NICET Special Hazards III cheat sheet
NICET Special Hazards III · Keep the key ideas within reach.
Special Hazards Systems
Clean agent total-flooding design concentration must be at least the NOAEL-adjusted extinguishing concentration; for Class C hazards the design concentration may not exceed the NOAEL, and for occupied spaces the worst-case exposure must stay below the NOAEL (NFPA 2001).
NFPA 2001 hold time: the agent concentration must remain at or above the design concentration for the period needed for occupant egress and for re-ignition control, with the minimum design hold time typically 10 minutes unless a documented risk analysis justifies otherwise.
FM-200 (HFC-227ea) design concentrations commonly range 6.25% to 7.0% for Class A and 7.0% to 8.0% for Class B; NOAEL is 9.0%, so Class C designs must not exceed 9.0%.
Inergen (IG-541) design concentrations typically run 34% to 38% for Class A and up to 43% for Class B; NOAEL is 43%, so Class C designs must not exceed 43%.
Novec 1230 (FK-5-1-12) design concentration is typically 4.2% to 5.0% for Class A and up to 5.85% for Class B; NOAEL is 10%, giving a wide safety margin.
CO2 total-flooding for occupied spaces is prohibited; CO2 is permitted only in unoccupied spaces, normally with lockout/tagout and pre-discharge alarm, and design concentration is typically 34% or higher.
For inert-gas systems, the agent quantity is calculated using the ideal gas relation: agent mass = (volume of enclosure x design concentration x gas density) / (1 - design concentration), with altitude correction for the enclosure volume.
Halocarbon agent quantity uses the NFPA 2001 formula: W = (V/S) x (C/(100-C)), where W is agent mass, V is enclosure volume, S is the specific vapor volume at the design temperature, and C is the design concentration in percent.
Pre-discharge alarm and time delay: NFPA 2001 requires a distinctive alarm and a time delay (commonly 30 seconds, adjustable) before discharge in occupied areas to allow egress, with abort stations provided where occupants may need to stop discharge.
Special Hazards Systems
Clean agent total-flooding design concentration must be at least the NOAEL-adjusted extinguishing concentration; for Class C hazards the design concentration may not exceed the NOAEL, and for occupied spaces the worst-case exposure must stay below the NOAEL (NFPA 2001).
NFPA 2001 hold time: the agent concentration must remain at or above the design concentration for the period needed for occupant egress and for re-ignition control, with the minimum design hold time typically 10 minutes unless a documented risk analysis justifies otherwise.
FM-200 (HFC-227ea) design concentrations commonly range 6.25% to 7.0% for Class A and 7.0% to 8.0% for Class B; NOAEL is 9.0%, so Class C designs must not exceed 9.0%.
Inergen (IG-541) design concentrations typically run 34% to 38% for Class A and up to 43% for Class B; NOAEL is 43%, so Class C designs must not exceed 43%.
Novec 1230 (FK-5-1-12) design concentration is typically 4.2% to 5.0% for Class A and up to 5.85% for Class B; NOAEL is 10%, giving a wide safety margin.
CO2 total-flooding for occupied spaces is prohibited; CO2 is permitted only in unoccupied spaces, normally with lockout/tagout and pre-discharge alarm, and design concentration is typically 34% or higher.
For inert-gas systems, the agent quantity is calculated using the ideal gas relation: agent mass = (volume of enclosure x design concentration x gas density) / (1 - design concentration), with altitude correction for the enclosure volume.
Halocarbon agent quantity uses the NFPA 2001 formula: W = (V/S) x (C/(100-C)), where W is agent mass, V is enclosure volume, S is the specific vapor volume at the design temperature, and C is the design concentration in percent.
Pre-discharge alarm and time delay: NFPA 2001 requires a distinctive alarm and a time delay (commonly 30 seconds, adjustable) before discharge in occupied areas to allow egress, with abort stations provided where occupants may need to stop discharge.