Hazen-Williams formula
Friction loss per foot = 4.52 Q^1.85 / (C^1.85 × d^4.87), where Q is flow in gpm, d is internal pipe diameter in inches, and C is the roughness coefficient.
Sprinkler K-factor
The discharge coefficient relating flow to pressure: flow (gpm) = K × √P (psi). Common K-factors are 5.6, 8.0, 11.2, 14.0, and 25.2.
Remote area reduction
NFPA 13 permits reducing the remote area by 25% for dry systems, 30% for double-interlock preaction, and up to 40% for quick-response sprinklers in light hazard.
Design density
The minimum water flow rate per square foot (gpm/ft²) applied over the remote area, selected from NFPA 13 based on hazard classification and ceiling height.
Light hazard spacing
Maximum sprinkler spacing is 15 feet between sprinklers and 225 square feet per sprinkler for light hazard occupancies, per NFPA 13.
Deflector clearance
Minimum 1 inch below ceiling for standard spray sprinklers; 18 inches below noncombustible ceilings for extended coverage; 12 inches below combustible ceilings for ESFR.
Sprinkler temperature ratings
Ordinary: 135–170°F (orange/red); intermediate: 175–225°F (yellow/green); high: 250–300°F (blue); extra high: 325–375°F (purple); ultra high: 400–650°F (black).
Main drain test
A flow test at the riser to verify water supply and detect obstructions; compare static and residual pressures; a drop exceeding 10% from baseline indicates a problem.
Fire pump churn pressure
The pressure developed by a fire pump at zero flow; for centrifugal pumps, churn pressure must not exceed 140% of rated head.
Standpipe Class I
A standpipe system with 2-1/2-inch outlets intended for fire department use, requiring 100 psi residual pressure at the topmost outlet.
Fire pump flow test
Annual test at 100%, 150%, and churn flow; verify pump performance curve: at 150% flow, pressure must be at least 65% of rated head.
Backflow preventer loss
A reduced pressure zone (RPZ) backflow preventer typically causes a 5–10 psi pressure loss that must be included in hydraulic calculations.
Weekly inspection tasks
Inspect gauges for normal pressure, test alarm valves if not monitored, check diesel fuel level and battery condition, and verify valve positions.
Sprinkler spare stock
Minimum spare sprinklers: 6 for systems up to 300 sprinklers, 12 for 300–1000, and 24 for over 1000; include a sprinkler wrench.
5-year internal inspection
NFPA 25 requires internal inspection of piping and sprinklers in dry systems every 5 years, and replacement of dry-pipe sprinklers every 10 years.
Obstruction investigation
Required when a main drain test shows a pressure drop exceeding 10% from baseline, or when sprinkler discharge is visibly reduced.
Nevada C-41 license
Nevada State Contractors Board classification for fire protection systems, with no monetary limit; requires 4 years experience, exams, and a $10,000 bond.
Mechanic's lien deadline
In Nevada, file a preliminary notice within 31 days of first furnishing labor or materials; record the lien within 90 days after completion.
Continuing education requirement
Nevada contractors must complete 16 hours of continuing education every two years for license renewal, including at least 4 hours on business practices.
Nevada prompt payment
Owner must pay contractor within 30 days of invoice; if not, contractor may stop work after providing 10-day written notice.
Clark County sprinkler requirement
Clark County requires fire sprinkler systems in all new commercial buildings and residential occupancies with more than two dwelling units, regardless of area.
High-rise sprinkler threshold
Nevada requires automatic sprinkler systems in high-rise buildings, defined as 75 feet or more in height, per state fire marshal amendments.
Fire flow duration
Nevada adopts IFC Appendix B: minimum fire flow for light hazard is 1,500 gpm for 2 hours; for ordinary hazard, 2,000 gpm for 2 hours.
Plan review submission
Submit fire sprinkler plans to the local fire authority having jurisdiction and building department; approval is required before installation begins.
Fall protection threshold
OSHA requires fall protection when working at heights of 6 feet or more; use guardrails, safety nets, or personal fall arrest systems.
Hydrostatic test pressure
New sprinkler systems must be hydrostatically tested at 200 psi for 2 hours, or 50 psi above maximum working pressure, whichever is greater.
As-built drawings
Final drawings reflecting actual installed conditions, including pipe sizes, sprinkler locations, and revisions; required for owner and AHJ records.
Job hazard analysis
A documented process to identify potential hazards for each task and define controls before work begins, required for safety compliance.
NFPA 13R design density
Residential sprinkler systems use lower design densities, such as 0.05 gpm/ft² over four sprinklers, with a 10-minute duration, and are limited to 4 stories.
ESFR sprinkler criteria
Early Suppression Fast Response sprinklers are for storage occupancies up to 45 feet ceiling height, with design density 0.35–0.7 gpm/ft² and 12 sprinklers flowing.
Clean agent hold time
NFPA 2001 requires a 10-minute hold time for clean agent systems in occupied spaces, verified by a room integrity test.
Kitchen hood suppression
NFPA 96 requires wet chemical suppression systems for commercial cooking hoods, with semi-annual inspection and cleaning, and automatic fuel shutoff.