CO2 Total Flooding in a Periodically Occupied Solvent Room

NICET Special Hazards III · Put your knowledge to work in context.

All case studies

CO2 Total Flooding in a Periodically Occupied Solvent Room

A printing plant protects a 4,200 ft3 solvent storage room with a CO2 total-flooding system: eight 50 lb cylinders on a manifold, a 34% design concentration, and a 60-second design discharge. The room is normally unoccupied but is entered several times per shift to move solvent drums. The only door is a 3 ft swing door with a keypad lock and no panic hardware. A bell is mounted outside the door; there is no alarm or warning sign inside the room. The room's return-air duct discharges into the adjacent occupied production area with no damper. During your survey, a maintenance worker says he just props the door and works fast when the system is armed, and the plant has no procedure for locking out the system during maintenance. The owner wants to add an odorizer to the CO2 and delete the outside bell, which has caused three nuisance alarms this year.

1. Evaluate this installation. What must change before you would recommend sign-off, and what question about occupancy remains?

Read the worked answer

Several features are unacceptable as found, regardless of the agent calculation. The door must permit egress without a key, so panic hardware or a fail-safe release is required; a keypad lock on the only exit is a life-safety defect. There must be a conspicuous warning sign at the entrance and an alarm perceptible inside the room before discharge, with a time delay long enough for a person inside to reach the exit. A bell outside only warns people about to enter, not the person already inside. A maintenance lockout on the manifold, a written entry and lockout procedure, and training are essential, especially given the worker's practice of propping the door. The return-air duct must have a damper interlocked to close on actuation, or CO2 will migrate into the occupied production area. After a discharge, ventilation and controlled re-entry with atmosphere testing are required. Beyond these fixes, the real question is whether total-flooding CO2 is appropriate for a room entered several times per shift; that occupancy pattern may require a different agent or a different approach, and the AHJ should decide it.

2. The owner proposes adding an odorizer and deleting the outside bell to reduce nuisance alarms. How do you respond?

Read the worked answer

Reject both changes. CO2 is colorless and odorless, and an odorizer is not a reliable warning: at a 34% design concentration a person can be incapacitated within a breath or two, so by the time the odor is noticed the exposure may already be disabling. An odorizer is not a substitute for the predischarge alarm, time delay, signs, and entry controls. The outside bell is the only warning to someone about to open the door; removing it makes the room more dangerous, not less. The nuisance alarms are a detection or process problem, and the correct response is to find the cause, whether that is a detector in the wrong location, solvent vapor, or a maintenance activity, and fix it. You can add an abort or reset procedure, improve detector selection, or adjust the sequence, but the warning devices stay. Put the refusal in writing and copy the AHJ if the owner proceeds.

3. What do you require for the return-air duct and the enclosure boundary, and how do you verify it?

Read the worked answer

Require a listed damper in the return duct, interlocked to close on system actuation and on alarm, with position feedback so closure is proven rather than assumed. Confirm the supply air is shut down as well; otherwise the supply pressurizes the room and pushes agent out through the return. Evaluate the adjacent production area for CO2 migration through the duct, the door undercut, and any other shared openings, and consider detection or additional ventilation there. Verify by functional test: trip the system in test mode and confirm the damper closes, the fan stops, the alarm sounds, and the time delay runs before any agent would discharge. Record the results, update the sequence of operations, and have the owner add a post-discharge ventilation and re-entry procedure to the site plan.