where DPD reagent reacts with chlorine to form a colored compound; free and total chlorine are reported to 0.01 mg/L.
pH calibration buffers
A pH meter is calibrated with buffers at pH 4, 7, and 10 to bracket sample range; calibration is performed before each sampling day.
Nitrate MCL
Maximum contaminant level for nitrate is 10 mg/L as nitrogen; nitrite is 1 mg/L as nitrogen. Both are analyzed by ion chromatography or cadmium reduction.
Lead action level
The 90th percentile lead action level is 0.015 mg/L, based on first-draw one-liter samples collected after six hours without water use.
Chain of custody
Documentation recording sampler, date, time, location, preservation, and transfer signatures; it establishes sample integrity for regulatory and legal purposes.
Sample holding time
Maximum time a sample may be held before analysis; chlorine and pH are analyzed immediately, nitrate within 48 hours, and preserved metals within six months.
Safe Drinking Water Act
Federal law authorizing EPA to set maximum contaminant levels and treatment techniques; states with primacy enforce and report compliance.
TTHM MCL
Total trihalomethanes are limited to 80 micrograms per liter and HAA5 to 60 micrograms per liter, evaluated as locational running annual averages.
Consumer Confidence Report
Annual report delivered to customers by July 1, listing source water, detected contaminants, and required health effects language.
NPDES permit
Clean Water Act permit limiting effluent parameters and requiring monthly discharge monitoring reports for point source wastewater discharges.
Confined space entry
Entry requires atmospheric testing for oxygen, flammables, and hydrogen sulfide, plus a permit, attendant, and rescue plan before entry.
Chlorine gas response
Chlorine gas is heavier than air; responders use SCBA, evacuate upwind, and never use ammonia, which reacts to form dangerous compounds.
Operator certification
State-issued credential tied to system classification grade, requiring passing an exam and continuing education units for renewal.
Hazard communication
Requires accessible safety data sheets, labeled containers, and employee training on chemical hazards; lockout/tagout applies before equipment servicing.