Level 2 energy audit
An energy survey that breaks facility use into end uses, establishes an energy balance, and identifies and costs energy conservation measures with savings estimates and payback.
Audit baseline period
The reference period of typically 12 consecutive months used to characterize normal energy use, adjusted for occupancy, weather, and major facility changes.
IPMVP Option C
A measurement and verification approach using whole-facility utility meter data with routine and non-routine adjustments to determine savings from a multi-measure retrofit.
Energy use intensity
Annual site energy consumption divided by conditioned floor area, usually expressed in kBtu per square foot, used to benchmark a building against peers.
Balance-point temperature
The outdoor temperature at which internal gains offset envelope losses so no heating is needed, often 55 to 65 degrees Fahrenheit rather than the standard 65.
Load factor
Average load divided by peak load over a period; a low value indicates demand charges may dominate the bill and demand management is worthwhile.
Weather normalization regression
A regression of monthly energy against heating or cooling degree days whose slope gives weather sensitivity and whose intercept gives weather-independent baseload.
Three-phase power formula
Real power in watts equals the square root of three times line voltage times line current times power factor for a balanced three-phase load.
Pitot tube velocity
Duct air velocity in feet per minute equals 1,096 times the square root of velocity pressure measured in inches of water column.
Interval data logging
Recording measurements at fixed short intervals, typically 15 minutes, to capture load profiles, duty cycles, and peak demand rather than single spot readings.
Simple payback period
Initial measure cost divided by annual energy cost savings, expressed in years; it ignores time value of money and measure life.
Levelized cost of conserved energy
Annualized capital cost of an efficiency measure divided by its annual energy savings, compared against the marginal cost of purchased energy.
Demand charge
A utility billing component based on the highest kilowatt demand in a billing period, often with a ratchet that sets a floor for future months.
Internal rate of return
The discount rate at which a project's net present value equals zero; projects are accepted when it exceeds the owner's hurdle rate.
Lumen method
Illuminance equals lamp lumens times fixture count times coefficient of utilization times light loss factor, divided by the area served.
Lighting power density
Connected lighting watts divided by floor area in watts per square foot, compared against code allowances for the space type.
Ballast factor
The ratio of lamp light output with a given ballast to rated output with a reference ballast; it also scales input wattage.
Chiller efficiency in kW per ton
Chiller input power divided by cooling output in tons; COP equals 3.517 divided by kW per ton.
Affinity laws
For centrifugal fans and pumps, flow varies with speed, pressure with speed squared, and shaft power with speed cubed.
Economizer
A control strategy that uses cool outdoor air for free cooling when outdoor air enthalpy or dry-bulb conditions are favorable compared with return air.
Demand-controlled ventilation
Modulating outdoor air intake based on measured occupancy, typically carbon dioxide concentration, to reduce conditioning of excess ventilation air.
Domestic hot water energy
Energy in Btu equals gallons times 8.33 pounds per gallon times the temperature rise in Fahrenheit degrees, divided by system efficiency.
Heat pump water heater
A water heater using a vapor compression cycle with a coefficient of performance of roughly two to three, requiring conditioned air and condensate drainage.
Legionella temperature control
Storing hot water at 140 degrees Fahrenheit with a mixing valve, or at 120 degrees, to avoid the 68 to 122 degree range where bacteria thrive.
Compressed air rule of thumb
About one horsepower of compressor power produces four to five cubic feet per minute of air at 100 psig in a typical system.
Compressed air leak load
The compressor output consumed by leaks, often 20 to 30 percent of total output, quantified by measuring run time during non-production hours.
Motor input power
Kilowatts equal horsepower times 0.746 divided by motor efficiency at the actual load point, not nameplate rating.
Envelope heat transfer
Heat flow in Btu per hour equals the assembly U-value times area times the indoor-outdoor temperature difference, plus infiltration losses.
Blower door test
A diagnostic that pressurizes a building to measure leakage at 50 pascals, used to estimate natural infiltration and target air sealing.
BAS trend review
Analysis of logged building automation data, typically at 15-minute intervals, to find scheduling overrides, stuck valves, and simultaneous heating and cooling.
BACnet protocol
A standard data communication protocol for building automation and control networks that allows devices from different vendors to interoperate.
Battery round-trip efficiency
The ratio of energy discharged to energy charged, typically 85 to 95 percent for lithium-ion systems, affecting storage economics.