NICET Special Hazards III flashcards
NICET Special Hazards III · Build recall with a focused review session.
32 cards. Read the term and the definition here. The deck at the top of this page is optional.
- NOAEL
- No Observed Adverse Effect Level: the highest agent concentration at which no adverse physiological effect was observed in testing. Clean agent designs for occupied spaces must not exceed the NOAEL.
- LOAEL
- Lowest Observed Adverse Effect Level: the lowest concentration at which an adverse effect was observed. LOAEL is used to set egress and exposure limits for short-duration occupant exposure.
- Design concentration
- The agent concentration selected for a total-flooding system, at or above the minimum extinguishing concentration for the hazard class and, for Class C, at or below the NOAEL.
- Hold time
- The period during which the design concentration is maintained in the protected enclosure after discharge, allowing occupant egress and preventing re-ignition; typically at least 10 minutes.
- FM-200 NOAEL
- HFC-227ea (FM-200) has a NOAEL of 9.0 percent by volume. Class C designs must not exceed 9.0 percent, and occupied-space exposure must stay below that level.
- Inergen NOAEL
- IG-541 (Inergen) has a NOAEL of 43 percent by volume. Class C designs must not exceed 43 percent, and Class B designs commonly reach that limit.
- Novec 1230 NOAEL
- FK-5-1-12 (Novec 1230) has a NOAEL of 10 percent by volume, well above typical Class A and Class B design concentrations of roughly 4.2 to 5.85 percent.
- CO2 total-flooding restriction
- Carbon dioxide total-flooding systems are prohibited in occupied spaces because the design concentration is lethal. They are permitted only in unoccupied areas with lockout and pre-discharge alarm.
- Pre-discharge alarm
- A distinctive alarm required before clean agent discharge in occupied areas, paired with a time delay (commonly 30 seconds) to allow occupants to egress safely.
- Abort station
- A manual device that stops the pre-discharge timer and prevents agent release, typically located at the egress door and permitted only where the hazard does not require immediate discharge.
- Halocarbon agent formula
- NFPA 2001 agent quantity: W = (V/S) x (C/(100-C)), where W is mass, V is enclosure volume, S is specific vapor volume at design temperature, and C is design concentration.
- Inert gas agent formula
- Agent mass = (enclosure volume x design concentration x gas density) / (1 - design concentration), with altitude correction applied to the enclosure volume for inert-gas systems.
- Class C hazard
- An energized electrical or electronic hazard. Clean agent design concentration for Class C must not exceed the NOAEL, and the agent must be non-conductive.
- Class B hazard
- A flammable liquid or gas hazard. Clean agent design concentrations for Class B are typically higher than Class A and are set by the minimum extinguishing concentration plus a safety factor.
- Class A hazard
- An ordinary combustible hazard such as paper or wood. Clean agent design concentrations for Class A are typically the lowest of the three classes, commonly 6.25 to 7.0 percent for FM-200.
- Total-flooding system
- A system that discharges agent into an enclosure to achieve and maintain a design concentration throughout the protected volume, requiring a sealed enclosure and pressure relief venting.
- Pressure relief vent
- A vent sized to relieve the overpressure created by agent discharge in a sealed enclosure, preventing structural damage while maintaining the design concentration hold time.
- Enclosure integrity test
- A door-fan or equivalent test that measures enclosure leakage to confirm the space can hold the design concentration for the required hold time before system acceptance.
- Clean agent
- A non-conductive, electrically non-conducting, volatile extinguishing agent that leaves no residue, such as FM-200, Novec 1230, or Inergen, used for total-flooding applications.
- Halocarbon agent
- An agent containing carbon and halogen atoms, such as HFC-227ea or FK-5-1-12, that extinguishes primarily by absorbing heat and interrupting the combustion chain.
- Inert gas agent
- An agent such as IG-541, IG-55, or IG-01 that extinguishes by reducing oxygen concentration below the level supporting combustion while remaining breathable at design concentration.
- Specific vapor volume (S)
- The volume occupied by a unit mass of agent vapor at the design temperature, used in the NFPA 2001 halocarbon agent quantity formula to convert enclosure volume to agent mass.
- Discharge nozzle
- A device that distributes agent uniformly throughout the protected enclosure; nozzle type, spacing, and elevation are selected from the manufacturer's listed design manual.
- Piping hydrostatic test
- A pressure test of the agent piping at a pressure above the design working pressure, performed before acceptance to confirm the piping and fittings will contain the discharge.
- Detection cross-zoning
- A design where two independent detectors must both alarm before agent discharge, reducing false discharges; the arrangement is defined by the system design and listing.
- Clean agent cylinder storage
- Agent cylinders must be stored within the listed temperature range, secured against movement, and located where ambient temperature does not cause overpressurization or under-discharge.
- Weighing agent cylinders
- The primary method to verify halocarbon agent quantity in the field: compare cylinder weight to the stamped fill weight, since pressure gauges do not reliably indicate agent loss.
- NFPA 2001
- The standard for clean agent fire extinguishing systems, covering design concentration, agent quantity, hold time, enclosure integrity, and occupant safety requirements.
- NFPA 12
- The standard for carbon dioxide extinguishing systems, covering total-flooding, local application, and CO2 restrictions for occupied spaces.
- NFPA 12A
- The standard for halon 1301 fire extinguishing systems, covering design, installation, and the phase-out and recycling requirements for halon agents.
- NFPA 750
- The standard for water mist fire protection systems, covering design, installation, and acceptance testing for water mist systems used on special hazards.
- NFPA 2010
- The standard for fixed aerosol extinguishing systems, covering design, installation, and the limitations of condensed and dispersed aerosol agents for special hazards.