NRCA Modified Bitumen study materials
NRCA Modified Bitumen study resources

NRCA Modified Bitumen flashcards

NRCA Modified Bitumen · Build recall with a focused review session.

32 cards. Read the term and the definition here. The deck at the top of this page is optional.

SBS modifier
Styrene-butadiene-styrene elastomer that gives modified bitumen rubbery, elastic behavior and high elongation, making SBS membranes suited to roofs subject to movement.
APP modifier
Atactic polypropylene plastomer that gives modified bitumen a more rigid, heat-tolerant compound, which is why APP membranes are commonly torch-applied.
Polyester reinforcement
Nonwoven polyester mat used as a membrane carrier; it provides high tear strength and elongation, making it suitable for roofs that experience movement.
Fiberglass reinforcement
Glass mat carrier that gives modified bitumen high tensile strength and dimensional stability but low elongation, so it is less tolerant of substrate movement.
Granule surfacing
Mineral granules applied to the top of a cap sheet to protect the bitumen compound from ultraviolet degradation and provide a walking surface.
ASTM D6164
Product standard for SBS-modified bitumen sheet using polyester reinforcement; it specifies physical properties such as tensile, tear, and low-temperature flexibility.
Roll storage rule
Store rolls upright on pallets, protected from standing water and direct sun; heat deforms SBS rolls and wet or dirty rolls contaminate laps.
Deck deflection limit
Low-slope membrane roofs are designed so the deck deflects no more than L/360 of the span under design load, verified before membrane installation.
Steel deck minimum
Roof steel deck is typically minimum 22 gage, fastened to supports with side laps stitched or fastened per the deck manufacturer's span table.
Vapor retarder placement
Installed on the warm side of the insulation, continuous and sealed at laps and penetrations, to limit moisture migration into the roof assembly.
Minimum roof slope
New low-slope roofs are designed for positive drainage at a minimum of 1/4 in. per foot, or 2 percent, toward drains or scuppers.
Ponding water definition
Water that remains standing on the roof surface more than 48 hours after rain, indicating inadequate slope, deflection, or blocked drainage.
Base sheet attachment
Base sheets are fastened by mechanical fasteners and plates, hot asphalt, cold adhesive, or torch, using the method approved for the deck and wind load.
Typical lap widths
Modified bitumen ply sheets typically use 3 in. side laps and 6 in. end laps, but the membrane manufacturer's printed instructions always govern.
Shingle-fashion ply layout
Each ply is installed lapping over the previous ply so water drains over the laps, with end laps staggered between plies to avoid buildup.
Hot asphalt temperature
Built-up and modified systems typically use asphalt heated to about 400 to 440 degrees Fahrenheit at the kettle, never above its flash point.
Overdriven fastener
A fastener set below the deck surface or with a crushed plate; it is a defect that reduces uplift resistance and must be replaced.
Torch lap indicator
A continuous bead of molten asphalt visible at the lap edge shows the sheet was heated enough to bond; glossy or charred compound indicates burnout.
Hot asphalt embedding
The membrane is laid into a mopped or applied layer of ASTM D312 Type III or IV asphalt at proper temperature, then broomed to remove air.
Cold adhesive application
Adhesive is applied with a notched trowel or spray, allowed to reach open time, and the sheet is rolled in; laps may need lap adhesive or sealant.
Self-adhered application
Substrate is primed and dried to touch, release film is removed progressively, and the sheet is pressed with a weighted roller for full contact.
Sheet orientation
Granule-surfaced cap sheets face up for UV protection, while sanded or film-surfaced sides face down to receive the bonding bitumen.
Base flashing height
Wall base flashing typically extends a minimum of 8 in. above the roof surface, terminated in a reglet, counterflashing, or termination bar.
Termination bar spacing
Fasteners through a termination bar are spaced at a maximum of 12 in. on center, with a sealant bead applied over the fastener heads.
Pitch pan use
A flanged metal pan set in membrane adhesive or hot asphalt and filled with sealant, used for clusters of pipes and irregular penetrations.
Drain flange stripping
The drain flange is set in adhesive or hot asphalt, clamped by the strainer, and stripped with a reinforcing ply at least 6 in. wide.
Hot-work permit
A written authorization required before torch or hot asphalt work, specifying fire watch, extinguisher, combustible clearance, and post-work monitoring.
Combustible clearance
Combustible materials within 35 ft of torch work must be removed or protected, and combustible decking or insulation must be shielded.
Fire watch duration
A fire watch remains on site during torch work and for at least 1 hour after the last torch is shut off, unless local code requires longer.
Fishmouth repair
An open lap or fishmouth is cut back to sound membrane and patched with new membrane extending at least 6 in. beyond the cut.
Blister repair
The blister is cut open, the area dried, and a patch installed extending at least 6 in. beyond the cut; widespread blistering may require replacement.
Fire classification
Roof assemblies are rated Class A, B, or C under ASTM E108 or UL 790; Class A is often required where the roof is over a combustible deck.