NFPA 13
The primary standard for design and installation of automatic sprinkler systems; it does not govern ongoing inspection, testing, and maintenance.
NFPA 25
Standard for inspection, testing, and maintenance of water-based fire protection systems; it sets frequencies and records for valves, gauges, alarms, and drains.
Authority having jurisdiction
Authority having jurisdiction; the official or agency that reviews plans, issues permits, conducts inspections, and enforces the adopted fire code.
Sprinkler discharge formula
Q equals K times the square root of pressure, where Q is flow in gpm, K is the sprinkler discharge coefficient, and P is pressure in psi.
Density-area method
Design density in gpm per square foot multiplied by the remote design area in square feet gives the required sprinkler flow before hose and other demands.
Hazen-Williams formula
Estimates friction loss in water-filled pipe using flow, internal diameter, and a C factor; in US units the constant is 4.52 for psi per foot.
Water supply curve
A plot of available pressure versus flow at the system connection; the demand point must fall below or on the curve with all adjustments applied.
Wet-pipe system
A sprinkler system with water in the piping at all times; it is the simplest and fastest-acting type where freezing is not a concern.
Dry-pipe system
Uses compressed air or nitrogen to hold a dry-pipe valve closed; water enters after a sprinkler opens and pressure drops, so design area is increased.
Deluge system
Open sprinklers or nozzles discharge together when detection operates a deluge valve; used where rapid application over an area is needed.
K-factor
Sprinkler discharge coefficient in gpm per square root psi; a larger K produces more flow at the same pressure and affects required pressure.
Quick-response sprinkler
Sprinkler with a fast-responding thermal element; response rating is separate from temperature rating and may affect design area allowances.
Alarm check valve
A wet-pipe valve that opens to supply water and directs a portion of flow to an alarm line when a sprinkler operates.
Grooved coupling
Mechanical pipe joint using rolled or cut grooves and a gasket housed in a coupling; must be listed for fire protection and installed to the manufacturer's torque.
Dielectric union
Fitting that separates dissimilar metals to reduce galvanic corrosion; commonly used where steel meets copper or brass in sprinkler piping.
Thrust restraint
Method of resisting unbalanced pressure forces at underground fittings and bends using blocking, restrained joints, or tie rods.
Sway bracing
Seismic restraint that limits lateral or longitudinal pipe movement; bracing type, spacing, and attachment depend on the adopted seismic provisions.
Hanger rod
Vertical support rod that carries sprinkler pipe from building structure; rods must be sized, attached, and not bent or damaged.
Seismic separation assembly
Flexible arrangement at building expansion or seismic joints that allows independent movement without damaging sprinkler piping.
Fire pump churn
Pump operating at shutoff or no-flow condition; NFPA 20 limits shutoff pressure to a percentage of rated head and requires relief protection.
Jockey pump
Small pump that maintains system pressure and prevents main fire pump from starting on minor leaks; it is not a fire pump substitute.
Anti-vortex plate
Device in a water storage tank that prevents air from being drawn into the fire pump suction as the water level drops.
Approved working plans
Plans and calculations stamped approved by the authority having jurisdiction; they must be available on site and changes require reapproval.
Rough-in inspection
Inspection of concealed sprinkler piping, hangers, and components before ceiling or wall closure; approval is needed before concealment.
Record of completion
Document signed by the installing contractor and owner listing system details, tests, and approvals; it is part of the acceptance record.
Hydrostatic test
Pressure test of sprinkler piping, commonly 200 psi for two hours or 50 psi above working pressure when higher, with no leaks.
Main drain test
Flow test through the main drain that indicates water supply and valve condition; results are compared with previous baseline readings.
Dry-pipe trip test
Test that simulates sprinkler operation to verify the dry valve trips and water reaches the test connection within the required time.
NFPA 25 annual inspection
Yearly check of gauges, valves, alarm devices, and waterflow alarms; specific components have monthly, quarterly, or five-year frequencies.
Lockout/tagout
Procedure that isolates hazardous energy before maintenance; it protects workers from unexpected startup or release of pressure and electricity.
Hot work permit
Written authorization for cutting, welding, or soldering; it defines fire watch, combustible clearance, and post-work monitoring.
Impairment coordinator
Person responsible for managing a fire protection impairment, notifying affected parties, and arranging fire watch or alternate protection.