Working space depth
The minimum clear distance in front of electrical equipment, typically 3 ft for 0–150 V to ground, 3.5 ft for 151–600 V, and 4 ft for 601–1000 V, per Table 110.26(A)(1).
Listed equipment
Equipment that is included in a list published by a nationally recognized testing laboratory (NRTL) and found to meet designated standards.
Receptacle spacing rule
In dwelling units, receptacle outlets must be installed so that no point along the floor line in any wall space is more than 6 ft from a receptacle.
GFCI protection locations
Required for 125-V, 15- or 20-A receptacles in bathrooms, garages, outdoors, kitchens, laundry areas, and within 6 ft of sinks in dwelling units.
AFCI requirement
Arc-fault circuit-interrupter protection is required for 120-V, 15- or 20-A branch circuits supplying dwelling unit bedrooms, living rooms, and similar areas.
NM cable ampacity
Ampacity must be limited to the 60°C column of Table 310.16, and the 90°C rating may be used only for derating purposes.
Conductor adjustment factors
For more than three current-carrying conductors in a raceway, apply factors: 4–6 conductors = 80%, 7–9 = 70%, 10–20 = 50%.
EMT support spacing
EMT must be securely fastened within 3 ft of each box and supported at intervals not exceeding 10 ft.
Motor branch-circuit conductors
Conductors supplying a single motor must have an ampacity not less than 125% of the motor full-load current rating.
Transformer overcurrent protection
Primary overcurrent protection for transformers must be not more than 125% of the primary current, unless otherwise permitted by Table 450.3(B).
Commercial garage classification
Areas within 18 in. of the floor are Class I, Division 2; areas above 18 in. are unclassified unless otherwise specified.
Health care redundant grounding
Patient care areas require an insulated copper equipment grounding conductor and a metal raceway or cable armor for redundant grounding.
Pool receptacle location
Receptacles must be located not less than 6 ft from the inside wall of the pool and be GFCI-protected.
Emergency system battery capacity
Battery capacity must be sufficient for 1.5 hours of operation at full load for emergency systems.
Optional standby transfer switch
A transfer switch must be provided to prevent inadvertent interconnection between the optional standby source and the normal supply.
Busbar 120% rule
The sum of the ampere ratings of all overcurrent devices on a panelboard, both load and supply, excluding the main, must not exceed 120% of the busbar rating.
Communications cable support
Communications cables must be supported at intervals not exceeding 4 ft and within 12 in. of boxes.
Coaxial cable bonding
Coaxial cable shields must be bonded to the grounding electrode system at the point of entry using a listed grounding conductor.
Table 250.66 sizing
Grounding electrode conductor size is based on the service-entrance conductor size; for 2 AWG or smaller, use 8 AWG copper.
Table 220.55 range demand
For one household electric range up to 12 kW, the demand load is 8 kW per Table 220.55.
Plan review working space
Verify that the plans show working space around electrical equipment meeting the depth, width, and height requirements of 110.26.
Available fault current
Equipment must have an interrupting rating or short-circuit current rating not less than the available fault current at the terminals.
Service-entrance conductor sizing
Service-entrance conductors must have ampacity not less than the load and not less than the rating of the service disconnect.
Small conductor protection
Overcurrent protection limits: 14 AWG copper-15 A; 12 AWG-20 A; 10 AWG-30 A, unless otherwise permitted by the Code.
Grounding electrode types
Include metal water pipe (10 ft or more in contact with earth), metal frame of building, concrete-encased electrode, ground ring, rod/pipe electrode, and plate electrode.
PVC conduit support
PVC conduit must be supported at intervals not exceeding 3 ft, and within 3 ft of boxes and fittings.
Switch height
Switches and circuit breakers must be installed so that the center of the grip of the operating handle is not more than 6 ft 7 in. above the floor.
Fire pump disconnecting means
Must be installed ahead of other building loads and be marked 'Fire Pump' to ensure continuous power.
PV system maximum voltage
The maximum PV system voltage is the sum of the rated open-circuit voltages of the modules corrected for the lowest expected ambient temperature.
Assembly occupancies wiring
Fixed wiring must be in metal raceways or metal-clad cables, or listed plenum cables where required.
Elevator traveling cable support
Traveling cables must be supported at intervals not exceeding 6 ft and be listed for the purpose.
Critical operations power systems
COPS must be designed so that a single fault does not cause loss of power to the critical load.