Quick reference

Fire Alarm System Fundamentals and Components

  • Conventional systems report alarms by zone; addressable systems report each device by its unique address.

  • A Class A circuit continues to operate after a single open or ground fault; a Class B circuit does not.

  • Photoelectric spot detectors respond best to smoldering fires; ionization detectors respond best to flaming fires.

  • Fixed-temperature heat detectors alarm at a set point; rate-of-rise detectors alarm when temperature rises faster than about 15 degrees F per minute.

  • Duct smoke detectors supervise HVAC air movement but do not replace area smoke detection.

  • Waterflow switches use a retard of about 10 to 60 seconds to avoid false alarms from pressure surges; valve tamper switches are supervisory.

  • For commercial protected premises, the default secondary battery supply is 24 hours of standby plus 5 minutes of alarm.

  • Notification appliance circuits are supervised power circuits; Class B NACs require an end-of-line resistor or equivalent supervision.

  • Alarm, trouble, and supervisory signals are distinct conditions that must be visually and audibly distinguishable.

Quick reference

Codes, Standards, and Referenced Documents

  • NFPA 72 is the fire alarm and signaling code for design, installation, testing, and maintenance; NEC Article 760 governs fire alarm wiring methods.

  • NFPA 101 addresses life safety and occupancy features; NFPA 13 covers sprinkler systems that interface with the fire alarm system.

  • UL 864 lists fire alarm control units; UL 268 covers smoke detectors; UL 521 covers heat detectors; UL 1971 covers visible signaling; UL 464 covers audible appliances.

  • The authority having jurisdiction enforces the adopted code edition; the IBC and IFC reference NFPA 72 for fire alarm requirements.

  • NFPA 72 permits prescriptive design or performance-based design; performance-based designs require documented engineering analysis and AHJ approval.

  • Pathway survivability levels 0 through 4 define increasing protection for fire alarm circuits, from no protection to 2-hour rated cable in a 2-hour enclosure.

  • Required documentation includes shop drawings, record of completion, as-built drawings, and inspection and test records.

  • Where NFPA 72 and the NEC both address an installation method, the NEC governs the wiring method.

Quick reference

System Layout, Design, and Documentation

  • On smooth ceilings, spot smoke detectors are typically spaced at 30 feet, with the first detector within 15 feet of any wall.

  • Spot heat detectors are typically spaced at 50 feet on smooth ceilings, with reduced spacing as ceiling height increases.

  • Manual pull stations are mounted 42 to 48 inches above finished floor, within 5 feet of an exit door, and unobstructed.

  • Visible notification candela is selected from UL 1971 tables based on room size and viewing distance; corridors require at least 15 candela.

  • Voltage drop equals 2 times length times current times resistance per 1000 feet; verify the last appliance receives its minimum rated voltage.

  • Battery capacity equals standby current times standby hours plus alarm current times alarm minutes divided by 60, plus derating.

  • Shop drawings show device locations, wiring, conduit routes, and panel schedules and are submitted for approval before installation.

  • Duct smoke detectors are located in the return or main duct downstream of filters and before branch connections, with access for service.

Quick reference

Installation, Wiring, and Circuit Integrity

  • A Class B notification circuit uses an end-of-line resistor at the last device; a Class A circuit returns conductors to the panel for supervision.

  • Addressable signaling line circuits are typically shielded twisted pair with the shield grounded at the panel only.

  • Fire alarm cable in plenums must be listed FPLP; riser cable must be FPLR; general-purpose cable must be FPL.

  • NEC Article 760 requires fire alarm conductors to be separated from power conductors or separated by an approved barrier.

  • Pathway survivability Level 4 requires 2-hour fire-rated cable installed within a 2-hour rated enclosure or an equivalent method.

  • Devices and junction boxes above suspended ceilings must remain accessible; concealed splices are not permitted.

  • Detector bases and devices must be installed at the manufacturer's listed spacing and orientation.

  • A ground fault on a supervised circuit annunciates as a trouble condition; the control unit must be grounded per NEC requirements.

Quick reference

Testing, Inspection, and Maintenance

  • All initiating devices, notification appliances, and control unit functions are tested at least annually unless a different interval is specified.

  • Smoke detector sensitivity is tested within one year of installation and then at alternating years thereafter.

  • Smoke detectors are tested with listed aerosol or smoke; heat detectors are tested with a controlled heat source, not an open flame.

  • A sprinkler waterflow switch must cause an alarm at the control unit within 90 seconds of waterflow.

  • Secondary batteries receive an annual load test, typically a 30-minute discharge, and are replaced when capacity falls below 80 percent.

  • A record of completion certifies that the system was installed and tested in accordance with approved plans and code.

  • Inspection and test records must be retained and made available to the authority having jurisdiction for the required period.