Addressable fire alarm system
A system in which each initiating and notification device has a unique address so the panel can identify the specific device in alarm or trouble.
Conventional zone
A grouping of devices on a circuit that reports only the zone identity, not individual device identity, to the fire alarm control unit.
Class A circuit
A supervised circuit that continues to operate after a single open or ground fault because the outgoing and return conductors both terminate at the panel.
Class B circuit
A supervised circuit that does not continue to operate after a single open fault; it uses an end-of-line device and has only one path.
Photoelectric smoke detector
A spot-type detector that uses light scattering to sense smoke particles and responds best to smoldering fires with larger particles.
Ionization smoke detector
A spot-type detector that senses a change in ionization current caused by combustion particles and responds best to flaming fires.
Waterflow switch retard
A built-in delay, typically 10 to 60 seconds, that prevents sprinkler waterflow switches from alarming on pressure surges.
NFPA 72
The National Fire Alarm and Signaling Code, covering design, installation, testing, inspection, and maintenance of fire alarm systems.
NEC Article 760
The National Electrical Code article governing fire alarm system wiring methods, conductor requirements, and installation practices.
UL 864
The product standard listing fire alarm control units and related equipment for use in protected premises systems.
Authority Having Jurisdiction
The organization or individual that enforces code requirements and approves designs, installations, and modifications.
Performance-based design
A design approach that states fire safety goals and demonstrates compliance through engineering analysis rather than prescriptive spacing rules.
Pathway survivability
A classification from Level 0 to Level 4 describing how well fire alarm circuit pathways resist fire damage during a fire.
Smoke detector spacing
On smooth ceilings, spot smoke detectors are typically spaced at 30 feet, with the first detector within 15 feet of any wall.
Heat detector spacing
Standard spot heat detectors are typically spaced at 50 feet on smooth ceilings, with reduced spacing for higher ceilings.
Manual pull station height
Pull stations are mounted 42 to 48 inches above the finished floor, within 5 feet of an exit door, and unobstructed.
Voltage drop formula
Vdrop equals 2 times length times current times resistance per 1000 feet; verify the last appliance still receives its minimum rated voltage.
Battery sizing formula
Required capacity equals standby current times standby hours plus alarm current times alarm minutes divided by 60, with derating.
Shop drawings
Detailed installation drawings showing device locations, wiring, conduit routes, and panel schedules, submitted for approval before installation.
Duct smoke detector location
Installed in the return or main duct downstream of filters and before branch connections, with access for testing and service.
End-of-line resistor
A resistor at the last device of a Class B circuit that allows the panel to supervise the circuit for opens and shorts.
FPLP cable
Fire alarm cable listed for use in plenums, where smoke and flame spread requirements are more stringent than riser or general-use cable.
SLC wiring
Signaling line circuit wiring for addressable systems, typically shielded twisted pair with the shield grounded at the panel only.
Above-ceiling accessibility
Fire alarm devices and junction boxes installed above suspended ceilings must remain accessible for inspection, testing, and maintenance.
Ground fault
An unintended connection between a fire alarm conductor and ground, annunciated as a trouble condition by the control unit.
Survivability Level 4
The highest pathway protection level, requiring 2-hour fire-rated cable installed within a 2-hour rated enclosure or equivalent.
Annual device testing
All initiating devices, notification appliances, and control unit functions are tested at least annually unless the code specifies a different interval.
Smoke sensitivity test interval
Detectors are tested for sensitivity within one year of installation and then at alternating years thereafter, per NFPA 72.
Waterflow alarm time
A sprinkler waterflow switch must cause an alarm at the fire alarm control unit within 90 seconds of waterflow.
Battery load test
An annual test that discharges the secondary battery under load, typically for 30 minutes, to verify capacity.
Record of completion
A document certifying that the fire alarm system was installed and tested in accordance with the approved plans and code.
Test record retention
Inspection and test records must be retained and made available to the authority having jurisdiction for the required period.