NEC Architecture · Keep the key ideas within reach.

Quick reference

General Requirements and Administration

  • Article 100 definitions: 'Approved' means acceptable to the AHJ; 'Listed' means equipment evaluated by a NRTL and included in a published list.

  • 90.4: The AHJ has final interpretation and may grant exceptions; enforcement is the AHJ's responsibility.

  • 110.3(B): Equipment must be installed and used in accordance with its listing and labeling instructions.

  • 110.12: Work must be performed in a neat and workmanlike manner; unused openings must be closed.

  • 110.26(A): Working space depth in front of electrical equipment is 3 ft (0–150 V to ground), 3.5 ft (151–600 V), 4 ft (601–1000 V), or greater for higher voltages, based on Table 110.26(A)(1).

  • 110.26(B): Working space must be clear and not used for storage.

  • 110.26(C)(2): For equipment over 1200 A or over 6 ft wide, provide one entrance at each end, or a single entrance if the equipment is accessible from only one end.

  • 110.27: Guard live parts operating at 50 V or more against accidental contact.

  • Article 200: Grounded conductors must be identified by white or gray finish, or by three continuous white stripes on other than green insulation.

Quick reference

Wiring and Protection

  • 210.52(A)(1): Receptacles must be spaced so that no point along the floor line in any wall space is more than 6 ft from a receptacle outlet.

  • 210.52(C): Kitchen countertop receptacles: no point along the counter wall line more than 24 in. from a receptacle; at least one receptacle per island or peninsular counter space.

  • 210.8(A): GFCI protection is required for 125-V, 15- or 20-A receptacles in dwelling unit bathrooms, garages, outdoors, kitchens, laundry areas, and within 6 ft of sinks, among other locations.

  • 210.12(A): Arc-fault circuit-interrupter protection is required for 120-V, 15- or 20-A branch circuits supplying dwelling unit bedrooms, living rooms, and similar areas.

  • 220.12: Lighting load for dwelling units is 3 VA per square foot; for other occupancies, use Table 220.12.

  • 220.82: Optional feeder/service calculation for dwelling units: 100% of first 10 kVA plus 40% of remaining load, plus 100% of largest motor.

  • 230.42: Service-entrance conductors must have ampacity not less than the load and not less than the service disconnect rating.

  • 240.4(D): Small conductor overcurrent protection limits: 14 AWG copper-15 A; 12 AWG-20 A; 10 AWG-30 A (unless otherwise permitted).

  • 250.52(A): Grounding electrodes include metal water pipe (10 ft or more in contact with earth), metal frame of building, concrete-encased electrode, ground ring, rod/pipe electrode, and plate electrode.

Quick reference

Wiring Methods and Materials

  • 300.4: Conductors must be protected from physical damage where passing through framing members; use nail plates or bushings as required.

  • 310.15(B)(3)(a): Adjustment factors for more than three current-carrying conductors in a raceway or cable: 4–6 conductors = 80%; 7–9 = 70%; 10–20 = 50%.

  • 310.15(B)(2): Ambient temperature correction factors apply to conductor ampacity based on Table 310.15(B)(2)(a).

  • 334.80: NM cable ampacity must be limited to the 60°C column of Table 310.16, and the 90°C rating may be used only for derating purposes.

  • 352.30: PVC conduit must be supported at intervals not exceeding 3 ft, and within 3 ft of boxes and fittings.

  • 358.30: EMT must be securely fastened within 3 ft of each box and supported at intervals not exceeding 10 ft.

  • 376.30: Metal wireways must be supported at intervals not exceeding 5 ft and within 3 ft of each end.

  • 404.8(A): Switches and circuit breakers must be readily accessible and installed so that the center of the grip of the operating handle is not more than 6 ft 7 in. above the floor.

  • 406.4(D): Replacement receptacles must be GFCI-protected where required by 210.8, and tamper-resistant where required by 406.12.

Quick reference

Equipment for General Use

  • 422.16(B)(2): Kitchen countertop appliances may be cord-and-plug connected; the receptacle must be accessible and the cord length must not exceed 2 ft.

  • 430.52: Motor branch-circuit short-circuit and ground-fault protection: use Table 430.52 percentages; if the standard size does not allow starting, the next higher size may be used.

  • 430.22: Motor branch-circuit conductors must have ampacity not less than 125% of the motor full-load current.

  • 440.32: Air-conditioning branch-circuit conductors must have ampacity not less than 125% of the rated-load current.

  • 450.3(B): Transformer overcurrent protection: primary protection at not more than 125% of primary current for transformers over 1000 V, or as specified in Table 450.3(B).

  • 680.26: Equipotential bonding is required for pools, including bonding of metal parts, conductive pool shells, and perimeter surfaces within 3 ft.

  • 690.7: Maximum PV system voltage is the sum of the rated open-circuit voltages of the modules corrected for the lowest expected ambient temperature.

  • 695.4: Fire pump disconnecting means must be installed ahead of other building loads and be marked 'Fire Pump'.

Quick reference

Special Occupancies

  • 511.3: Commercial garages: areas within 18 in. of the floor are Class I, Division 2; areas above 18 in. are unclassified unless specified.

  • 514.3: Motor fuel dispensing facilities: areas within 18 in. of the floor and within 20 ft of dispensers are classified.

  • 517.13: Health care facilities: patient care areas require redundant grounding using an insulated copper equipment grounding conductor and a metal raceway or cable armor.

  • 518.4: Assembly occupancies: fixed wiring must be in metal raceways or metal-clad cables, or listed plenum cables where required.

  • 525.11: Carnivals, circuses, and fairs: receptacles must be GFCI-protected and have covers.

  • 547.5: Agricultural buildings: equipotential planes are required in concrete slabs and at metallic water system connections.

  • 550.4: Mobile homes: the frame must be bonded to the grounding electrode system and the equipment grounding conductor.

  • 555.9: Marinas and boatyards: shore power receptacles must be GFCI-protected and located not less than 6 ft above the deck.

Quick reference

Special Equipment

  • 620.21: Elevator traveling cables must be supported at intervals not exceeding 6 ft and be listed for the purpose.

  • 625.40: Electric vehicle supply equipment (EVSE) branch circuits must be supplied by a separate circuit and protected by a GFCI breaker if required.

  • 630.11: Welding receptacle outlets must have a rating not less than the rating of the welder and be protected by a time-delay fuse or circuit breaker.

  • 645.4: Information technology equipment rooms: disconnecting means must be provided and clearly marked.

  • 680.22: Pool receptacles must be located not less than 6 ft from the inside wall of the pool and be GFCI-protected.

  • 700.12: Emergency system battery capacity must be sufficient for 1.5 hours of operation at full load.

  • 701.12: Legally required standby systems must have an alternate power source that can supply the load within 60 seconds.

  • 702.11: Optional standby systems must have a transfer switch that prevents inadvertent interconnection with the normal supply.

Quick reference

Special Conditions

  • 700.5: Emergency systems must be capable of supplying the load for at least 1.5 hours.

  • 701.6: Legally required standby systems must be capable of supplying the load for the duration of the outage.

  • 702.5: Optional standby systems must be sized to supply the selected loads.

  • 705.12(D)(2): Busbars in panelboards used for backfed power must have a rating not less than 120% of the sum of the overcurrent devices supplying them.

  • 705.12(D)(3): The sum of the ampere ratings of all overcurrent devices on panelboards, both load and supply devices, excluding the main overcurrent device, must not exceed 120% of the busbar rating.

  • 706.10: Energy storage systems must be listed and installed per manufacturer instructions; a disconnecting means must be provided.

  • 708.10: Critical operations power systems (COPS) must be designed so that a single fault does not cause loss of power to the critical load.

  • 712.10: Stand-alone systems must have a disconnecting means to isolate the system from the premises wiring.

Quick reference

Communications Systems

  • 800.24: Communications cables must be supported at intervals not exceeding 4 ft and within 12 in. of boxes.

  • 800.110: Communications cables must be installed in raceways or be listed for the purpose; plenum cables must be used in environmental air spaces.

  • 820.25: Coaxial cables must be bonded to the grounding electrode system using a listed grounding conductor.

  • 830.11: Network-powered broadband cables must be listed and marked; they must not be installed in the same raceway as power conductors unless separated by a barrier.

  • 840.4: Optical fiber cables must be listed for the application; nonconductive cables may be installed without grounding.

  • 800.154: Communications cables must be protected from physical damage where exposed to damage.

  • 820.100: Coaxial cable shields must be bonded to the grounding electrode system at the point of entry.

  • 830.40: Network-powered broadband cables must be installed in accordance with Article 830 and be listed as plenum, riser, or general-purpose.

Quick reference

Tables and Annexes

  • Table 310.16: Ampacities of insulated conductors rated 0–2000 V; use 60°C column for NM cable per 334.80.

  • Table 250.66: Grounding electrode conductor sizing based on service-entrance conductor size; for 2 AWG or smaller, use 8 AWG copper.

  • Table 250.122: Equipment grounding conductor sizing based on overcurrent device rating; for 15–20 A, use 14 AWG copper.

  • Table 430.248: Full-load currents for single-phase AC motors; use for motor branch-circuit calculations.

  • Table 220.42: Lighting load demand factors for dwelling units: first 3000 VA at 100%, next 117,000 VA at 35%, remainder at 25%.

  • Table 220.55: Demand factors for household electric ranges; for one range up to 12 kW, demand is 8 kW.

  • Annex D: Examples of load calculations for dwelling units and other occupancies.

  • Annex C: Conduit fill tables for conductors of the same size and type.

Quick reference

Plan Review and Code Application

  • Plan review must verify that the service and feeder calculations comply with Article 220 and that conductor and overcurrent protection sizes are correct.

  • Check that working space around electrical equipment meets 110.26 dimensions for depth, width, and height.

  • Verify that all required GFCI and AFCI protections are shown on the plans for the applicable occupancies.

  • Confirm that grounding and bonding are detailed per Article 250, including grounding electrode conductor sizing from Table 250.66.

  • Ensure that the number and location of receptacles meet 210.52 spacing requirements.

  • Review that wiring methods are suitable for the environment (e.g., wet locations, hazardous locations) per Articles 300 and 500–516.

  • Check that the available fault current at the service is considered for equipment ratings (110.9 and 110.10).

  • Verify that the plans show the proper identification of grounded and equipment grounding conductors.